Skip to main content
05-1988-0270Administrative - FormalClosedFY 1988· Region 05

EPA v. RENSSELAER, CITY OF

Source Agrees

Case summary

COMPLAINT ALLEGES VIOLATION OF SECTION 15 OF TSCA AND 40 CFR SECTION 761.180(A) FOR FAILURE TO DEVELOP AND MAINTAIN ANNUAL DOCUMENT; 40 CFR SECTION 761.30 FOR FAILURE TO REGI- STER WITH FIRE PERSONNEL; FOR STORING COMBUSTIBLE MATERIALS WITHIN 5 METERS OF A PCB TRANSFORMERS, AND FOR FAILURE TO DEVELOP AND MAINTAIN RECORDS OF QUARTERLY INSPECTIONS; 40 CFR SECTION 761.65(A) FOR FAILUTE TO DISPOSE OF PCB TRANS- FORMERS AND PCB FLUID WITHIN 1 YEAR OF THE DATE THEY WERE PLACED IN STORAGE FOR FOR DISPOSAL; AND 40 CFR SECTION 761. 40 FOR FAILURE TO MARK THE ACCESS DOORS TO ITS PCB TRANS- FORMERS WITH THE ML LABEL.

Facilities (1)

  • RENSSELAER CITY OF ELEC DEPT

    125 S VAN RENSSELAER, RENSSELAER, IN, 47978

    Registry ID: 110064127699

Statutes cited

  • TSCA 6-PCBSPCBS

Timeline (4 milestones)

  • 1988-09-19Enforcement Action Data Entered
  • 1988-09-19Complaint Filed/Proposed Order
  • 1989-04-05Final Order Issued
  • 1989-04-05Enforcement Action Closed

Case metadata

EPA activity ID
26966
Case number
05-1988-0270
Lead agency
EPA
HQ division
TOX
EPA region
05
Multimedia
No
Voluntary self-disclosure
No
Primary statute
PCBS

Sourced verbatim from EPA ECHO Enforcement Case Report for case 05-1988-0270 . Bulk data: ICIS-FEC download summary.