EPA v. Butterball LLC-Huntsville, AR-GDC RMP AOC-FY2020
Final Order No Penalty
Case summary
Respondent's failure to identify the proximity of the roof top ammonia vent and the air intake for the air handler as a hazard and either physically relocate or add administrative controls to prevent ammonia intake by air intake equipment while ammonia venting constitutes a violation of Section 112(r)(7) of the CAA, 42 U.S.C. 7412(r)(7), and the implementing regulations found at 40 CFR 68.67(c).
Defendants (1)
- Butterball LLCNamed in complaintNamed in settlement
Facilities (2)
BUTTERBALL LLC - HUNTSVILLE FACILITY
1294 NORTH COLLEGE AVENUE, HUNTSVILLE, AR, 72740
Registry ID: 110030906143
BUTTERBALL LLC - HUNTSVILLE FACILITY
1294 NORTH COLLEGE AVENUE, HUNTSVILLE, AR, 72740
Registry ID: 110030906143
Statutes cited
- CAA 112[R][1] — Prevention of Accidental Release/General Duty Clause
- CAA 112[R][7] — Prevention of Accidental Release/Risk Management Plans (RMPs)
Enforcement conclusions (1)
Butterball LLC-Huntsville, AR-GDC RMP AOC-FY2020entered 2019-11-07
Primary law: CAA
Timeline (6 milestones)
- 2019-11-06Complaint Filed/Proposed Order
- 2019-11-07Final Order Issued
- 2019-11-15Enforcement Action Data Entered
- 2020-05-01Compliance Achieved
- 2020-05-01Air Resolved
- 2020-05-11Enforcement Action Closed
Case metadata
- EPA activity ID
- 3602044295
- Case number
- 06-2019-3345
- Lead agency
- EPA
- Branch
- ECDAC
- EPA region
- 06
- Voluntary self-disclosure
- No
- Primary statute
- Prevention of Accidental Release/General Duty Clause
Sourced verbatim from EPA ECHO Enforcement Case Report for case 06-2019-3345 . Bulk data: ICIS-FEC download summary.
This is legal information, not legal advice. Laws vary by jurisdiction and change frequently. Always verify current law with official sources and consult a licensed attorney in your jurisdiction for advice on your specific situation.