Proposed Rule2026-22396

Pipeline Safety: Amendments to Liquefied Natural Gas Facilities

Primary source

Metadata and text below are from the Federal Register, a public-domain U.S. government work. Always verify the official published version before relying on it for any legal matter.

Published
November 3, 2026

Issuing agencies

Transportation DepartmentPipeline and Hazardous Materials Safety Administration

Abstract

PHMSA proposes updating its regulations for liquefied natural gas (LNG) facilities to incorporate by reference the most recent industry safety standards and to make other changes to account for more than two decades of improvements and technological advancements. This rulemaking also responds to congressional mandates directing PHMSA to integrate risk-based regulatory approaches for certain LNG facilities.

Full Text

<html>
<head>
<title>Federal Register, Volume 91 Issue 211 (Tuesday, November 3, 2026)</title>
</head>
<body><pre>
[Federal Register Volume 91, Number 211 (Tuesday, November 3, 2026)]
[Proposed Rules]
[Pages 69314-69388]
From the Federal Register Online via the Government Publishing Office [<a href="http://www.gpo.gov">www.gpo.gov</a>]
[FR Doc No: 2026-22396]



[[Page 69313]]

Vol. 91

Tuesday,

No. 211

November 3, 2026

Part II





 Department of Transportation





-----------------------------------------------------------------------





 Pipeline and Hazardous Materials Safety Administration





-----------------------------------------------------------------------





49 CFR Parts 191 and 193





Pipeline Safety: Amendments to Liquefied Natural Gas Facilities; 
Proposed Rule

Federal Register / Vol. 91 , No. 211 / Tuesday, November 3, 2026 / 
Proposed Rules

[[Page 69314]]


-----------------------------------------------------------------------

DEPARTMENT OF TRANSPORTATION

Pipeline and Hazardous Materials Safety Administration

49 CFR Parts 191 and 193

[Docket No. PHMSA-2019-0091]
RIN 2137-AF45


Pipeline Safety: Amendments to Liquefied Natural Gas Facilities

ACTION: Notice of proposed rulemaking (NPRM).

-----------------------------------------------------------------------

AGENCY: Pipeline and Hazardous Materials Safety Administration (PHMSA), 
Department of Transportation (DOT).
SUMMARY: PHMSA proposes updating its regulations for liquefied natural 
gas (LNG) facilities to incorporate by reference the most recent 
industry safety standards and to make other changes to account for more 
than two decades of improvements and technological advancements. This 
rulemaking also responds to congressional mandates directing PHMSA to 
integrate risk-based regulatory approaches for certain LNG facilities.

DATES: Comments on this NPRM must be submitted by January 4, 2027. A 
public meeting of PHMSA's statutory advisory committees will be held on 
a date to be announced in the Federal Register.

ADDRESSES: Submit comments by any of the following methods, identifying 
docket number PHMSA-2019-0091 at the top of the first page:
    <bullet> On <a href="https://www.regulations.gov">https://www.regulations.gov</a>, follow instructions to 
``submit a comment.''
    <bullet> By mail or hand delivery to Docket Management System, U.S. 
Department of Transportation, 1200 New Jersey Avenue SE, Washington, DC 
20590-0001. Hand delivery is available to this address between 9:00 
a.m. and 5:00 p.m., Monday through Friday (except Federal holidays). 
Include two copies if submitting by mail and include a self-addressed 
and stamped postcard to receive confirmation of receipt.
    Comments may be viewed at <a href="https://www.regulations.gov/docket/PHMSA-2019-0091">https://www.regulations.gov/docket/PHMSA-2019-0091</a>. Comments are posted without changes or edits, including any 
personal information provided. DOT's privacy statement can be reviewed 
at <a href="https://www.dot.gov/privacy">https://www.dot.gov/privacy</a>. A plain language summary of the 
proposed rule is also available in section I.B. that is placed on the 
rulemaking docket, pursuant to 5 U.S.C. 553(b)(4).
    Confidential Business Information (CBI): You may designate a 
comment as CBI if your comment contains commercial or financial 
information that is customarily treated as private and that you 
actually treat as private by sending to Brianna Wilson, at the contact 
information listed below, the following: (1) the original document with 
each page containing CBI marked as ``confidential;'' (2) a redacted 
copy with the CBI deleted; and (3) an explanation of why the 
information you are submitting is CBI. See 49 CFR 190.343. Any comment 
not specifically designated as CBI will be placed in the public docket.

FOR FURTHER INFORMATION CONTACT: Brianna Wilson, Standards and 
Rulemaking Division, by phone at (771) 215-0969 or by email at 
<a href="/cdn-cgi/l/email-protection#eb8999828a85858ac59c8287988485ab8f849fc58c849d"><span class="__cf_email__" data-cfemail="5537273c343b3b347b223c39263a3b15313a217b323a23">[email&#160;protected]</span></a>.

SUPPLEMENTARY INFORMATION:

Table of Contents

I. Executive Summary
II. Background
III. Section-by-Section Discussion of the Proposed Changes in Part 
191
IV. Section-by-Section Discussion of the Proposed Changes in Part 
193
V. Regulatory Analyses and Notices

I. Executive Summary

A. Purpose and Scope of the Regulatory Action

    PHMSA has been regulating the safety of LNG facilities for more 
than five decades. When PHMSA issued the first Federal safety standards 
in 1970, the U.S. LNG industry comprised mostly relatively small 
``peak-shaving'' facilities used to liquefy and store natural gas for 
delivery to local markets during times of peak demand. The handful of 
large-scale LNG facilities at that time were primarily built to import 
natural gas for domestic consumption. The U.S. LNG industry did not 
have a significant role as an exporter of natural gas.
    Market conditions have changed dramatically since the 1970s. U.S. 
natural gas production has increased significantly, particularly in the 
past two decades as technological advancements in the oil and gas 
industry have led to the development of energy resources from the 
Nation's shale plays. Domestic natural gas demand has continued to 
grow, and an increasing number of U.S.-based facilities are exporting 
LNG to foreign markets. These changes have created a need for the 
construction of new LNG facilities and for the expansion of existing 
LNG facilities.
    Modern operational and maintenance practices within the LNG 
industry are considerably more sophisticated and robust, reflecting 
many thousands of hours of experience since the 1970s. New technologies 
have emerged, such as ``membrane'' tanks (which employ a thin cryogenic 
steel inner liner with a load-bearing, concrete outer tank--an approach 
offering improved storage capacity, reduced material costs, and faster 
construction schedules than earlier LNG storage tank designs) and pipe-
in-pipe (PIP) transfer systems (which provide enhanced containment of 
releases from cryogenic piping).
    PHMSA's oversight of the LNG industry has not kept pace with these 
dramatic changes. PHMSA's LNG regulations are largely based on the 2001 
edition of an industry standard, NFPA 59A, Standard for the Production, 
Storage, and Handling of Liquefied Natural Gas (LNG), and have not been 
updated since 2006. NFPA 59A-2001 is now seven editions out of date, 
and multiple stakeholders have called on PHMSA to update its 
regulations to account for the latest practices in the siting, design, 
construction, operation, and maintenance of LNG facilities. For 
example, in the Protecting our Infrastructure of Pipelines and 
Enhancing Safety Act of 2016 (PIPES Act of 2016), Congress directed 
PHMSA to develop regulations for permanent, small-scale LNG facilities, 
an issue specifically addressed in the more recent editions of NFPA 
59A.\1\ In the Protecting our Infrastructure of Pipelines and Enhancing 
Safety Act of 2020 (PIPES Act of 2020), Congress directed PHMSA to 
develop alternative, risk-based operations and maintenance requirements 
for large-scale LNG facilities, an approach consistent with modern 
regulatory frameworks that apply in other industries.\2\ The Government 
Accountability Office (GAO) has also advised PHMSA to update its 
regulations to align better with current editions of consensus industry 
standards.\3\
---------------------------------------------------------------------------

    \1\ PIPES Act of 2016, Public Law 114-183 (June 22, 2016).
    \2\ PIPES Act of 2020, Public Law 116-260 (Dec. 27, 2020).
    \3\ GAO, Natural Gas Exports: Updated Guidance and Regulations 
Could Improve Facility Permitting Processes (Aug. 6, 2020) (GAO 
Report).
---------------------------------------------------------------------------

    To address these concerns, PHMSA proposes a comprehensive revision 
to its safety standards for LNG facilities. The proposed amendments 
would enhance public safety by incorporating the latest consensus 
industry standards for the siting, design, construction, operation, and 
maintenance of LNG facilities. These changes will promote the use of 
new technologies, reduce unnecessary barriers to investment, and 
provide regulatory certainty for

[[Page 69315]]

interested stakeholders. PHMSA's proposals will also address 
outstanding Congressional mandates and GAO recommendations and advance 
the President's commitments to unleashing American energy, sustaining 
U.S. defense operations, and ensuring the energy security of the U.S. 
and its allies.

B. Summary of the Major Regulatory Provisions

    Below is a high-level summary of the most substantial changes 
proposed in this document. This NPRM discusses each change in more 
detail in the ``Section-by-Section Discussion of the Proposed 
Changes.''
1. Calibrating Reporting Requirements to Public Safety Risks
    PHMSA proposes to amend the reporting requirements for safety-
related conditions and incidents. First, PHMSA proposes to clarify that 
operators of LNG facilities must report safety-related conditions and 
incidents during initial startup. This clarification would help ensure 
that operators are reporting incidents and safety-related conditions 
that occur at the earliest phase in the operational lifetime of an LNG 
facility, which is critical in determining its long-term integrity. 
PHMSA also proposes to broaden the definition of incidents and safety-
related conditions to encompass hazardous fluids beyond LNG alone; this 
proposed change will improve risk mitigation and incident response by 
focusing on the various materials involved in gas processing activities 
at LNG facilities. Second, PHMSA proposes to revise the incident and 
annual report forms to eliminate content with little or no safety 
value, and to update the operator identification number (OPID) and 
annual report forms to accommodate the new requirements for permanent, 
small-scale LNG facilities in subpart D.
2. Incorporation by Reference Updated Editions of Leading Industry 
Standards
    PHMSA proposes to incorporate by reference the 2026 edition of NFPA 
59A.\4\ PHMSA currently incorporates the 2001 edition of NFPA 59A for 
most purposes. Incorporating the 2026 edition is consistent with 
PHMSA's longstanding practice of integrating NFPA 59A as a key 
component of its regulations for LNG facilities. As part of that 
process, PHMSA proposes to redesignate or to remove certain duplicative 
or unnecessary regulatory requirements and to modify or to supplement 
certain provisions in NFPA 59A-2026 (e.g., design wind resistance of 
certain LNG facilities; design spill assumptions in hazard modeling) to 
accommodate significant public safety risks or to facilitate 
implementation.
---------------------------------------------------------------------------

    \4\ National Fire Protection Association (NFPA), 59A-2026 
Standard for the Production, Storage, and Handling of Liquefied 
Natural Gas (LNG) (Dec. 9, 2025) (NFPA 59A-2026).
---------------------------------------------------------------------------

    Incorporating NFPA 59A-2026 would enhance the requirements for the 
siting, design, installation, construction, operations, and maintenance 
of LNG facilities and align PHMSA's regulations with the latest safety-
enhancing practices and technologies. It would also reduce certain 
compliance costs by allowing LNG operators to use those practices and 
technologies without obtaining special permits or waivers and address 
outstanding Congressional mandates and GAO recommendations.
3. Improved Alignment Between Facility Siting Requirements and Safety 
Risks
    PHMSA proposes to incorporate by reference the traditional, 
prescriptive siting requirements in chapter 5 of NFPA 59A-2026. 
Incorporating chapter 5 would expand the universe of hazards operators 
must evaluate to comply with the part 193, subpart B siting 
requirements, ensuring that those analyses are consistent with current 
knowledge of the public safety risks posed by releases of hazardous 
fluids from LNG facilities.
    PHMSA also proposes to incorporate the new risk-based siting 
requirements in chapter 19 (Performance-Based LNG Plant Siting Using 
Quantitative Risk Analysis (QRA)) of NFPA 59A-2026. PHMSA expects that 
the QRA-based approach will improve facility safety by allowing a more 
sophisticated understanding of public safety risks, enhancing the 
allocation of resources, and incentivizing deployment of innovative 
operational practices and technology. PHMSA expects that improved 
flexibility regarding LNG facility siting and internal layout under the 
QRA-based approach could enable investment in additional capacity at 
existing locations.
4. Introduction of Targeted Requirements for Permanent, Small-Scale LNG 
Facilities
    PHMSA proposes to establish requirements for permanent, small-scale 
LNG facilities by incorporating chapter 17 of NFPA 59A-2026 by 
reference into a new subpart D. Permanent, small-scale LNG facilities 
entail lower risks to public safety and the environment than larger LNG 
facilities, primarily due to their distinguishable liquefaction 
processes, lower liquefaction capacity, and smaller LNG storage 
volumes, and should be regulated accordingly. Incorporating the chapter 
17 requirements would also address the rulemaking mandate in section 
27(b) of the PIPES Act of 2016 for permanent, small-scale LNG 
facilities.
5. Integration of an Alternative, Risk-based Operations and Maintenance 
Framework
    Consistent with section 110 of the PIPES Act of 2020, PHMSA 
proposes to adopt an alternative, risk-based operations and maintenance 
(O&M) program for FERC-jurisdictional LNG facilities in a new subpart 
F. The risk-based O&M alternative would be a structured program with 
procedures developed and implemented to identify, to evaluate, and to 
mitigate or to eliminate hazards and the resulting risks. Operators 
employing this approach would have flexibility to tailor a risk-based 
approach to the specific risks from their facilities. Operators 
electing to use the risk-based O&M alternative would be required to 
submit an implementation plan specifying a timeline for integration of 
program elements.

C. Costs and Benefits

    PHMSA estimates the annualized cost savings from the proposed rule 
to be approximately $98 million (discounted at three percent). PHMSA 
notes that some of the new compliance costs and many of the cost 
savings of the proposed rule could not be quantified based on the 
available data.
    PHMSA anticipates significant unquantified safety benefits would 
result from adopting the safety-enhancing elements of NFPA 59A-2026, as 
supplemented and qualified by other proposed part 193 amendments. 
Because LNG facilities are complex systems whose failure generally 
involves multiple ``but for'' causes, PHMSA was not able to quantify a 
reduction in incident risk pursuant to the proposed rule. Other 
unquantified benefits include increased flexibility for LNG facility 
siting under the QRA-based approach in NFPA 59A-2026 chapter 19, 
increased regulatory flexibility for permanent, small-scale LNG 
facilities subject to the requirements in NFPA 59A-2026 chapter 17, and 
the use of new technologies, such as membrane tanks, single-walled ASME 
(American Society of Mechanical Engineers) containers, and PIP systems, 
which PHMSA was not able to quantify due to uncertainty around 
potential uptake of the proposed flexibilities.
    The preliminary regulatory impact analysis (PRIA) provided in the 
docket for this rulemaking includes additional information about the 
costs, benefits,

[[Page 69316]]

and other impacts of the proposed rule. The PRIA's quantification of 
costs and benefits reflects assumptions and estimates based on the 
information and data available. PHMSA requests information and data 
from the public regarding the PRIA's evaluation of expected costs and 
benefits of its proposed requirements. PHMSA has preliminarily 
determined that, notwithstanding the uncertainties and data limitations 
discussed in the PRIA, the proposals in the NPRM would be justified by 
their corresponding compliance costs savings, enhanced regulatory 
flexibility, or improved public safety benefits.

