Skip to main content
02-2019-7701Administrative - FormalClosedFY 2019· Region 02

EPA v. The United States Postal Service

Final Order With Penalty

Case summary

During the May 10, 2018 inspection of the Albany facility, the piping leak sensor in the tanktop sump of the facility's 1,000-gallon motor oil UST was lying on its side. This violation was corrected. During the February 28, 2018 inspection of the Bellmawr facility, the Respondent provided the latest 3-year CP test, conducted in May 2015, of the sacrificial anodes protecting the Bellmawr facility's two 10,000-gallon fuel USTs, which included no remote readings and no diagram of testing locations as required by the Respondent's April 23, 2018 response to EPA's March 12, 2018 issuance of its inspection report, Steel Tank Institute (STI). In the Respondent's response, a diagram showing the field testing locations obtained from their vendor who conducted the May 2015 CP survey, was attached. However, the remote locations in the diagram are parallel to the line of the tanks, not perpendicular, as required by STI to assess the cathodic protection afforded to the bottom of the tanks. In addition, the vendor provided no remote readings.

Defendants (1)

  • The United States Postal ServiceNamed in complaintNamed in settlement

Facilities (2)

  • ALBANY VMF

    30 OLD KARNER ROAD, ALBANY, NY, 12288

    Registry ID: 110004325677

  • US POSTAL SERVICE

    421 BENIGNO BOULEVARD, BELLMAWR, NJ, 08031-2520

    Registry ID: 110006867177

Statutes cited

  • RCRA 9006AUnderground Storage Tanks Compliance Order

Enforcement conclusions (1)

  • The United States Postal Serviceentered 2019-04-18

    Primary law: RCRA

    Federal penalty: $1,870

Timeline (4 milestones)

  • 2019-04-18Final Order Issued
  • 2019-04-18Enforcement Action Closed
  • 2019-04-18Complaint Filed/Proposed Order
  • 2019-07-15Enforcement Action Data Entered

Case metadata

EPA activity ID
3601904533
Case number
02-2019-7701
Lead agency
EPA
EPA region
02
Voluntary self-disclosure
No
Primary statute
Underground Storage Tanks Compliance Order