EPA v. CERSOSIMO INDUSTRIES
Final Order With Penalty
Case summary
On February 12, 2007, approximately 1,700 gallons of fuel oil of was discharged from the boiler, and made its way to the Connecticut River at the Riverside Industrial Center. The spill originated from a filter drain valve on the boiler, spilled on the floor and made its way to an old abandoned boiler blow down pit to a storm drain manhole in the warehouse. Once in the storm drain line it traveled 310 feet to a manhole in another part of the building and then traveled another 230 feet to the Connecticut River. There were no reports of environmental harm as a result of the discharge.
Defendants (1)
- CERSOSIMO INDUSTRIESNamed in complaintNamed in settlement
Facilities (1)
CERSOSIMO INDUSTRIES INC
210 RIVERSIDE DRIVE, BRATTLEBORO, VT, 05302
Registry ID: 110033195067
Statutes cited
- CWA 311B — Oil & Hazardous Substances Discharge
Enforcement conclusions (1)
CERSOSIMO INDUSTRIESentered 2007-11-06
Primary law: CWA
Federal penalty: $5,000
Timeline (4 milestones)
- 2007-10-15Enforcement Action Data Entered
- 2007-11-06Final Order Issued
- 2007-11-06Complaint Filed/Proposed Order
- 2007-11-06Enforcement Action Closed
Case metadata
- EPA activity ID
- 600070300
- Case number
- 01-2008-2007
- Lead agency
- EPA
- EPA region
- 01
- Voluntary self-disclosure
- No
- Primary statute
- Oil & Hazardous Substances Discharge
Sourced verbatim from EPA ECHO Enforcement Case Report for case 01-2008-2007 . Bulk data: ICIS-FEC download summary.
This is legal information, not legal advice. Laws vary by jurisdiction and change frequently. Always verify current law with official sources and consult a licensed attorney in your jurisdiction for advice on your specific situation.