II. Background

A. LNG as an Energy Source, Industry Growth, and Regulatory Safety

1. LNG as an Energy Source
    Natural gas is vital to the energy and economic security of the 
United States and its allies abroad, serving as an economic driver and 
essential fuel source for residential, commercial, and industrial 
purposes. Total annual U.S. natural gas consumption has increased from 
5.0 Tcf in 1949 to 33.5 Tcf in 2025.\5\ Global natural gas consumption 
similarly is expected to grow from 152.9 Tcf to 194.3 Tcf by 2050 due 
to increasing demand in emerging markets and developing economies.\6\ 
Domestic U.S. and international demand for natural gas has made it an 
important driver of the U.S. economy; a smaller U.S. natural gas sector 
in 2018 contributed over 3.4 million jobs and $408 billion to U.S. 
Gross Domestic Product (GDP).\7\
---------------------------------------------------------------------------

    \5\ U.S. Energy Info. Admin. (EIA), Natural Gas: U.S Gas Total 
Consumption, available at: <a href="https://www.eia.gov/dnav/ng/hist/n9140us2a.htm">https://www.eia.gov/dnav/ng/hist/n9140us2a.htm</a> (last visited Apr. 23, 2026).
    \6\ EIA, International Energy Outlook 2023 Table: World Natural 
Gas Consumption by Region, available at: <a href="https://www.eia.gov/outlooks/aeo/data/browser/#/?id=6-IEO2023&region=0-0&cases=Reference&start=2020&end=2050&f=A&linechart=Reference-d230822.21-6-IEO2023&map=&ctype=linechart&sourcekey=0">https://www.eia.gov/outlooks/aeo/data/browser/#/?id=6-IEO2023&region=0-0&cases=Reference&start=2020&end=2050&f=A&linechart=Reference-d230822.21-6-IEO2023&map=&ctype=linechart&sourcekey=0</a>.
    \7\ Am. Gas Ass'n (AGA), Benefits to the Economy through the 
Direct Use of Natural Gas (July 9, 2020), available at: <a href="https://www.aga.org/research-policy/resource-library/benefits-to-the-economy-through-the-direct-use-of-natural-gas/">https://www.aga.org/research-policy/resource-library/benefits-to-the-economy-through-the-direct-use-of-natural-gas/</a>.
---------------------------------------------------------------------------

    Increased reliance on natural gas from a variety of applications is 
contributing to this growing demand. First, natural gas is a critical 
source of electric power generation capacity and grid stability. In 
addition to providing dispatchable electricity, natural gas electric 
power generation also supplies grid attributes (e.g., inertia) 
increasingly vital to grid stability as more intermittent renewable 
energy generation capacity joins the grid and baseload coal and nuclear 
plants retire. Second, natural gas is essential for many industrial 
feedstock and process heat applications, as well as commercial and 
residential heating and cooking purposes. Third, natural gas is an 
increasingly vital fuel source in the transportation sector, powering 
maritime vessels (i.e., marine bunkering), fueling truck fleets, and 
providing an alternative gas supply during pipeline testing activities.
    But many regions--both within the United States and the wider 
world--do not have reliable access to natural gas. Some regions are 
far-removed from natural gas supply reservoirs; others have limited 
pipeline infrastructure enabling transportation of natural gas in 
gaseous form or are vulnerable to supply interruptions on natural gas 
pipelines. Reliable natural gas supply in such circumstances may turn 
on access to LNG--natural gas that has been cooled to low temperatures 
(minus 260 [deg]F or minus 162 [deg]C) and converted to a liquid state. 
This conversion process, known as liquefaction, reduces the volume of 
natural gas to approximately 1/600th of its volume in a gaseous state. 
The reduction in volume makes LNG efficient for transportation and 
storage purposes in areas with limited natural gas resources or limited 
pipeline supply of natural gas.
    Prior to liquefaction, the natural gas must be treated (pre-
treatment) to remove impurities and extract heavy hydrocarbons 
(extraction). The pre-treatment, hydrocarbon extraction, and 
liquefaction processes may involve a number of hazardous fluids--
including materials that are flammable (e.g., methane, ethane, 
ethylene, propane, butane, pentane, other heavy hydrocarbons including 
aromatic hydrocarbons, hydrogen sulfide, and anhydrous ammonia); toxic 
(e.g., aromatic hydrocarbons, hydrogen sulfide, and anhydrous ammonia); 
and corrosive (e.g., anhydrous ammonia, amine solution, and aromatic 
hydrocarbons). Such hazardous materials can be present in either 
gaseous or liquid form at different stages of these processes. Larger 
LNG facilities, such as import or export terminals, will typically 
employ more complex liquefaction processes (and different, and larger 
quantities of, hazardous fluids) than smaller LNG facilities, such as 
peak shavers and mobile and temporary facilities. After liquefaction, 
LNG is stored and transported in specialized tanks that are insulated 
and refrigerated to maintain low temperatures. When needed for use, LNG 
undergoes a regasification process in which it is warmed and converted 
back into its gaseous state. The vaporized natural gas can then be 
injected into a pipeline system for distribution or used as fuel for 
natural gas-operated equipment.
    The flexibility arising from the transportation and storage of LNG 
has made it a vital element in natural gas supply infrastructures 
around the world. Within the United States, LNG peak shaving facilities 
provide local customers with access to natural gas during times of peak 
demand. There is also increasing interest in developing small-scale, 
mobile, or temporary LNG facilities to support novel applications 
(e.g., ensuring continuity of power to data centers and for industrial 
applications). And U.S. LNG export facilities are a critical energy 
resource for a variety of countries--including strategic U.S. allies in 
Asia and Europe--which either have limited native energy resources, 
desires to diversify their energy portfolios, or plans to transition 
away from coal for electric power and process heat generation. Recent 
supply disruptions of LNG exports from international LNG suppliers like 
Qatar have also underscored the unique value of U.S. LNG exports to the 
energy security of America's trading partners.
2. Growth and Increasing Domestic and International Significance of the 
U.S. LNG Industry
    The U.S. LNG industry has undergone significant changes in the two 
decades since PHMSA last amended its part 193 regulations. The design 
and configuration of the 117 regulated LNG facilities in service at 
that time reflected the more limited role of natural gas within the 
domestic U.S. economy and consisted mostly of the following:
    <bullet> Peak-shaving plants designed to store surplus natural gas 
for use during high demand periods, such as summer and winter. Peak-
shaving plants ensure reliability by liquefying and storing natural gas 
when demand is low and re-gasifying and distributing natural gas when 
demand is high. Natural gas shortages in the 1970s drove a wave of 
construction of peak-shaving plants. Operators began slowly retiring 
those plants in subsequent decades. The number of peak-shaving plants 
decreased from 75 in 2006 to 67 in 2018.
    <bullet> Satellite plants serving peak-shaving purposes but lacking 
the processing equipment required to convert natural gas to LNG. 
Specially equipped trucks (or tanks transported on rail flatcars) 
deliver LNG to satellite plants, where the LNG is stored and later re-
gasified and injected into natural gas distribution systems to meet

[[Page 69317]]

demand. In 2006, there were 23 satellite plants.
    <bullet> Mobile and temporary LNG plants designed to be easily 
movable rather than permanent structures. Mobile LNG plants, such as 
skid-mounted or trailer-mounted units, can be relocated as needed. 
Temporary LNG plants are used for short-term applications, providing 
supply during planned construction and maintenance activities or to 
meet unanticipated demand. Mobile and temporary LNG plants are compact 
and often located near end users to minimize transportation costs and 
enhance accessibility. In 2006, there were nine mobile and temporary 
facilities.
    <bullet> Large-scale terminals for importing LNG for domestic use, 
exporting LNG to foreign markets, or both. In 2006, the United States 
was a net importer of natural gas; there were four import terminals and 
one export terminal representing an aggregate 4.877 Bcf/d vaporization 
capacity. These terminals played a relatively small role in the U.S. 
and global energy economy in 2006.
    The shale gas revolution has fundamentally reshaped domestic and 
international energy markets over the past two decades. Newly abundant 
natural gas supplies have resulted in a rapid expansion of natural gas 
power generation capacity and industrial and commercial applications 
within the United States--a trend that is expected to accelerate due to 
onshoring of industrial capacity and skyrocketing demand for continuous 
electric generation capacity supporting super intelligence and data 
centers.\8\ The number of part 193-regulated U.S. LNG facilities has 
increased in response to these recent market developments. As of 2025, 
there are 69 peak shaving plants, many of which are larger, and more 
complex, than the smaller plants typical in 2006. The number of other 
PHMSA-jurisdictional LNG plants has increased as well: in 2004, there 
were 22 satellite plants, 8 mobile or temporary facilities, and 4 
import terminals (representing 4.877 Bcf/d import capacity); in 2025 
there were 32 satellite plants, 43 mobile or temporary facilities, and 
9 import terminals (representing 14.934 Bcf/d import capacity). 
Abundant natural gas supplies have also resulted in proliferation of 
so-called ``small-scale'' applications of LNG catering to niche 
markets, including off-grid power generation, localized peak-shaving, 
industrial equipment usage (such as oil and gas drilling equipment), 
and transportation fuels for vehicles, rail, or maritime use.\9\
---------------------------------------------------------------------------

    \8\ See Sturgeon (Xcel) & Hummel (Chart Industries), Transcript 
of Oct. 2025 Public Meeting, Docket ID PHMSA-2019-0091-7624, at 
67:12-70:20, 72:20-77:16 (Oct. 25, 2025).
    \9\ See Hummel (Chart Industries), Transcript of Oct. 2025 
Public Meeting, Docket ID PHMSA-2019-0091-7624, at 72:20-77:16 (Oct. 
25, 2025); Christa Marshall, Data Centers Increasingly Turn to Off-
Grid Gas, EE News (Feb. 5, 2026).
---------------------------------------------------------------------------

    But the most significant change since 2006 has been the emergence 
of enormous U.S. natural gas export capacity. The United States now 
boasts eight operational, PHMSA-jurisdictional export terminals 
providing ca. 17.0 Bcf/d of capacity. Sixteen additional projects 
(providing an additional ca. 31.28 Bcf/d capacity) either are in 
construction or are expected to begin construction in the near 
future.\10\ And the United States--a net importer of natural gas in 
2006--exported approximately 15.1 Bcf/d of LNG in 2024, making it the 
world's largest LNG exporter, responsible for roughly 21 percent of 
worldwide LNG supply.
---------------------------------------------------------------------------

    \10\ PHMSA, Liquefied Natural Gas (LNG) Annual Data--2010 to 
Present, available at: <a href="https://www.phmsa.dot.gov/data-and-statistics/pipeline/gas-distribution-gas-gathering-gas-transmission-hazardous-liquids">https://www.phmsa.dot.gov/data-and-statistics/pipeline/gas-distribution-gas-gathering-gas-transmission-hazardous-liquids</a> (last visited Apr. 14, 2026); FERC, U.S. LNG 
Export Terminals--Existing, Approved Not Yet Built, and Proposed, 
available at: <a href="https://www.ferc.gov/media/us-lng-export-terminals-existing-approved-not-yet-built-and-proposed">https://www.ferc.gov/media/us-lng-export-terminals-existing-approved-not-yet-built-and-proposed</a> (last visited Apr. 14, 
2026).
---------------------------------------------------------------------------

    LNG exports have become critical to U.S. economic prosperity and 
national security. A 2026 study predicts that through 2040 U.S. LNG 
exports will contribute an aggregate of around $1.4 trillion to U.S. 
GDP, more than $2.9 trillion in total revenues for U.S. businesses, 
$206 billion in Federal and State tax revenues, and more than $630 
billion in labor income. The industry will support an average of over a 
half-million U.S. jobs annually.\11\ U.S. LNG exports also reduce trade 
deficits with economic competitors and have become a focal point for 
U.S. policymakers in recent tariff negotiations with U.S. trading 
partners.\12\ U.S. LNG exports are a vital form of support for key U.S. 
allies as well. Europe and Asia were the top destinations for U.S. LNG 
exports in 2025.\13\ Japan alone imported 222.9 Bcf of U.S. LNG in 
2025, roughly 4.0 percent of the U.S. LNG exports for 2025. The 
Netherlands imported 645.8 Bcf of U.S. LNG in 2025, the most of any 
country and roughly 11.7 percent of U.S. LNG exports that year.\14\ 
Exports to Europe increased following Russia's invasion of Ukraine; in 
2022, Europe received 69 percent of all LNG exports from the United 
States, up from 34 percent in 2021. From January through November 2025, 
Europe received 68 percent of U.S.-origin volumes.\15\
---------------------------------------------------------------------------

    \11\ S&P Global, Price and Economic Impacts of an Accelerating 
Export Industry: U.S. LNG Impact Study--Phase 4 (July 2026).
    \12\ Reuters, U.S. LNG Producers Climb as EU Agrees to $750 
Billion in Energy Purchases (July 28, 2025), available at: <a href="https://www.reuters.com/business/energy/us-lng-producers-climb-eu-agrees-750-billion-energy-purchases-2025-07-28/">https://www.reuters.com/business/energy/us-lng-producers-climb-eu-agrees-750-billion-energy-purchases-2025-07-28/</a>.
    \13\ EIA, Today in Energy: U.S. Natural Gas Exports to Grow 
Nearly 30% by 2027 as LNG Facilities Ramp Up (Apr. 16, 2026), 
available at: <a href="https://www.eia.gov/todayinenergy/detail.php?id=67484">https://www.eia.gov/todayinenergy/detail.php?id=67484</a>.
    \14\ EIA, U.S. Natural Gas Exports and Re-Exports by Country, 
available at: <a href="https://www.eia.gov/dnav/ng/NG_MOVE_EXPC_S1_A.htm">https://www.eia.gov/dnav/ng/NG_MOVE_EXPC_S1_A.htm</a> 
(last visited Apr. 22, 2026).
    \15\ EIA, Today in Energy: Ten Years After First Sabine Pass 
Cargo, U.S. LNG Exports are Still on the Rise (Feb. 24, 2026), 
available at: <a href="https://www.eia.gov/todayinenergy/detail.php?id=67224">https://www.eia.gov/todayinenergy/detail.php?id=67224</a>.
---------------------------------------------------------------------------

3. The Regulatory Framework and Industry Efforts To Ensure LNG Facility 
Safety
    Multiple Federal agencies play a role in ensuring the safety of 
onshore LNG facilities.\16\ These agencies exercise their respective 
authorities through a variety of administrative tools--including 
implementing regulations, guidance, orders, and enforcement actions--
that can govern different phases of the lifecycle (including 
authorization, construction, and operations) of LNG facilities. The 
States also have a role in administering the Federal safety framework 
for intrastate LNG facilities. Industry, too, has pursued continuous 
safety improvement, developing voluntary (but widely adopted) consensus 
and industry codes, standards, recommended practices, guidelines 
reflecting safety-enhancing best practices, and technological advances 
that have outpaced the development of Federal safety regulatory 
regimes. These mutually reinforcing approaches have yielded a strong 
historical safety record for all PHMSA-jurisdictional LNG facilities.
---------------------------------------------------------------------------

    \16\ PHMSA has not attempted to identify here the entire 
universe of Federal agencies whose regulatory schemes could touch on 
the diverse activities of PHMSA-jurisdictional LNG facilities but 
instead focused on those playing the most prominent role in their 
safety regulation.
---------------------------------------------------------------------------

a. The Regulatory Framework Ensuring Safety
    Guardrails for Federal agencies' exercise of their respective 
regulatory authorities over the safety of LNG facilities are set forth 
in a series of interagency agreements and memoranda of understanding. 
Noteworthy among those interagency efforts are: a 2004 Interagency 
Agreement between PHMSA, FERC, and the USCG governing waterfront LNG 
facilities (typically FERC-jurisdictional import and export 
facilities); \17\ a 2018

[[Page 69318]]

Memorandum of Understanding between FERC and PHMSA regarding PHMSA's 
role in FERC's environmental analyses supporting LNG facility 
certificate applications; \18\ and a 2020 Annex to a 2004 Memorandum of 
Understanding between DOT and DHS outlining the respective roles of 
PHMSA and the DHS agencies (including TSA, USCG, and CISA) regarding 
the physical and cybersecurity of PHMSA-jurisdictional LNG 
facilities.\19\
---------------------------------------------------------------------------

    \17\ Interagency Agreement Among the Federal Energy Regulatory 
Commission, United States Coast Guard, and Research and Special 
Programs Administration for the Safety and Security Review of 
Waterfront Import/Export Liquefied Natural Gas Facilities (Feb. 10, 
2004), available at: <a href="https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/docs/InteragencyAgreementLNG%2CFeb2004.pdf">https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/docs/InteragencyAgreementLNG%2CFeb2004.pdf</a> (2004 Interagency 
Agreement).
    \18\ Memorandum of Understanding Between the Department of 
Transportation and the Federal Energy Regulatory Commission 
Regarding Liquefied Natural Gas Transportation Facilities (Aug. 31, 
2018), available at: <a href="https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/docs/news/64706/ferc-phmsa-mou.pdf">https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/docs/news/64706/ferc-phmsa-mou.pdf</a> (2018 Memorandum of 
Understanding).
    \19\ Annex to the Memorandum of Understanding Between the 
Department of Homeland Security and the Department of Transportation 
Concerning Transportation Security Administration and Pipeline and 
Hazardous Materials Safety Administration Cooperation on Pipeline 
Transportation Security and Safety (Feb. 26, 2020), available at: 
<a href="https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/docs/regulatory-compliance/phmsa-guidance/73466/phmsa-tsa-mou-annexexecuted.pdf">https://www.phmsa.dot.gov/sites/phmsa.dot.gov/files/docs/regulatory-compliance/phmsa-guidance/73466/phmsa-tsa-mou-annexexecuted.pdf</a> 
(2020 Annex).
---------------------------------------------------------------------------

PHMSA
    PHMSA's authority to regulate the safety of LNG facilities is 
derived from the Pipeline Safety Laws (49 U.S.C. 60101 et seq.). The 
Natural Gas Pipeline Safety Act of 1968 authorized DOT to prescribe and 
to enforce minimum Federal safety standards for gas pipeline facilities 
and persons engaged in the transportation of gas, including the 
conversion and storage of gas by LNG facilities.\20\ Subsequent 
amendments to the Pipeline Safety Laws directed DOT to establish and to 
enforce safety standards specific to LNG facilities.\21\ The PHMSA 
Administrator exercises this authority on behalf of the Secretary 
pursuant to a delegation at 49 CFR 1.97.\22\
---------------------------------------------------------------------------

    \20\ Public Law 90-481.
    \21\ 49 U.S.C. 60103; see Public Law 114-183; Public Law 116-
260.
    \22\ For additional information on the history of PHMSA's 
authority to regulate the safety of LNG facilities, see RSPA, 
Associate Administrator Decision Denying Petition for Rulemaking 
from the Commonwealth of Massachusetts and the State of Rhode 
Island, Docket ID PHMSA-RSPA-2004-19208-0007 (Oct. 25, 2006).
---------------------------------------------------------------------------

    PHMSA has prescribed comprehensive minimum safety standards for LNG 
facilities at part 193. These safety standards consist of siting, 
design, installation, construction, testing, maintenance, and 
operations (including fire protection and physical security) 
requirements. PHMSA also requires owners and operators of LNG 
facilities to submit annual, incident, and safety-related condition 
reports. PHMSA oversees compliance with the part 193 regulations by 
conducting inspections; investigating incidents; and, if necessary, 
initiating enforcement actions.\23\ PHMSA also plays an important role 
in FERC's exercise of its authority under sections 3 or 7 of the 
Natural Gas Act (NGA, 15 U.S.C. 717 et seq.). Pursuant to the 2004 
Interagency Agreement between PHMSA, FERC, and the USCG, PHMSA serves 
as a cooperating agency supporting FERC's compliance with the National 
Environmental Policy Act (NEPA, 42 U.S.C. 4321 et seq.) in connection 
with certificates for new and modified LNG facilities. The 2018 
Memorandum of Understanding elaborated on that historical role, as it 
provides that PHMSA's participation in FERC's NEPA reviews will also 
entail issuance of a letter of determination on an applicant's 
compliance with PHMSA's part 193, subpart B siting requirements.
---------------------------------------------------------------------------

    \23\ 49 U.S.C. 60112 and 49 CFR 190.233 (corrective action order 
authority based on PHMSA decision that a pipeline facility is or 
would be ``hazardous''); 49 U.S.C. 60117(m) and 49 CFR 190.239 
(notice of proposed safety order authority based on PHMSA 
determination that a pipeline facility has a condition posing a 
``pipeline integrity risk''); 49 U.S.C. 60117(p) and 49 CFR 190.235-
190.237 (emergency order authority based on PHMSA determination that 
an unsafe condition or practice ``constitutes or is causing an 
imminent hazard''); 49 U.S.C. 60122 and 49 CFR 190.221-190.225 
(civil penalty authority based on PHMSA determination that a person 
violated a pipeline safety law, regulation, or order); 49 U.S.C. 
60118(b) and 49 CFR 190.217 (compliance order authority based on 
PHMSA determination that a person is violating a pipeline safety 
law, regulation, or order).
---------------------------------------------------------------------------

    PHMSA's enabling statutes and implementing regulations also 
prescribe important limits on its authority to regulate LNG facilities. 
For example, because PHMSA's statutory authority only extends to the 
transportation of gas by pipeline, part 193 has historically only 
applied to LNG facilities that receive gas from or deliver gas to a 
part 192-regulated pipeline.\24\ Part 193 has also not applied to LNG 
facilities used either by ultimate consumers of LNG or natural gas 
(Sec.  193.2001(b)(1)) or in natural gas treatment or hydrocarbon 
extraction that do not store LNG (Sec.  193.2001(b)(2)). The Pipeline 
Safety Laws at 49 U.S.C. 60101(a)(14)(B) explicitly prohibit PHMSA from 
regulating structures or equipment at LNG facilities located in 
navigable waters as defined by the Federal Power Act (16 U.S.C. 796), a 
prohibition codified by regulation at 49 CFR 193.2001(b)(4). In 
addition, part 193 regulations codify at Sec.  193.2001(b)(3) the 
allocation of regulatory authority between the USCG and the Research 
and Special Projects Administration (RSPA, PHMSA's predecessor agency) 
memorialized within a 1978 Memorandum of Understanding, whereby RSPA 
disclaimed regulatory authority for matters other than siting with 
respect to the ``marine cargo transfer system and associated 
facilities'' at waterfront LNG facilities.\25\
---------------------------------------------------------------------------

    \24\ See, e.g., PHMSA, LNG Plant Requirements: Frequently Asked 
Questions, at G1, available at: <a href="https://www.phmsa.dot.gov/pipeline/liquified-natural-gas/lng-plant-requirements-frequently-asked-questions">https://www.phmsa.dot.gov/pipeline/liquified-natural-gas/lng-plant-requirements-frequently-asked-questions</a> (last visited Sep. 11, 2025) (LNG FAQs).
    \25\ See MTB, Liquefied Natural Gas Facilities; New Federal 
Safety Standards, 45 FR 9184, 9188 (Feb. 11, 1980).
---------------------------------------------------------------------------

    Other documents inform PHMSA's exercise of its statutory authority 
over LNG facilities. The 2004 Memorandum of Understanding between DOT 
and DHS reflects post-9/11 legislation re-allocating primary 
responsibility for transportation security from DOT to the then newly 
established DHS (though the Memorandum contemplates that DOT operating 
administrations will support DHS security efforts and retain their pre-
existing statutory authority to ensure the safety of different modes of 
transportation in ways that could overlap with DHS's security mission). 
Subsequently negotiated annexes (most recently the 2020 Annex 
negotiated between TSA and PHMSA) elaborate on each agency's respective 
responsibilities and commit to mutual collaboration on information 
sharing, critical infrastructure security and resilience, strategic 
planning, and development of standards and guidance. The 2004 
Interagency Agreement between PHMSA, FERC, and USCG similarly 
memorializes commitments among those agencies for cooperation in their 
respective operations-phase inspections of LNG facilities.
    PHMSA exercises jurisdiction over 23 FERC-authorized (including 
existing, certificated but not-yet-built) onshore LNG import and export 
terminals; there are two additional LNG import and export terminal 
applications currently under FERC review that would be regulated by 
PHMSA as well. PHMSA also regulates more than 69 LNG peak-shaving 
facilities, 43 mobile/temporary facilities, and 32 satellite 
facilities.\26\
---------------------------------------------------------------------------

    \26\ PHMSA, LNG Annual Data--2010 to Present.
---------------------------------------------------------------------------

Federal Energy Regulatory Commission (FERC)
    Under the NGA, FERC issues orders authorizing the siting, 
construction, expansion, and operation of LNG import and export 
terminals (NGA, section 3

[[Page 69319]]

(codified at 15 U.S.C. 717b and 717b-1)) and certificates of public 
convenience and necessity for some LNG peak shaving facilities (NGA, 
section 7 (codified at 15 U.S.C. 717f)).\27\ As part of the application 
process, FERC requires operators to submit detailed site-specific 
engineering, design, and operations information; evidence that the 
facility will safely receive or deliver LNG; and procedures and design 
features to mitigate potential hazards to the public resulting from 
accidental releases or natural catastrophes.\28\ Most of the 
information submitted to FERC during the application process would be 
considered process safety information required to be addressed under 
the PIPES Act of 2020.
---------------------------------------------------------------------------

    \27\ See 15 U.S.C. 717a(11), b(e), f. FERC also has the 
authority to approve the design, construction, and siting of natural 
gas import and export facilities. See 15 U.S.C. 717b(a); see also 42 
U.S.C. 7151(b) (2012); U.S. Dep't of Energy, Delegation Order No. 
00-004.00A (May 16, 2006).
    \28\ See 18 CFR part 153; 18 CFR 380.12(m)-(o).
---------------------------------------------------------------------------

    Furthermore, FERC requires applicants to explain how the proposed 
project will comply with applicable Federal regulations, including part 
193, in implementing NEPA and the NGA.\29\ FERC engages PHMSA as a 
cooperating agency as part of the application review process in 
analyzing compliance with the part 193 siting requirements. In 
addition, FERC evaluates the engineering information submitted by an 
applicant against the applicable regulations and additional codes, 
standards, and other recommended and generally accepted good 
engineering practices (RAGAGEPs) listed by the applicant or that are 
routinely applied to LNG facilities. FERC similarly engages USCG as 
another cooperating agency under NEPA in reviewing waterway suitability 
assessments (WSAs).
---------------------------------------------------------------------------

    \29\ See 18 CFR 380.12(o)(14).
---------------------------------------------------------------------------

    FERC orders for LNG facilities typically contain conditions 
memorializing a broad range of applicant commitments and FERC-imposed 
requirements directed toward safety and environmental protection. Such 
conditions include, but are not limited to, submitting for review and 
approval: final designs of various engineering and process safety 
information, completed process hazard analyses (PHAs), management of 
change (MOC) procedures and logs, pre-start-up safety reviews (PSSRs), 
O&M procedures, including preventative and predictive maintenance plans 
(e.g., mechanical integrity procedures), hot work procedures, 
contractor oversight procedures, and emergency response plans developed 
in consultation with Federal, State, and local emergency management 
agencies and emergency responders. Moreover, FERC requires an 
implementation plan and schedule for meeting the conditions in its 
orders, authorizes initiation of various activities, and conducts 
annual or biennial inspections to verify compliance during 
construction, commissioning, and operations. FERC also requires 
operators to notify its staff of significant non-scheduled events, 
including safety and security-related incidents, and to submit semi-
annual reports of modifications in design of facilities and operating 
conditions and abnormal operating and maintenance experiences, 
including release of hazardous fluids.
    FERC exercises jurisdiction over 23 (including existing, 
certificated but not-yet-built) LNG import and export terminals onshore 
or in State waters, as well as 13 LNG peak-shaving plants involved in 
interstate gas transportation.\30\ Additional LNG import and export 
terminal applications are currently under FERC formal application or 
pre-filing review.
---------------------------------------------------------------------------

    \30\ FERC, U.S. LNG Export Terminals--Existing, Approved Not Yet 
Built, and Proposed; FERC, U.S. LNG Import Terminals--Existing, 
Approved Not Yet Built, and Proposed, available at: <a href="https://www.ferc.gov/media/us-lng-import-terminals-existing-approved-not-yet-built-and-proposed">https://www.ferc.gov/media/us-lng-import-terminals-existing-approved-not-yet-built-and-proposed</a> (last visited Apr. 14, 2026); FERC, 
Jurisdictional Peakshavers (Nov. 2, 2020), available at: <a href="https://www.ferc.gov/sites/default/files/industries/gas/indus-act/lng/lng-peakshavers.pdf">https://www.ferc.gov/sites/default/files/industries/gas/indus-act/lng/lng-peakshavers.pdf</a>.
---------------------------------------------------------------------------

Department of Homeland Security (DHS)--United States Coast Guard (USCG)
    USCG's regulatory authority over onshore, waterfront LNG facilities 
arises from statutes governing the safety and security of ports and 
navigable waterways.\31\ USCG exercises primary regulatory authority 
for safety within marine cargo transfer areas at waterfront LNG plants, 
which USCG refers to as the marine transfer area for LNG, and has 
adopted regulations at 33 CFR part 127 governing the design, 
construction, maintenance and operations of those facilities--but has 
historically deferred to PHMSA's evaluation under 49 CFR part 193, 
subpart B of the hazards arising from their siting. USCG also exercises 
primary responsibility for physical security of the marine cargo 
transfer area as well as the entirety of waterfront LNG facilities and 
has issued regulations at 33 CFR part 105 governing the submission and 
approval of FSPs. Title 33 CFR part 101 (Subpart F) also governs 
cybersecurity requirements of LNG facilities under 33 CFR part 105.
---------------------------------------------------------------------------

    \31\ E.g., Magnuson Act of 1950 (46 U.S.C. 70051); Ports and 
Waterways Safety Act of 1972, as amended (46 U.S.C. Ch. 700); 
Maritime Transportation Security Act of 2002 (46 U.S.C. Ch. 701). 
PHMSA notes that the proposed amendments to 49 CFR parts 191 and 193 
do not modify, limit, supersede, or otherwise affect existing Coast 
Guard authorities or requirements applicable to waterfront LNG 
facilities, marine transfer areas, mobile or temporary LNG 
facilities at or near waterfront locations where Coast Guard 
requirements may apply, including facility security, waterway 
suitability, and Captain of the Port authorities. In addition, PHMSA 
clarifies that compliance with 49 CFR part 193, including any 
incorporated NFPA 59A-2026 provisions, does not relieve an operator 
of any applicable Coast Guard requirement.
---------------------------------------------------------------------------

    USCG regulations address the suitability of waterways for LNG 
marine traffic in connection with waterfront LNG facilities (33 CFR 
127.007 and 127.009), and vessel engineering and construction safety 
(46 CFR part 154) and security (33 CFR part 104) for LNG ship traffic 
in connection with waterfront LNG facilities; USCG reviews operator-
submitted WSAs documenting compliance with those regulations for each 
such LNG facility. USCG also performs reasonable examinations and 
inspections at waterfront LNG facilities to verify compliance with its 
regulations and any obligations imposed in connection with its review 
of FSPs and WSAs.\32\ In addition, USCG regulations require that 
operators notify the appropriate Federal agency of suspicious 
activities, security breaches, and transportation security 
incidents.\33\
---------------------------------------------------------------------------

    \32\ 33 CFR 127.011.
    \33\ 33 CFR 101.305.
---------------------------------------------------------------------------

    USCG exercises jurisdiction over 23 (including existing, 
certificated but not-yet-built) waterfront LNG import and export 
terminals, as well as 4 bunkering facilities.\34\
---------------------------------------------------------------------------

    \34\ Int'l Mar. Org, Fuel Supply: Supply of Alternative Fuels, 
available at: <a href="https://futurefuels.imo.org/latest-information/fuel-supply/">https://futurefuels.imo.org/latest-information/fuel-supply/</a> (last visited Apr. 21, 2026).
---------------------------------------------------------------------------

    Department of Homeland Security (DHS)--Transportation Security 
Agency (TSA) and Cybersecurity and Infrastructure Security Agency 
(CISA)
    The Homeland Security Act of 2002 consolidated homeland security 
responsibilities within DHS. Congress transferred two DOT operating 
administrations to DHS in that legislation: the USCG and TSA.\35\ 
Subsequently, Congress passed the Cybersecurity and Infrastructure 
Security Agency Act of 2018, establishing CISA within DHS and

[[Page 69320]]

assigning CISA primary responsibility for coordinating cybersecurity 
protection for the Nation's energy infrastructure.\36\
---------------------------------------------------------------------------

    \35\ Public Law 107-296, 116 Stat. 2135, 2249-50 (codified as 
amended at 6 U.S.C. 468(b)) (transferring the USCG's authorities, 
functions, personnel, and assets to DHS). Congress established TSA 
in the Aviation and Transportation Security Act of 2001 (Pub. L. 
107-71, 115 Stat. 597, 597-98 (codified as amended at 49 U.S.C. 
114)) and assigned it primary responsibility for transportation 
security in all modes of transportation. 49 U.S.C. 114(d).
    \36\ Public Law 115-278, 132 Stat. 4169-72.
---------------------------------------------------------------------------

    In 2010, TSA issued the initial edition of its Pipeline Security 
Guidelines to assist operators of gas pipelines and LNG facilities in 
the development and evaluation of comprehensive security programs at 
their facilities. TSA's Pipeline Security Guidelines, which have been 
updated several times (most recently in April 2021), set forth non-
binding guidance pertaining to corporate security policies, security 
vulnerability assessments, physical security measures, and 
cybersecurity efforts.\37\ TSA conducts voluntary visits with pipeline 
operators as part of its Corporate Security Review Program. TSA 
personnel work with operator personnel during these visits to analyze 
FSPs and policies and compare practices against the Pipeline Security 
Guidelines.
---------------------------------------------------------------------------

    \37\ TSA, Pipeline Security Guidelines (Apr. 2021), available 
at: <a href="https://www.tsa.gov/sites/default/files/pipeline_security_guidelines.pdf">https://www.tsa.gov/sites/default/files/pipeline_security_guidelines.pdf</a>.
---------------------------------------------------------------------------

    Following the 2021 Colonial Pipeline ransomware attack, TSA issued 
Security Directives imposing mandatory cybersecurity requirements on a 
limited number of critical pipeline facilities, including certain peak 
shaving facilities. TSA issued Security Directive Pipeline-2021-01 
(Security Directive) requiring owners and operators of critical 
pipeline facilities to take crucial measures to enhance pipeline 
cybersecurity.\38\ This Security Directive requires operators of those 
facilities (1) to report confirmed and potential cybersecurity 
incidents to CISA; (2) to designate a Cybersecurity Coordinator to be 
available 24 hours a day, seven days a week; (3) to review current 
practices by performing a cybersecurity vulnerability assessment; and 
(4) to identify any gaps and related remediation measures to address 
cyber-related risks and report the results to TSA and CISA.\39\
---------------------------------------------------------------------------

    \38\ On May 8, 2021, the Colonial Pipeline Company announced 
that it had halted its pipeline operations due to a ransomware 
attack. This attack temporarily disrupted critical supplies of 
gasoline and other refined petroleum products throughout the East 
Coast of the United States. See TSA, Ratification of Security 
Directive, Security Directive Pipeline-2021-01, 86 FR 38209 (July 
20, 2021); DHS, DHS Announces New Cybersecurity Requirements for 
Critical Pipeline Owners and Operators (May 27, 2021), available at: 
<a href="https://www.dhs.gov/news/2021/05/27/dhs-announces-new-cybersecurity-requirements-critical-pipeline-owners-and-operators">https://www.dhs.gov/news/2021/05/27/dhs-announces-new-cybersecurity-requirements-critical-pipeline-owners-and-operators</a>.
    \39\ TSA, Ratification of Security Directive, Security Directive 
Pipeline-2021-01, 86 FR 38209 (July 20, 2021).
---------------------------------------------------------------------------

    On July 20, 2021, TSA issued Security Directive Pipeline-2021-02 
requiring operators of TSA-designated critical facilities to implement 
additional protections against cyber intrusions and degradation of 
critical infrastructure, including development and execution of 
Cybersecurity Implementation, Response, and Assessment Plans as well as 
annual Cybersecurity Assessment Plan reporting to CISA.\40\ Subsequent 
renewals of each of those Security Directives have clarified and 
expanded pertinent programmatic and reporting requirements.\41\
---------------------------------------------------------------------------

    \40\ TSA, Ratification of Security Directive, Security Directive 
Pipeline-2021-02, 86 FR 52953 (Sep. 24, 2021).
    \41\ TSA, Security Directive Pipeline-2021-01G (Jan. 6, 2026); 
TSA, Security Directive Pipeline-2021-02F (May 1, 2025). TSA 
Pipeline Security Directives are maintained at <a href="https://www.tsa.gov/sd-and-ea">https://www.tsa.gov/sd-and-ea</a>.
---------------------------------------------------------------------------

States
    The Federal Pipeline Safety Laws preserve a role for States in 
regulating the safety of LNG facilities. State authorities may obtain a 
certification from PHMSA to regulate the safety of intrastate LNG 
facilities not subject to the jurisdiction of FERC under the NGA--
typically peak shaving, mobile/temporary, and satellite LNG 
facilities.\42\ Certified State authorities may prescribe and enforce 
additional or more stringent safety standards for intrastate LNG 
facilities, so long as those safety standards are compatible with the 
Federal requirements in the Pipeline Safety Regulations (49 CFR parts 
190-199). As of February 2026, 41 State authorities are certified to 
regulate approximately 149 intrastate LNG facilities.\43\
---------------------------------------------------------------------------

    \42\ PHMSA also notes that most LNG facilities not subject to 
FERC authority under the NGA are approved by State regulators (e.g., 
public utility commissions). Those State regulators may either list 
safety requirements among the terms and conditions of such approvals 
or accept regulatory commitments by project sponsors to adopt 
certain safety requirements.
    \43\ The Pipeline Safety Laws at 49 U.S.C. 60106 also permit 
PHMSA to make an agreement with a State authority authorizing it to 
participate in the oversight of interstate LNG facilities and other 
gas pipeline facilities. No State with interstate LNG facilities has 
entered into such an agreement. See PHMSA, LNG Plant Safety 
Programs: Participating States in the Federal/State Cooperative 
Partnership (Apr. 2026), available at: <a href="https://www.npms.phmsa.dot.gov/Documents/LNG_CoopAgreementsMap.pdf">https://www.npms.phmsa.dot.gov/Documents/LNG_CoopAgreementsMap.pdf</a>.
---------------------------------------------------------------------------

b. Industry Efforts Promoting LNG Facility Safety
    The LNG industry plays an active role in ensuring the safety of 
PHMSA-jurisdictional LNG facilities, particularly through the 
development of voluntary consensus industry standards and recommended 
practices. The leading industry standard for LNG facilities is NFPA 
59A. First published in 1967, PHMSA has incorporated NFPA 59A by 
reference into the Federal safety standards for LNG facilities since 
1972.\44\ The most recent edition of NFPA 59A, published in 2026, 
includes mandatory standards for the siting, design, construction, 
operation, and maintenance of LNG facilities. This edition incorporates 
a comprehensive list of other consensus industry standards addressing 
particular topics as well as several informational annexes providing 
guidance to facilitate compliance with its mandatory provisions.\45\
---------------------------------------------------------------------------

    \44\ 37 FR 21638 (amending part 192 to create a new Sec.  192.12 
that will establish Federal safety standards for liquefied natural 
gas facilities at Sec.  192.12 and incorporating, by reference, the 
1971 edition of NFPA 59A).
    \45\ Standards listed in NFPA 59A-2026's mandatory provisions 
and informational annexes are also generally themselves mature 
documents (building on successive editions issued over many years) 
resulting from extensive discussions among industry technical 
experts and government regulators on technical issues.
---------------------------------------------------------------------------

    A technical committee (Technical Committee) is responsible for 
drafting each edition of NFPA 59A to ensure its provisions reflect the 
latest safety-enhancing advances in operator practices and 
technologies. The Technical Committee consists of 35 principal experts 
and 21 alternates from State and Federal government and the LNG 
industry. Collectively, the Technical Committee has extensive expertise 
on all aspects of LNG safety. PHMSA and FERC are among the government 
participants on the Technical Committee, with representatives of each 
of those agencies serving as voting members.
    The process employed by the Technical Committee in updating NFPA 
59A has been accredited by the American National Standards Institute 
(ANSI). Development of each edition of NFPA 59A lasts between three to 
five years and involves a four-step process: (1) public input; (2) 
public comment; (3) NFPA Technical Committee meeting; and (4) standards 
council action. Public input from industry stakeholders and members of 
the general public is accepted for consideration in the Technical 
Committee's development of the initial draft of an updated edition. 
Once the initial draft is developed, the Technical Committee posts that 
initial draft (accompanied by reports summarizing and responding to 
input from the public and Technical Committee members) on a publicly 
available website and solicits comments. After analyzing any comments 
received, the Technical Committee prepares the second draft (and 
potentially subsequent drafts)

[[Page 69321]]

pursuant to a similar process and posts its responses to the comments 
received on the previous draft. After the Technical Committee approves 
the revised draft, the NFPA Standards Council approves issuance of the 
updated standard.
c. The LNG Industry's Strong Safety Record Since 2006
    The U.S. LNG industry has a remarkably strong safety record. Since 
2010, there has been more than a 50 percent increase in the number of 
all PHMSA-jurisdictional LNG facilities--121 facilities in 2010 
compared to the 181 facilities in 2024. That increase has not led to 
more incidents. Incident data across all PHMSA-jurisdictional LNG 
facilities shows that there have been three or fewer significant 
incidents reported in each of the past 15 years.\46\ In 11 out of those 
15 years, one or fewer significant incidents were reported. Zero 
significant incidents were reported in six of those years, and only two 
reportable injuries occurred during that entire 15-year period--one at 
a peak shaving facility in 2014 and one at a mobile and temporary 
facility in 2023. And there was only a single fatality (at a mobile/
temporary facility--not the more complex LNG export or peak shaving 
facilities).
---------------------------------------------------------------------------

    \46\ PHMSA, Liquefied Natural Gas (LNG) Incident Data--January 
2011 to Present, available at: <a href="https://www.phmsa.dot.gov/data-and-statistics/pipeline/distribution-transmission-gathering-lng-and-liquid-accident-and-incident-data">https://www.phmsa.dot.gov/data-and-statistics/pipeline/distribution-transmission-gathering-lng-and-liquid-accident-and-incident-data</a> (LNG Incident Report Data). By 
``significant'' PHMSA means an incident involving fatality, injury, 
or total property damage of $50K or more in 1984 dollars.
---------------------------------------------------------------------------

    The same strong safety record holds if the 15-year data is examined 
for each type of LNG facility. For LNG export facilities, there were no 
significant incidents reported in 10 out of the 15 years even as the 
number of those facilities has more than doubled between 2010 and 2024. 
Peak shaving facilities reported only three significant incidents, and 
mobile and temporary LNG facilities had only one significant incident--
even as the number of each of those facilities increased since 2010. 
And non-marine baseload and satellite facilities had no significant 
incidents during the 15-year period even as the number of those 
facilities increased more than 100 percent.
4. Broad Demand for Updated PHMSA Regulations on LNG Facility Safety
    Despite the significant changes that have occurred throughout the 
LNG industry, PHMSA has not updated its part 193 regulations since 
2006. Instead, PHMSA has leaned more heavily on guidance in the form of 
its LNG FAQs implementing its part 193 regulations to accommodate 
innovations in facility design, function, construction and operational 
practices, and technology. But PHMSA's LNG FAQs--which have been 
updated nine times since their introduction in 2014--are not legally 
binding and do not provide interested stakeholders with the regulatory 
certainty needed to make informed decisions. PHMSA's delay in updating 
its part 193 regulations has in turn encouraged FERC to exercise its 
statutory authority to impose more legally binding, safety-related 
conditions in authorizing new LNG projects. Although this case-by-case 
approach is done with PHMSA and USCG as cooperating agencies and 
includes a fairly consistent set of conditions, PHMSA's or USCG's 
recommendations are subject to FERC's consideration, which can inject 
further uncertainty into the regulatory framework. As discussed in more 
detail below, a broad consensus has been reached about the need to 
update part 193 regulations to address these and other concerns.
Executive Orders
    Noting that modern LNG facilities ``bear little resemblance to the 
small peak shaving facilities'' typical when PHMSA first issued its 
part 193 regulations in February 1980, President Trump in his first 
term issued Executive Order (E.O.) 13868, Promoting Energy 
Infrastructure and Economic Growth, directing PHMSA to issue a final 
rule updating its part 193 regulations no later than May 2020.\47\ E.O. 
13868 directed PHMSA to ensure that those updated regulations employed 
``risk-based standards to the maximum extent possible.''
---------------------------------------------------------------------------

    \47\ E.O. 13868, Promoting Energy Infrastructure and Economic 
Growth, 84 FR 15495 (Apr. 19, 2019).
---------------------------------------------------------------------------

    In his second term, President Trump has issued a series of 
executive orders encouraging investment in the Nation's energy 
infrastructure and the use of risk-informed regulations ensuring the 
safety of those facilities. On his first day in office for his second 
term, the President issued E.O. 14156, Declaring a National Energy 
Emergency, identifying the integrity and expansion of U.S. energy 
infrastructure to support affordable domestic energy prices and robust 
energy exports as a U.S. national and economic security priority.\48\ 
That same day, President Trump issued E.O. 14154, Unleashing American 
Energy, requiring agencies to reduce undue burdens on the 
identification, development, or use of domestic energy resources to 
protect U.S. energy and national security, singling out the 
contribution of LNG exports to U.S. national security and economic 
growth.\49\ Later his first month in office, President Trump issued 
E.O. 14192, Unleashing Prosperity Through Deregulation, requiring 
agencies to identify opportunities to alleviate unnecessary regulatory 
compliance burdens imposed on industry and the general public.\50\ 
Lastly, in response to disruptions in LNG supply routes due to regional 
conflicts, President Trump issued a Determination under the Defense 
Production Act of 1950 (Pub. L. 81-774) to promote expansion of (inter 
alia) U.S. LNG export capacity to sustain U.S. defense operations and 
ensure the energy security of U.S. allies.\51\
---------------------------------------------------------------------------

    \48\ E.O. 14156, Declaring a National Energy Emergency, 90 FR 
8433 (Jan. 29, 2025).
    \49\ E.O. 14152, Unleashing American Energy, 90 FR 8353 (Jan. 
29, 2025).
    \50\ E.O. 14192, Unleashing Prosperity Through Deregulation, 90 
FR 9065 (Feb. 6, 2025).
    \51\ Presidential Determination Pursuant to Section 303 of the 
Defense Production Act of 1950, as amended, on Natural Gas 
Transmission, Processing, Storage and Liquefied Natural Gas Capacity 
(Apr. 20, 2026).
---------------------------------------------------------------------------

Congressional Mandates
    Congress has repeatedly called on PHMSA to update its part 193 
regulations. On June 22, 2016, Congress enacted the PIPES Act of 
2016.\52\ Section 27 directed PHMSA to review and to update the minimum 
safety standards for LNG facilities and to ensure that those 
regulations appropriately address the public safety risks posed by 
permanent, small-scale LNG pipeline facilities.
---------------------------------------------------------------------------

    \52\ Public Law 114-183.
---------------------------------------------------------------------------

    On December 27, 2020, Congress enacted the PIPES Act of 2020.\53\ 
Section 110 of that legislation directed PHMSA to review existing part 
193 regulations governing operations and maintenance (including those 
pertaining to fire protection, security, and training) and to establish 
a framework by which operators of ``large-scale'' LNG facilities can 
design and employ alternative, risk-based regulatory approaches. 
PHMSA's regulatory framework governing operators' risk-based 
alternatives must achieve a level of safety that is equivalent to, or 
greater than, the level of safety required by the minimum part 193 
standards existing as of December 2020. Section 110 also requires PHMSA 
to review and to approve LNG facility implementation plans created 
under that alternative regulatory framework specifying a timeline for 
integration of elements mandated by statute. Congress

[[Page 69322]]

directed that PHMSA codify the regulatory amendments required by 
section 110 by no later than December 2023.
---------------------------------------------------------------------------

    \53\ Public Law No. 116-260.
---------------------------------------------------------------------------

GAO Recommendations
    On August 6, 2020, GAO published a report titled Natural Gas 
Exports: Updated Guidance and Regulations Could Improve Facility 
Permitting Processes (GAO-20-619).\54\ In that report, GAO made nine 
recommendations, including one to PHMSA that ``the Administrator of 
PHMSA should conduct a standards-specific review of regulations that 
incorporate standards and, if necessary, update the regulations or 
document its decision for not updating them. (Recommendation 5).'' \55\ 
This rulemaking, if codified, would update the incorporated-by-
reference standards and resolve Recommendation 5.
---------------------------------------------------------------------------

    \54\ GAO Report.
    \55\ Id.
---------------------------------------------------------------------------

Regulated Community and Members of the Public--Historical Petitions for 
Rulemaking and Public Meetings
    Industry and members of the public have repeatedly called on PHMSA 
to update its part 193 regulations. Since 2006, PHMSA has received 
several petitions for rulemaking on diverse topics including: pressure 
relief device (PRD) inspection periodicities; \56\ application of 
updated editions of NFPA 59A to peak-shaving, satellite and small-scale 
LNG facilities; \57\ targeted application of updated editions of NFPA 
59A to LNG export terminals; \58\ incorporation by reference of 
consensus industry standards governing concrete LNG storage containers; 
\59\ and implementation of the PIPES Act of 2020 section 110 
mandate.\60\ PHMSA has also received petitions for rulemaking from 
members of the public, including a number of petitions submitted by a 
single commenter pertaining to vapor cloud dispersion modeling 
methodologies within PHMSA's siting analyses.\61\ The discussions in 
section IV below respond to those petitions.
---------------------------------------------------------------------------

    \56\ AGA & Interstate Nat. Gas Ass'n of Am. (INGAA), Petition to 
Modify Language in 49 CFR 193.2619, Docket ID PHMSA-2018-0070-0001 
(June 19, 2018).
    \57\ AGA, Petition to Amend part 193 NFPA 59A 2020, Docket ID 
PHMSA-2019-0091-0005 (Jan. 21, 2020).
    \58\ Ctr. for LNG (CLNG), Petition for Rulemaking, Docket ID 
PHMSA-2019-0091-0004 (Oct. 5, 2020). This petition was subsequently 
withdrawn in 2021. See CLNG, Request to Withdraw Petition for 
Rulemaking, Docket ID PHMSA-2019-0091-0007 (May 1, 2021).
    \59\ Am. Concrete Inst. (ACI), Petition for Rulemaking to Amend 
49 CFR part 193, Docket ID PHMSA-2019-0091-0008 (May 3, 2021); ACI, 
Letter Update to ACI Petition_ACI, Docket ID PHMSA-2019-0091-0011 
(Nov. 9, 2023); ConocoPhillips, Support for PHMSA Rulemaking--ACI 
376, Docket ID PHMSA-2019-0091-0009 (Nov. 18, 2021).
    \60\ See Am. Petrol. Inst. (API), CLNG & INGAA, Pipeline Safety 
Amendments to Large-Scale LNG Facilities, Docket ID PHMSA-2019-0091-
7623 (Nov. 18, 2025).
    \61\ Havens, Workshop on LNG Regulation--Petition for 
Rulemaking, Docket ID PHMSA-2022-0076-0001 (June 8, 2022).
---------------------------------------------------------------------------

    In addition, PHMSA has held multiple public meetings in the last 
two decades focused on improved safety at LNG facilities, including: a 
February 2005 workshop on LNG safety regulations; a May 2016 public 
workshop on LNG regulations; a February 2020 meeting; and a November 
2022 forum on LNG research and development to improve part 193 
regulations.\62\ PHMSA has also held several meetings (including 
meetings in December 2007 and January 2025) of the Gas Pipeline 
Advisory Committee (GPAC) to consider proposed revisions to regulations 
pertinent to part 193-regulated facilities. In each of the meetings 
above, stakeholders from industry and environmental advocacy groups 
alike have emphasized the need for review and update of PHMSA's part 
193 regulations.
---------------------------------------------------------------------------

    \62\ Materials for each of those meetings are available on 
PHMSA's Public Meetings web page, available at: <a href="https://primis-meetings.phmsa.dot.gov/">https://primis-meetings.phmsa.dot.gov/</a> (last visited Jan. 25, 2026).
---------------------------------------------------------------------------

2025 Advance Notices of Proposed Rulemaking and Public Meeting
    In response to the Presidential directives, Congressional mandates, 
and broad stakeholder interest in updated part 193 regulations, PHMSA 
in May 2025 issued an Advance Notice of Proposed Rulemaking (ANPRM) 
soliciting stakeholder feedback on a variety of LNG-related topics 
informing its development of this NPRM.\63\ PHMSA received over 7,618 
comments. In parallel, PHMSA issued another ANPRM responding to E.O. 
14154 soliciting stakeholder feedback on opportunities to ``unleash 
American energy'' by reducing undue burdens imposed by its Pipeline 
Safety Regulations--including its part 193 regulations.\64\ PHMSA 
received another 528 comments in response to that ANPRM, with 79 of 
those comments identifying potential amendments of part 193 
regulations. In October 2025, PHMSA also held a public meeting to 
discuss LNG issues consisting of moderated panel discussions 
supplementing the administrative record developed from those ANPRMs and 
earlier public meetings.\65\ A diverse spectrum of stakeholders--
including LNG industry operators and trade associations, State 
regulatory officials, and members of the public--expressed a uniform 
desire in each of these proceedings for PHMSA to update its 
regulations, even as they expressed diverse opinions as to the form 
those updates should take. PHMSA addressed those comments and 
discussions where pertinent within the discussions in section IV below.
---------------------------------------------------------------------------

    \63\ PHMSA, Pipeline Safety: Amendments to Liquefied Natural Gas 
Facilities, 90 FR 18949 (advanced proposal May 5, 2025) (May 2025 
ANPRM).
    \64\ PHMSA, Pipeline Safety: Mandatory Regulatory Reviews To 
Unleash American Energy and Improve Government Efficiency, 90 FR 
23660 (advanced proposal June 4, 2025).
    \65\ PHMSA, Pipeline Safety: Liquefied Natural Gas Facilities 
Public Meeting 2025, 90 FR 47901 (Oct. 2, 2025).
---------------------------------------------------------------------------

III. Section-by-Section Discussion of the Proposed Changes in Part 191

    PHMSA proposes to delete Sec.  193.2011. Section 193.2011 simply 
directs operators of LNG facilities to report incidents, safety-related 
conditions, and annual pipeline summary data in accordance with the 
requirements in 49 CFR part 191. Part 191 applies on its own terms to 
LNG facilities, rendering the reference in Sec.  193.2011 unnecessary. 
PHMSA discusses proposed revisions to part 191 reporting requirements 
in this section.\66\
---------------------------------------------------------------------------

    \66\ PHMSA acknowledges multiple industry comments on the May 
2025 ANPRM regarding the burden imposed on some stakeholders from 
occasionally overlapping USCG, FERC, and PHMSA reporting 
requirements. See, e.g., API, CLNG, INGAA, AGA, Am. Pub. Gas Ass'n 
(APGA), Northeast Gas Ass'n (NGA) (Joint Trade Associations), 
Comments on the ANPRM, Docket ID PHMSA-2019-0091-7611, at 12 (July 
7, 2025). PHMSA notes that each agency imposes different timing, 
content, and format requirements, complicating review of such 
information for trend analysis purposes. In addition, such 
facilities are a minority of those subject to PHMSA part 191 
requirements. PHMSA therefore expects that synchronization of 
reporting requirements across Federal agencies will require 
additional coordination among the affected agencies.
---------------------------------------------------------------------------

A. Section 191.3--Definitions

Incident
    PHMSA proposes to revise the definition of an ``incident'' to 
include the release of any hazardous fluid (as defined under proposed 
Sec.  193.5) from an LNG facility. Section 191.3 is currently limited 
to releases of LNG, LPG, refrigerants, or natural gas. PHMSA has 
preliminarily determined that releases of hazardous fluids involved in 
the processing of gas within an LNG facility--including LNG, LPG, 
natural gas (which is composed predominantly of methane), ethane, 
ethylene, propane, butane, pentane, other heavy hydrocarbons (including

[[Page 69323]]

aromatic hydrocarbons, hydrogen sulfide, and anhydrous ammonia), as 
well as toxic (e.g., aromatic hydrocarbons, hydrogen sulfide, and 
anhydrous ammonia), and corrosive (e.g., anhydrous ammonia, amine 
solution, and aromatic hydrocarbons) materials--should be treated as 
reportable incidents. Such reporting will facilitate Federal and State 
emergency response actions as well as regulatory oversight in 
identifying facility/operator-specific or industry-wide safety 
concerns.
LNG Facility
    PHMSA proposes to revise the definition of an ``LNG facility'' to 
reflect the new code sections for part 193 proposed in this NPRM. 
Specifically, PHMSA proposes to revise the definition of ``LNG 
facility'' in Sec.  191.3 to cite proposed Sec.  193.5 instead of the 
current Sec.  193.2007.
LNG Plant
    PHMSA proposes to add a definition for an ``LNG plant'' aligned 
with the definition of that term in NFPA 59A-2026 (``an LNG facility or 
collection of LNG facilities functioning as a unit'') for clarity.

B. Section 191.22--National Registry of Operators

    On September 12, 2014, PHMSA issued an advisory bulletin to owners 
and operators of gas and hazardous liquid pipelines to clarify the 
notifications required for certain construction-related events.\67\ 
PHMSA believes that the guidance in that advisory bulletin could also 
assist LNG operators in determining what constitutes new construction 
or construction-related activities and clarify when to make required 
notifications proposed in this rulemaking.
---------------------------------------------------------------------------

    \67\ PHMSA, ADB-2014-03, Pipeline Safety: Construction 
Notification, 79 FR 54777 (Sep. 14, 2014).
---------------------------------------------------------------------------

    Accordingly, PHMSA encourages operators to provide the required 
notification(s) no later than 60 days prior to whichever of the 
following construction-related activities occur first: material 
purchasing and manufacturing; plant site or right-of-way acquisition; 
construction equipment move-in activities; onsite or offsite 
fabrications; or plant site or right-of-way clearing, grading, and 
ditching. Although the notification prior to the first occurring 
construction-related activity is strongly encouraged and will benefit 
both PHMSA and the operator, these activities may not necessarily 
represent the commencement of construction for purposes of triggering 
the minimum 60-day notice period under the regulations.\68\ PHMSA does 
not in this NPRM propose any modification to corresponding Sec.  191.22 
regulatory text but solicits comment as to how it can clarify the 60-
day notice period for new construction in Sec.  191.22 or any other 
sections of part 191.
---------------------------------------------------------------------------

    \68\ Id.
---------------------------------------------------------------------------

    PHMSA also proposes updating OPID forms and instructions to require 
operators of permanent, small-scale LNG facilities availing themselves 
of the regulatory flexibilities in subpart D to memorialize that 
designation. Existing facilities opting for that designation would need 
to update their OPIDs consistent with a new Sec.  191.22(c)(2)(vi).

C. Section 191.15--Incident Reporting

    PHMSA is not proposing any changes to the regulatory text at Sec.  
191.15 governing incident reporting for LNG facilities. However, PHMSA 
is proposing changes to the incident report form for LNG facilities 
(PHMSA F7100.3) and its accompanying instructions to address the 
proposed revisions to Sec. Sec.  191.3 and 193.5 related to the 
addition of ``hazardous fluids.'' PHMSA also proposes to delete blocks 
C.1f to C.1i on PHMSA F7100.3 consistent with comments on its May 2025 
ANPRM. The comments noted that the ``cost of commodity'' information 
did not contribute to safety or inform the calculation of the monetary 
threshold for incident reporting.\69\ PHMSA notes that proposed changes 
to calculation of the monetary threshold within the Sec.  191.3 
definition of ``incident'' under consideration in a parallel rulemaking 
would--if adopted--apply to LNG facility incident reporting as 
well.\70\
---------------------------------------------------------------------------

    \69\ Joint Trade Associations, Comments on the ANPRM, Docket ID 
PHMSA-2019-0091-7611, at 11.
    \70\ See PHMSA, Pipeline Safety: Property Damage Definition for 
Reporting Incidents on Gas Pipelines and Accidents on Hazardous 
Liquid and Carbon Dioxide Pipelines, 91 FR 22096 (proposed Apr. 24, 
2026).
---------------------------------------------------------------------------

D. Section 191.17--Annual Reporting

    PHMSA is proposing to revise the annual report form for LNG 
facilities (PHMSA F7100.3-1) and its accompanying instructions to 
address the proposed revisions to Sec. Sec.  191.3 and 193.5 related to 
releases of ``hazardous fluids'' generally, as well as to memorialize 
operator election as a ``permanent, small-scale LNG facility'' pursuant 
to the requirements in proposed subpart D.\71\
---------------------------------------------------------------------------

    \71\ In parallel with issuance of this NPRM, PHMSA has notified 
the public of its intention to modify previously approved 
information collections to replace the annual National Pipeline 
Mapping System filing requirement for LNG facilities with a one-time 
submission via the LNG facility annual report form. See PHMSA, 
Pipeline Safety: Information Collection Activities, 91 FR 36946 
(June 18, 2026). Should PHMSA adopt those modifications, any final 
rule in this rulemaking proceeding would make a conforming revision 
to Sec.  191.29(a) to delete the reference in that provision to ``or 
liquefied natural gas facility.''
---------------------------------------------------------------------------

E. Section 191.23--Reporting Safety-Related Conditions

    PHMSA proposes to revise the safety-related condition reporting 
requirements for LNG facilities to enhance safety monitoring and 
oversight. These changes would expand the scope of reporting to include 
releases of all hazardous fluids at LNG facilities and clarify that 
safety-related conditions during initial start-up (but not during 
earlier commissioning activities) must be reported.
    First, PHMSA proposes to revise the list of safety-related 
conditions in Sec.  191.23(a) to include the release of hazardous 
fluids involved in the processing of LNG. As discussed earlier, PHMSA 
proposes in Sec.  191.3 to expand the definition of an ``incident'' to 
include releases of all hazardous fluids at an LNG facility. That 
change would require operators to notify PHMSA of incidents that 
involved releases of hazardous fluids. Similarly, PHMSA proposes to 
revise the notification requirements at Sec.  191.23 to specify that 
releases of hazardous fluids at an LNG facility are reportable safety-
related conditions. Including all hazardous fluids would ensure that 
PHMSA has a complete picture of safety-related conditions and would 
help identify potential risks and hazards associated with the release 
of substances used in processing activities--not just LNG--at an LNG 
facility.
    Second, PHMSA proposes in Sec.  191.23 to add a new paragraph (c) 
to clarify that each operator of an LNG facility must report any 
safety-related condition that occurs during initial startup as 
equipment and components begin commercial operation. Currently, Sec.  
191.23 requires LNG operators to notify PHMSA of safety-related 
conditions that occur while an LNG facility is ``in service.'' PHMSA 
has interpreted ``in service'' for these purposes to mean any time a 
hazardous fluid is introduced into an LNG facility, including during 
both commissioning and subsequent initial startup. PHMSA understands 
that historical reading is appropriate as to the latter but not the 
former.
    Safety-related conditions present risks that are relevant 
throughout the life of

[[Page 69324]]

an LNG facility, beginning at the point of initial start-up.\72\ In 
contrast, commissioning activities pertain to equipment and components 
that are not yet ``in service,'' but rather are being evaluated for 
subsequent placement ``in service.'' Though PHMSA acknowledges that 
some commissioning activities involve the introduction of hazardous 
fluids, commissioning activities are necessarily directed toward 
identifying and curing potential issues under controlled and closely 
monitored conditions as a predicate for subsequent initial start-up 
activities; requiring operators to report these issues as safety-
related conditions is not appropriate in such circumstances. However, 
should an event occur during commissioning that qualifies as an 
``incident,'' operators would still remain obliged to notify PHMSA 
pursuant to Sec.  191.3.\73\ PHMSA expects that this revision to Sec.  
191.23 will allow operators to focus on identifying, evaluating, and 
curing system integrity concerns exposed during commissioning 
activities, rather than on filing safety related condition reports to 
PHMSA with potentially limited safety value.
---------------------------------------------------------------------------

    \72\ PHMSA is also aware that FERC requires reporting of safety-
related conditions occurring during initial startup activities. 
Given that PHMSA regulates LNG facilities not under FERC 
jurisdiction (such as intrastate and small-scale facilities), PHMSA 
cannot solely rely on communications with FERC to have awareness of 
safety-related conditions arising during initial start-up 
activities.
    \73\ PHMSA is also aware that other regulators (e.g., FERC) may 
impose their own reporting requirements and closely monitor 
commissioning-related activities for LNG facilities within their 
jurisdiction. PHMSA is also aware that individual operators may 
(e.g., by contract) conflate ``commissioning'' and ``initial start-
up'' activities; however, both PHMSA and NFPA 59A-2023 understand 
these phases to be generally distinguishable and sequential. See, 
e.g., NFPA 59A-2026 at 18.8.1 (characterizing testing and 
verification activities during commissioning as a condition 
precedent to start-up operations).
---------------------------------------------------------------------------

F. Section 191.25--Filing Safety-Related Condition Reports

    PHMSA proposes to change Sec.  191.25 to streamline the reporting 
process for safety-related conditions identified under Sec.  191.23. 
These changes include adding references to the newly proposed Sec.  
191.23(c) for LNG facilities and an editorial change for underground 
natural gas facilities, ensuring clarity and completeness in reporting 
procedures.

IV. Section-by-Section Discussion of the Proposed Changes in Part 193

    PHMSA proposes to update part 193 by referencing the latest edition 
of NFPA 59A and, where necessary, providing exceptions from or 
modifications to certain requirements. These changes would retain NFPA-
59A-2026 as the core of the part 193 regulations for LNG facilities, 
subject to certain additional or unique requirements. PHMSA also 
proposes to redesignate and to renumber various provisions throughout 
part 193 for clarity.

A. Incorporation by Reference of NFPA 59A-2026

    PHMSA has incorporated NFPA 59A by reference into its regulations 
for LNG facilities since the early 1970s.\74\ Part 193 currently 
incorporates by reference the 2001 edition of NFPA 59A into various 
requirements. The 2006 edition is incorporated by reference for 
purposes of certain specific requirements pertaining to LNG storage 
tanks.\75\
---------------------------------------------------------------------------

    \74\ See Office of Pipeline Safety, Liquefied Natural Gas 
Systems, 37 FR 21638 (Oct. 13, 1972). PHMSA subsequently 
incorporated updates to NFPA-59A again in 1976 (NFPA 59A-1972, in 
MTB, Part 192--Transportation of Natural and Other Gas by Pipeline; 
Minimum Federal Safety Standards, 41 FR 13586, 13590 (Mar. 13, 
1976)), 1980 (NFPA 59A-1979, in MTB, Liquefied Natural Gas 
Facilities; New Federal Safety Standards, 45 FR 9184, 9185 (Feb. 11, 
1980)), and 2000 (NFPA 59A-1996 in RSPA, Pipeline Safety: 
Incorporation of Standard NFPA 59A in the Liquefied Natural Gas 
Regulations, 65 FR 10950 (Mar. 1, 2000)).
    \75\ PHMSA, Update of Regulatory References to Technical 
Standards, 71 FR 33402 (June 9, 2006); PHMSA, Periodic Updates of 
Regulatory References to Technical Standards and Miscellaneous 
Edits, 75 FR 48593 (Aug. 11, 2010).
---------------------------------------------------------------------------

    PHMSA's historical approach to incorporating NFPA 59A-2001 has 
presented challenges to operators in developing their compliance 
strategies. First, PHMSA does not incorporate the entirety of NFPA 59A-
2001 by reference; rather, part 193 limits that incorporation to NFPA 
59A-2001's siting requirements (Sec.  193.2051), design requirements 
(Sec.  193.2101), construction requirements (Sec.  193.2301), equipment 
requirements (Sec.  193.2401), and certain fire protection requirements 
(Sec.  193.2801). Moreover, the broad language PHMSA uses in 
incorporating NFPA 59A-2001 within these requirements creates 
regulatory uncertainty. Stakeholders have expressed concern regarding 
the extent to which specific NFPA 59A-2001 provisions are incorporated 
by reference into certain regulatory requirements (e.g., design or 
construction).\76\ The conflict preemption clause that PHMSA employs in 
connection with its incorporation by reference of NFPA 59A-2001 only 
contributes to that uncertainty. Part 193 fails to provide a clear 
standard as to what qualifies as a ``conflict'' between the pertinent 
sections of NFPA 59A-2001 and applicable regulations.
---------------------------------------------------------------------------

    \76\ Pipeline Safety Tr. (PST), Comments on the ANPRM, Docket ID 
PHMSA-2019-0091-7613, at 9-10 (July 7, 2025).
---------------------------------------------------------------------------

    Second, NFPA 59A-2001 does not reflect the latest advancements in 
LNG facility design, function, construction, operational practices, and 
technologies. NFPA has been updated seven times since the publication 
of the 2001 edition; the current edition is a far more comprehensive 
and detailed document than its predecessor.\77\ PHMSA has attempted to 
bridge the gap between the 2001 and more recent editions of NFPA 59A by 
providing industry with additional guidance on certain topics, but 
stakeholders are correct that agency guidance cannot itself create 
legally binding obligations.\78\ The 2026 edition of NFPA 59A 
incorporates more recent editions of other industry standards (e.g., 
ASME Boiler and Pressure Vessel Code) that are used in manufacturing 
LNG equipment. Continuing to reference an outdated edition of NFPA 59A 
(which, in turn, incorporates older editions of other industry 
standards) imposes unnecessary regulatory burdens. Operators must 
either order manufacturers to follow older standards in designing and 
constructing LNG equipment or overcome expensive and time-consuming 
procedural hurdles (e.g., special permit applications or a finding of 
``safety equivalence'' pursuant to section 1.2 of NFPA 59A-2001) simply 
to follow the latest manufacturing techniques.\79\
---------------------------------------------------------------------------

    \77\ NFPA 59A-2001 contained 36 pages of mandatory provisions 
across 11 chapters, supplemented by 6 pages of non-mandatory, 
informational annexes. In contrast, NFPA 59A-2026 contains 65 pages 
of mandatory content across 19 chapters, supplemented by 28 pages of 
non-mandatory, informational annexes.
    \78\ See, e.g., Blue Eng'g & Consulting (BLUE), Comments on the 
ANPRM, Docket ID PHMSA-2019-0091-7503 (July 1, 2025) (discussing LNG 
FAQs).
    \79\ See, e.g., Williams Cos., Comments on the ANPRM, Docket ID 
PHMSA-2019-0091-7612 (July 7, 2025).
---------------------------------------------------------------------------

    To address these concerns, PHMSA proposes to incorporate the latest 
edition of NFPA 59A by reference and to expand reliance on the 
mandatory provisions in that standard in part 193.\80\ NFPA 59A-2026 is 
a consensus standard generated by industry and Federal and State 
regulators; public safety advocates have also endorsed its

[[Page 69325]]

incorporation by reference in part 193.\81\ PHMSA expects that greater 
reliance on NFPA 59A-2026 will improve LNG safety, as the mandatory 
provisions in that standard contain far more detailed and comprehensive 
requirements than its 2001 counterpart. The technically rigorous, 
transparent process employed in the development of each edition of NFPA 
59A ensures that the latest edition aligns with current practices in 
the LNG industry.\82\ NFPA 59A-2026 also includes informational annexes 
to assist stakeholders in understanding its mandatory requirements.
---------------------------------------------------------------------------

    \80\ PHMSA understands ``mandatory provisions'' consists of 
those provisions with imperative language (e.g., ``shall'') within 
chapters 4 through 19 of NFPA 59A-2026. PHMSA proposes to exclude 
the contents of chapter 1 (Administrative) from those mandatory 
provisions of NFPA 59A-2026 due to potential tension with statutory 
provisions pertaining to the scope of PHMSA's jurisdiction, 
retroactive application of certain safety requirements, and special 
permits granting waivers from part 193 requirements.
    \81\ Earthjustice & Env't Def. Fund (EDF), Comments on the 
ANPRM, Docket ID PHMSA-2019-0091-7596, at 1 (July 7, 2025).
    \82\ The NFPA website (<a href="https://www.nfpa.org/codes-and-standards/nfpa-59a-standard-development/59a">https://www.nfpa.org/codes-and-standards/nfpa-59a-standard-development/59a</a>) contains extensive documentation 
elaborating on the technical basis for revisions within each of the 
post-2006 editions of NFPA 59A and memorializing the Technical 
Committee's consideration of those revisions.
---------------------------------------------------------------------------

B. Subpart A--General

    Subpart A sets forth general rules governing application, 
interpretation, and implementation of part 193 regulations. It also 
contains a general requirement for operators to have and maintain plans 
and procedures as required by part 193.
    PHMSA proposes to retain the existing provisions in subpart A, 
subject to the redesignation and revision of certain provisions. PHMSA 
is not proposing to incorporate the ``Administrative'' provisions in 
NFPA 59A-2026 due to potential inconsistencies with the requirements in 
the Pipeline Safety Laws.\83\
---------------------------------------------------------------------------

    \83\ Among those provisions of NFPA 59A-2026 that PHMSA declines 
to incorporate by reference is the ``equivalency'' language at 
section 1.4. PHMSA has in the past employed similar language in 
section 1.2 of NFPA 59A-2001 to assist operators in overcoming the 
practical consequences of PHMSA's delay in updating its part 193 
regulations. See LNG FAQs, D5-D6. However, PHMSA understands that 
NFPA 59A-2001 language was never explicitly incorporated by 
reference into its part 193 regulations. In addition, PHMSA 
regulations at Sec.  190.341 allow operators to apply for special 
permits requesting waivers of part 193 requirements, and PHMSA has 
broad authority to exercise its enforcement discretion to minimize 
liability risks arising from future delays in updating its 
regulations.
---------------------------------------------------------------------------

B.1. Section 193.1--Scope of Part
    PHMSA proposes to redesignate in a new Sec.  193.1 much of the 
language currently located in Sec.  193.2001 describing the scope of 
the part 193 requirements. To provide additional clarity and ensure 
consistency with the terminology used in the USCG regulations for 
waterfront LNG facilities, PHMSA proposes to modify the exception in 49 
CFR 193.1(b)(3). The exception, as currently codified at Sec.  
193.2001(b)(3), limits the applicability of part 193 to marine cargo 
transfer systems at waterfront LNG facilities to matters related to 
siting.
    The term ``marine cargo transfer system'' is not defined in part 
193 or used in the parallel USCG regulations for waterfront LNG 
facilities. Instead, the USCG regulations use the term ``marine 
transfer area for LNG,'' which is defined as ``that part of a 
waterfront facility handling LNG between the vessel, or where the 
vessel moors, and the last manifold or valve immediately before the 
receiving tanks.'' That definition is consistent with the current 
limitation on part 193 applicability in Sec.  193.2001(b)(3), which 
also refers to ``the marine vessel and the last manifold (or in the 
absence of a manifold, the last valve) located immediately before a 
storage tank'' in describing a marine cargo transfer system.
    Rather than having parallel provisions that use slightly different 
terminology, PHMSA proposes to incorporate the phrase ``marine transfer 
area for LNG as defined in 33 CFR 127.005'' directly into the new 
version of the scope requirements in Sec.  193.1(b)(3). PHMSA also 
proposes to eliminate the remaining language from the current provision 
in Sec.  193.2001(b)(3), which is not necessary as the definition of 
``marine transfer area for LNG'' in 33 CFR 127.005 incorporates the 
relevant breakpoints used in delineating the scope of part 193 at 
waterfront LNG facilities. PHMSA does not intend this change to be 
substantive in nature or to alter the longstanding approach used in 
prescribing the scope of part 193's applicability at waterfront LNG 
facilities.
B.2. Section 193.3--Applicability
    PHMSA proposes to redesignate the applicability requirements 
currently prescribed in Sec.  193.2005 under a new Sec.  193.3. 
Consistent with historical practice, Sec.  193.3 would continue to 
reference the effective date of any final rule in this proceeding in 
prescribing the applicability of any part 193 subparts governed by the 
statutory retroactivity prohibition at 49 U.S.C. 60103(c) and 
60104(b)(2). PHMSA also proposes to clarify the scope of that 
prohibition by stating in Sec.  193.3(a) that the requirements in the 
non-retroactive subparts do not apply to existing LNG facilities or to 
proposed LNG facilities that an appropriate authority approved before 
those requirements went into effect. In addition, PHMSA proposes to 
remove from Sec.  193.3(b) the current requirement at Sec.  
193.2005(b)(2) that PHMSA approve exceptions from retroactive 
application of updated part 193 design, installation, and construction 
requirements for so-called ``in-kind'' replacements of facilities 
designed, installed, and constructed in accordance with original 
facility specifications. This proposed change will improve alignment 
with analogous provisions (particularly section 1.4.4) in NFPA 59A-
2026. PHMSA also proposes a revision to Sec.  193.3(b)(2) to clarify 
application of the ``in-kind'' replacement provision to LNG storage 
tanks replacement projects that increase capacity or relocate the 
tank(s).
B.3. Section 193.5--Definitions
    PHMSA proposes to redesignate the existing Sec.  193.2007 as a new 
Sec.  193.5 and to incorporate by reference the definitions in chapter 
3 of NFPA 59A-2026 in lieu of the existing definitions in Sec.  
193.2007, subject to certain exceptions and modifications as discussed 
below. PHMSA understands that the definitions listed in NFPA 59A-2026 
chapter 3 as supplemented or substituted by the definitions in the new 
Sec.  193.5 would govern the meaning of both NFPA 59A-2026 and part 
193.
Administrator
    PHMSA proposes to retain the existing definition of 
``Administrator'' in Sec.  193.5. NFPA 59A-2026 includes a definition 
of an ``Authority Having Jurisdiction (AHJ)'' and in various places 
references the need for AHJ approval. For purposes of PHMSA's 
application of the NFPA 59A-2026 provisions being incorporated into 
part 193 referencing an AHJ or ``approval,'' the AHJ will typically 
(unless PHMSA has resolved the issue generically via part 193 
regulatory text) be the PHMSA Administrator (or his delegate) by way of 
an operator-specific Sec.  190.341 special permit process.\84\ However, 
some NFPA 59A-2026 references to an ``AHJ'' may implicate the 
prerogative of other regulatory authorities; in those cases, PHMSA 
proposes to include within part 193 provisions disclaiming 
administration of an AHJ authorization called for by NFPA 59A-2026 
language.\85\
---------------------------------------------------------------------------

    \84\ PHMSA does not generally understand references within NFPA 
59A-2026 to ``AHJ approvals'' to implicate the procedural machinery 
at Sec.  190.9--an exception from this general rule being approval 
of model evaluation protocols (MEPs) and model validation databases 
(MVDs) in connection with siting analyses.
    \85\ PHMSA acknowledges requests by multiple industry 
stakeholders for improved allocation of responsibilities among 
different Federal agencies with statutory authority over LNG 
facilities--with some calling for each agency to have primary 
responsibility for one or another dimension of LNG facilities 
activities. See, e.g., Joint Trade Associations, Comments on the 
ANPRM, Docket ID PHMSA-2019-0091-7611, at 2-3. The fact that 
multiple Federal agencies share overlapping regulatory oversight 
authority over LNG facilities reflects congressional intent; PHMSA 
is, therefore, constrained in its ability to impose by amendments to 
its part 193 regulations boundaries on other agencies' exercise of 
their statutory prerogatives. That said, PHMSA will work with other 
Federal agencies to update pertinent interagency agreements to 
address this concern.

---------------------------------------------------------------------------

[[Page 69326]]

Component
    PHMSA proposes to retain within Sec.  193.5 the existing definition 
of ``component,'' albeit with revisions to improve readability. PHMSA 
also proposes to add a reference to ``pressure vessel'' within the list 
of examples of ``components'' for additional clarity.
Design Pressure
    PHMSA proposes to retain at Sec.  193.5 the existing definition of 
``design pressure.'' Section 193.2007 currently defines ``design 
pressure'' to mean ``the pressure used in the design of components for 
the purpose of determining the minimum permissible thickness or 
physical characteristics of its various parts . . . .'' NFPA 59A-2026 
adopts a similar definition for ``design pressure'' but, unlike NFPA 
59A-2001, omits the statement ``when applicable, the static head must 
be included in the design pressure to determine the thickness of any 
specific part.'' Because NFPA 59A-2026 removed that statement, PHMSA 
proposes to retain the current definition in part 193.
Design Spill
    PHMSA proposes to add at Sec.  193.5 a new definition for the term 
``design spill,'' which would mean ``a potential spill or release from 
LNG and hazardous fluid containers, piping, and equipment at 
liquefaction, storage, transfer, or other process areas in an LNG 
facility.'' NFPA 59A-2026 uses but does not define the term ``design 
spill.'' PHMSA proposes to address that omission by defining the term 
``design spill'' in the new Sec.  193.5.
Determine
    PHMSA proposes to retain at Sec.  193.5 the existing definition of 
``determine.'' Section 193.2007 currently defines ``determine'' as 
meaning to ``make a decision based on an appropriate investigation 
using scientific methods and sound engineering judgment, including 
documentation that demonstrates the basis of the decision.'' NFPA 59A-
2026 uses but does not define the term ``determine.'' PHMSA proposes to 
retain the existing definition in part 193 to address that gap and 
provide interested stakeholders with additional regulatory certainty.
Emergency
    PHMSA proposes to retain at Sec.  193.5 and to revise for clarity 
the existing definition of ``emergency.'' Section 193.2007 currently 
defines an ``emergency'' to mean ``a deviation from normal operation, a 
structural failure, or severe environmental conditions that probably 
would cause harm to people or property.'' NFPA 59A-2026 does not define 
the term ``emergency.'' PHMSA proposes to retain the current definition 
to address that gap and to provide interested stakeholders with 
additional regulatory certainty.
Exclusion Zone
    PHMSA proposes to retain at Sec.  193.5 and to revise the existing 
definition of ``exclusion zone'' with minor revisions. Section 193.2007 
currently defines ``exclusion zone'' to mean ``an area surrounding an 
LNG facility in which an operator or government agency legally controls 
all activities in accordance with Sec.  193.2057 and Sec.  193.2059 for 
as long as the facility is in operation.'' NFPA 59A-2026 does not 
define or use the term ``exclusion zone.'' PHMSA proposes to retain the 
existing definition in part 193 with an updated reference to subpart B 
siting requirements to accommodate other changes proposed in the NPRM. 
PHMSA is also proposing a minor revision to the existing regulatory 
text (``area within or surrounding an LNG facility'') to account for 
the fact that exclusion zones may surround an LNG facility even as they 
may be within the boundary of an LNG plant consisting of multiple LNG 
facilities.
Gas
    PHMSA proposes to retain at the new Sec.  193.5 the existing 
definition of ``gas.'' Section 193.2007 currently defines ``gas'' as 
``except when designated as inert, . . . natural gas, other flammable 
gas, or gas which is toxic or corrosive.'' NFPA 59A-2026 does not 
define the term ``gas.'' PHMSA proposes to retain the existing 
definition to provide interested stakeholders with additional 
regulatory certainty.
Hazardous Fluid
    PHMSA proposes to retain at the new Sec.  193.5 the existing 
definition of ``hazardous fluid,'' albeit with certain revisions. 
Section 193.2007 currently defines the term ``hazardous fluid'' to mean 
``gas or hazardous liquid.'' The terms ``gas'' and ``hazardous liquid'' 
are further defined, respectively, as ``except when designated as 
inert, . . . natural gas, other flammable gas, or gas which is toxic or 
corrosive'' and ``LNG or a liquid that is flammable or toxic.'' NFPA 
59A-2026 provides a slightly different definition for ``hazardous 
fluid'' in that it uses the term ``ignitible'' in lieu of 
``flammable,'' ostensibly to improve the scientific precision of the 
defined term. NFPA 59A-2026 also refers to both ``gas'' and ``hazardous 
liquids'' as potentially including corrosive substances.
    PHMSA proposes to retain the existing reference to ``flammable'' 
rather than to substitute the term ``ignitible'' in the definition. The 
term ``flammable'' has long been used in the existing definition at 
Sec.  193.2007 and mirrors corresponding statutory language at 49 
U.S.C. 60101(a)(2)-(a)(4). PHMSA notes that the substitution of 
``ignitible'' may not entirely resolve ambiguity in the regulatory 
language.\86\
---------------------------------------------------------------------------

    \86\ See BLUE, Comments on the ANPRM, Docket ID PHMSA-2019-0091-
7503, at 11 (criticizing the introduction of the ``ignitable'' 
language as ``add[ing] additional vagueness.'').
---------------------------------------------------------------------------

    PHMSA expects that the revised definition of ``hazardous fluid'' at 
Sec.  193.5 will enhance safety at LNG facilities. Both the existing 
part 193 regulations and comparable provisions of NFPA 59A-2001 are 
largely directed toward addressing the public safety risks associated 
with LNG. However, subsequent editions of NFPA 59A have increasingly 
used the broader term ``hazardous fluid,'' expanding the scope of 
public safety risks (and corresponding LNG facility equipment, 
components, and processing activities) addressed under the provisions 
in that standard. PHMSA further notes that the revised definition 
conforms with the proposed revisions to the reporting requirements for 
LNG facilities at Sec.  191.3, which would expand the incident, annual, 
and safety-related condition reporting to include the non-exhaustive 
list of ``hazardous fluids'' described in section III.A above.
Hazardous Liquid
    PHMSA proposes to retain at Sec.  193.5 and to revise the existing 
definition of ``hazardous liquid.'' Section 193.2007 currently defines 
``hazardous liquid'' as ``LNG or a liquid that is flammable or toxic.'' 
NFPA 59A-2026 does not define this term. PHMSA's enabling statute 
acknowledges at 49 U.S.C. 60101(a)(4)(B)-(C) that a hazardous liquid 
can be a substance that is ``corrosive,'' and some of the materials 
present in liquid form within processes at LNG facilities (e.g., 
hydrogen sulfide, anhydrous ammonia) are in fact corrosive for human 
tissue. For that reason, PHMSA proposes to add the term ``corrosive'' 
to the existing

[[Page 69327]]

definition of hazardous liquid in part 193.
Impounding System
    PHMSA proposes to retain at Sec.  193.5 and to revise the existing 
definition of ``impounding system.'' Section 193.2007 currently defines 
``impounding system'' as ``an impounding space, including dikes and 
floors for conducting the flow of spilled hazardous liquids to an 
impounding space.'' NFPA 59A-2026 does not define an ``impounding 
system'' but uses the term throughout the document. To provide 
additional regulatory certainty, PHMSA proposes to retain the 
definition for ``impounding system'' in part 193. However, PHMSA 
proposes to replace the term ``impounding space'' with ``impounding 
area'' for clarity by adopting the more modern term used by newer 
editions of NFPA 59A.
Liquefied Natural Gas or LNG
    PHMSA proposes to retain at Sec.  193.5 and to revise for editorial 
clarity the existing definition of LNG. Section 193.2007 currently 
defines ``LNG'' as ``natural gas or synthetic gas having methane 
(CH<INF>4</INF>) as its major constituent which has been changed to a 
liquid.'' PHMSA proposes to clarify that definition by replacing the 
word ``which'' with ``that'' to ensure a more precise definition.
LNG Facility
    PHMSA proposes to retain at Sec.  193.5 and to revise the existing 
definition of ``LNG facility.'' Section 193.2007 currently defines 
``LNG facility'' as a ``pipeline facility that is used for liquefying 
natural gas or synthetic gas or transferring, storing, vaporizing 
liquefied natural gas, including on-site power generation facilities.'' 
PHMSA proposes to add to this definition an explicit reference to ``on-
site power generation facilities.'' That addition is consistent with 
PHMSA's longstanding understanding that ``on-site power facilities'' 
are ``LNG facilities'' subject to the requirements in part 193.\87\ 
PHMSA further notes that this addition enhances public safety by 
ensuring that on-site power generation facilities (some of which may 
use fuels that are themselves flammable or explosive) are subject to 
the same safety standards as other LNG facilities.
---------------------------------------------------------------------------

    \87\ A 1980 final rule explicitly included power generation 
facilities within the scope of LNG facilities. See RSPA, Liquefied 
Natural Gas Facilities; New Federal Safety Standards, 45 FR 9184, 
9189, 9197-98 (Feb. 11, 1980). PHMSA consistently has held this to 
be the case since, even as a reference to power generation 
facilities in Sec.  193.2051 was omitted for other reasons. See, 
e.g., RSPA, Pipeline Safety: Incorporation of Standard NFPA 59A in 
the Liquefied Natural Gas Regulations, 65 FR 10958 (Mar. 1, 2000).
---------------------------------------------------------------------------

Maximum Allowable Working Pressure (MAWP)
    PHMSA proposes to retain in Sec.  193.5 the current definition of 
``maximum allowable working pressure (MAWP).'' Section 193.2007 
currently defines MAWP as ``the maximum gauge pressure permissible at 
the top of the equipment, containers, or pressure vessels while 
operating at design temperature.'' NFPA 59A-2026 adopts a similar 
definition, except that it specifies the maximum pressure permissible 
at the top of ``completed equipment.'' PHMSA is not aware of the 
reasoning behind the reference in NFPA 59A-2026 to ``completed 
equipment'' in defining MAWP. To avoid introducing unnecessary 
confusion as to whether ``equipment'' is completed or not, PHMSA 
proposes to retain the existing part 193 definition of MAWP.
Normal Operation
    PHMSA proposes to retain at Sec.  193.5 and to revise for clarity 
the existing definition of ``normal operation.'' Section 193.2007 
currently defines ``normal operation'' as ``functioning within 
allowable ranges of pressure, temperature, flow, and other operating 
criteria consistent with the requirements of this part.'' NFPA 59A-2026 
does not define this term. Accordingly, PHMSA proposes to retain the 
current definition without change.
Operator
    PHMSA proposes to retain at Sec.  193.5 and to revise the existing 
definition of the term ``operator'' to align with the definition of 
``liquefied natural gas pipeline facility'' in 49 U.S.C. 60101(a)(14). 
Section 193.2007 currently defines LNG facility as ``a pipeline 
facility that is used for liquefying natural gas or synthetic gas or 
transferring, storing, or vaporizing liquefied natural gas.'' Though an 
LNG facility is a type of ``pipeline facility'' as that term is defined 
in the Pipeline Safety Act, 49 U.S.C. 60101(a)(18) and 49 CFR 193.2007, 
NFPA 59A-2026 does not define this term. Moreover, section 193.2007 
currently defines an ``operator'' as a ``person who owns or operates an 
LNG facility.'' To ensure consistency with the definitions in the 
Pipeline Safety Act and implementing regulations, PHMSA proposes to 
revise the definition of ``operator'' in part 193 to mean ``a person 
who owns or operates a pipeline facility.'' PHMSA notes that a person 
seeking authorization to construct and operate planned LNG facilities 
is an ``operator'' for purposes of this definition.
Person
    PHMSA proposes to retain at Sec.  193.5 and to revise for 
readability the existing definition of ``person'' in part 193. Section 
60101(a)(17) of the Pipeline Safety Act defines a ``person'' as ``in 
addition to its meaning under section 1 of title 1 (except as to 
societies), includes a State, a municipality, and a trustee, receiver, 
assignee, or personal representative of a person.'' \88\ Similarly, 
section 193.2007 currently defines a ``person'' as ``any individual, 
firm, joint venture, partnership, corporation, association, State, 
municipality, cooperative association, or joint stock association, and 
includes any trustee, receiver, assignee, or personal representative 
thereof.'' NFPA 59A-2026 does not define this term. The proposed 
definition improves readability by replacing the phrase ``and 
includes'' with ``including'' and standardizing capitalization for 
regulatory entities (e.g., State), thereby ensuring the language is 
consistent with conventions elsewhere in part 193 regulations.
---------------------------------------------------------------------------

    \88\ 1 U.S.C. 1 (defining ``person'' to ``include corporations, 
companies, associations, firms, partnerships, societies, and joint 
stock companies, as well as individuals'').
---------------------------------------------------------------------------

Pipeline Facility
    PHMSA proposes to retain at Sec.  193.5 but to revise for 
readability the existing definition of ``pipeline facility'' in part 
193. Section 193.2007 currently defines ``pipeline facility'' to mean 
``new and existing piping, rights-of-way, and any equipment, facility, 
or building used in the transportation of gas or in the treatment of 
gas during the course of transportation.'' An LNG facility is a type of 
pipeline facility. NFPA 59A-2026 does not define this term. The 
proposed definition includes LNG facilities to reinforce that an LNG 
facility is a type of pipeline facility.
Piping
    PHMSA proposes to retain at Sec.  193.5 but to revise for clarity 
the existing definition of ``piping'' in part 193. Section 193.2007 
currently defines ``piping'' as ``pipe, tubing, hoses, fittings, 
valves, pumps, connections, safety devices or related components for 
containing the flow of hazardous fluids.'' NFPA 59A-2026 does not 
define this term. The proposed definition enhances specificity by 
replacing the general term ``pipe'' with the more precise ``line pipe'' 
language used elsewhere in PHMSA regulations.

[[Page 69328]]

Transfer Piping
    PHMSA proposes to retain at Sec.  193.5 but to revise for clarity 
the existing definition of ``transfer piping'' in part 193. Section 
193.2007 currently defines ``transfer piping'' as ``a system of 
permanent and temporary piping used for transferring hazardous fluids 
between any of the following: Liquefaction process facilities, storage 
tanks, vaporizers, compressors, cargo transfer systems, and facilities 
other than pipeline facilities.'' PHMSA believes that, as currently 
written, the phrase ``a system of permanent and temporary piping'' 
might imply the transfer system must include both permanent and 
temporary piping for the term to meet the definition, which is not the 
case.\89\ Therefore, PHMSA proposes to revise the definition of 
``transfer piping'' to mean ``a system of permanent or temporary 
piping, or both, used for transferring hazardous fluids between any of 
the following: liquefaction process facilities, storage tanks, 
vaporizers, compressors, cargo transfer systems, and facilities other 
than pipeline facilities.''
---------------------------------------------------------------------------

    \89\ See PHMSA, PI-10-0200, Interpretation Response re Mount Bay 
Hope Liquefied Natural Gas Transfer System (Mar. 25, 2010), 
available at: <a href="https://www.phmsa.dot.gov/regulations/title49/interp/pi-10-0020">https://www.phmsa.dot.gov/regulations/title49/interp/pi-10-0020</a> (discussing definition of ``transfer piping'' and 
``transfer system'').
---------------------------------------------------------------------------

Transfer System
    PHMSA proposes to retain at Sec.  193.5 the existing definition of 
``transfer system'' in part 193. Section 193.2007 currently defines 
``transfer system'' to ``include [ ] transfer piping and cargo transfer 
systems.'' NFPA 59A-2026 does not define a transfer system; however, 
the term is used throughout the document and part 193. PHMSA proposes 
to retain the definition to support operators' understanding of the 
regulations.
Vaporization
    PHMSA proposes to retain at Sec.  193.5 the existing definition of 
``vaporization'' in part 193. NFPA 59A-2026 does not define 
vaporization; however, the term is used throughout the document and 
part 193. PHMSA proposes to retain the definition to support operators' 
understanding of the regulations.
B.4. Section 193.7--Rules of Regulatory Construction
    PHMSA proposes to revise the requirements in the existing Sec.  
193.2009 and to relocate them to a new Sec.  193.7. The provision 
defines regulatory terms used in part 193, such as ``must'' and 
``shall.''
B.5. Section 193.9--What documents are incorporated by reference partly 
or wholly in this part?
    PHMSA proposes to incorporate by reference new or updated editions 
of consensus industry standards currently referenced in part 193. PHMSA 
also proposes to incorporate by reference additional consensus industry 
standards to improve enforceability. Below is a list of new or updated 
standards proposed for incorporation by reference into part 193; any 
standards not listed below that are currently incorporated by reference 
into PHMSA regulations would no longer be incorporated by reference 
into part 193.
    As discussed in section IV.A. above, PHMSA proposes to incorporate 
the mandatory provisions in the latest 2026 edition of NFPA 59A as the 
core of its regulatory framework for LNG facilities. NFPA 59A-2026 is 
therefore discussed first in this section IV.B.5, with other standards 
proposed to be incorporated by reference in PHMSA regulations appearing 
by the issuing standards development organizations thereafter. Most of 
the standards listed thereafter for incorporation by reference within 
part 193 are listed as mandatory references in chapter 2 of NFPA 59A-
2026.
    PHMSA also proposes incorporation by reference of one additional 
standard currently incorporated by reference at Sec.  193.2013 and 
another standard informing compliance with the alternative risk-based 
O&M approach at subpart F. In contrast, PHMSA does not propose to 
include within Sec.  193.9 standards not discussed below--even if those 
standards were listed among the mandatory references listed in NFPA 
59A-2026 chapter 2 or the informational references within NFPA 59A-2026 
Annex C. Instead, those standards should be considered non-binding 
guidance assisting operators in developing their part 193 compliance 
strategies. Similarly, PHMSA does not propose to incorporate by 
reference some of the consensus industry standards discussed in section 
IV.G below, even as PHMSA understands those resources could function as 
non-binding guidance informing operators' development of the risk-based 
O&M alternative framework mandated by section 110 of the PIPES Act of 
2020. PHMSA invites public comment on whether to incorporate any 
industry standard referenced in NFPA 59A-2026 or otherwise applicable 
to the LNG industry.
    The standards listed below for inclusion within the new Sec.  193.9 
are reasonably available to interested parties in several ways. First, 
PHMSA has negotiated agreements with some standards development 
organizations to make viewable copies of the standards available to the 
public at no cost. Organizations that have agreed to the public access 
requirements of the statutory mandate discussed above include the 
American Petroleum Institute (API), the American Gas Association (AGA), 
ASTM International (formerly the American Society for Testing and 
Materials), and the National Fire Protection Association (NFPA). Those 
organizations' standards can be accessed through the websites listed in 
the proposed Sec.  193.9 regulatory text. Second, interested persons 
may obtain (on loan from PHMSA) physical copies of standards issued by 
organizations with which PHMSA has not at the time of publication of 
this NPRM been able to reach a general agreement for free online 
access. Those organizations include the American Society of Mechanical 
Engineers (ASME), the American Society for Nondestructive Testing 
(ASNT), American Concrete Institute (ACI), American Society of Civil 
Engineers (ASCE), Brazed Aluminum Plate-fin Heat Exchanger 
Manufacturers' Association (ALPEMA), Center for Chemical Process Safety 
(CCPS), Compressed Gas Association (CGA), CSA Group (CSA), 
International Society of Automation (ISA), National Board of Boiler and 
Pressure Vessel Inspectors (NBBI), and UL Solutions. Interested persons 
seeking a loan of a physical copy of a standard issued by those 
organizations may contact the PHMSA standards library (at the email 
address: <a href="/cdn-cgi/l/email-protection#73031b1e0012031b030007121d171201170033171c075d141c05"><span class="__cf_email__" data-cfemail="fc8c94918f9d8c948c8f889d92989d8e988fbc989388d29b938a">[email&#160;protected]</span></a>; such requests should include a 
phone number, physical address, and an email address), or through the 
contact information listed in the proposed Sec.  193.9 amendatory text. 
Additional information regarding standards availability can be found at 
<a href="https://www.phmsa.dot.gov/standards-rulemaking/pipeline/standards-incorporated-reference">https://www.phmsa.dot.gov/standards-rulemaking/pipeline/standards-incorporated-reference</a>.
NFPA 59A-2026
    As discussed in section IV.A. above, PHMSA proposes to incorporate 
by reference into part 193 the mandatory provisions in the 2026 edition 
of NFPA 59A. PHMSA proposes to delete all existing references to the 
2001 and 2006 editions of NFPA 59A. NFPA 59A-2026 provides minimum fire 
protection and safety requirements for the location, design, 
construction, security, operation, and maintenance of liquefied natural 
gas (LNG) plants.

[[Page 69329]]

Standards Incorporated by Reference in NFPA 59A-2026
    PHMSA proposes to incorporate by reference into part 193 certain 
consensus industry standards that are referenced in the mandatory 
provisions in chapter 2 of NFPA 59A-2026. PHMSA identifies these new 
standards in the table below, which would be incorporated into the new 
Sec.  193.9. PHMSA has reviewed the content and preliminarily concluded 
that each standard contributes to the improvement of public safety. 
PHMSA notes in the table below the provisions of NFPA 59A-2026 that are 
proposed for incorporation and the purpose for doing so. PHMSA solicits 
comment on these provisions and on any additional standards that should 
be incorporated by reference within a final rule.\90\
---------------------------------------------------------------------------

    \90\ PHMSA acknowledges that the above table does not identify 
every mandatory standard listed in chapter 2 of NFPA 59A-2026. PHMSA 
has tried to limit the standards proposed for incorporation by 
reference to those that are most critical to the understanding and 
enforceability of the design, installation, construction, and 
operations and maintenance requirements in NFPA 59A-2026.
---------------------------------------------------------------------------

BILLING CODE 4910-60-P
[GRAPHIC] [TIFF OMITTED] TP03NO26.008


[[Page 69330]]


[GRAPHIC] [TIFF OMITTED] TP03NO26.009


[[Page 69331]]


[GRAPHIC] [TIFF OMITTED] TP03NO26.010


[[Page 69332]]


[GRAPHIC] [TIFF OMITTED] TP03NO26.011


[[Page 69333]]


[GRAPHIC] [TIFF OMITTED] TP03NO26.012


[[Page 69334]]


[GRAPHIC] [TIFF OMITTED] TP03NO26.013


[[Page 69335]]


[GRAPHIC] [TIFF OMITTED] TP03NO26.014


[[Page 69336]]


[GRAPHIC] [TIFF OMITTED] TP03NO26.015


[[Page 69337]]


[GRAPHIC] [TIFF OMITTED] TP03NO26.016


[[Page 69338]]


[GRAPHIC] [TIFF OMITTED] TP03NO26.017


[[Page 69339]]


[GRAPHIC] [TIFF OMITTED] TP03NO26.018


[[Page 69340]]


[GRAPHIC] [TIFF OMITTED] TP03NO26.019


[[Page 69341]]


[GRAPHIC] [TIFF OMITTED] TP03NO26.020


[[Page 69342]]


[GRAPHIC] [TIFF OMITTED] TP03NO26.021


[[Page 69343]]


[GRAPHIC] [TIFF OMITTED] TP03NO26.022


[[Page 69344]]


[GRAPHIC] [TIFF OMITTED] TP03NO26.023

BILLING CODE 4910-60-C
American Gas Association (AGA)
    PHMSA also proposes to incorporate by reference in Sec.  193.403(a) 
AGA's Purging Manual, Fourth edition, published in September 2018. The 
Purging Manual provides principles and general procedures for purging 
pipeline

[[Page 69345]]

systems containing flammable gas to maintain safety.
    In this NPRM, PHMSA proposes new purging requirements in Sec.  
193.403, which are discussed in more detail in section IV.F.5. As part 
of those requirements, PHMSA proposes that purging be performed in 
accordance with the Purging Manual as well as NFPA 59A-2026. Chapter 1 
of the Purging Manual contains requirements such as requiring operators 
to prepare written site-specific purging procedures and hazard 
assessments detailing the sequence of events, a predetermined rate of 
introduction of a purge medium, and verification of endpoints at 
properly vented locations. These steps must be followed and carried out 
by properly trained and qualified individuals. Chapter 1 further 
requires operators to plan for the safety of plant personnel, such as 
requiring appropriate personal protective equipment and the 
identification of hazardous materials. Chapter 6 of the Purging Manual 
contains specific purging requirements for different types of LNG 
storage tanks.
    The Fourth edition of the AGA Purging Manual contains a substantial 
revision to the currently incorporated Third edition to include more 
comprehensive guidance and modern purging techniques. For example, 
chapter 1 now requires management of change, lock out/tag out, and 
instruction and assignment of personnel to be included in written 
plans. Chapter 6 also expands the general requirements and includes a 
description of LNG facilities and the physical properties of LNG. The 
Fourth edition adds LNG trucking cargo tanks to the purging 
requirements as well. Finally, the Fourth edition also changes the name 
of the standard from ``Purging Principles and Practices'' to ``Purging 
Manual.'' PHMSA believes that these updates will be beneficial to 
safety.
American Institute of Chemical Engineers, Center for Chemical Process 
Safety
    PHMSA proposes to incorporate by reference into Sec.  193.503 the 
Center for Chemical Process Safety's (CCPS's) Guidelines for Hazard 
Evaluation Procedures (Guidelines), Third edition, published in April 
2008. The Guidelines provide principles and general procedures for 
performing process hazard assessments (PHAs) and evaluating and 
implementing of the results of PHAs. As discussed in section IV.G, 
PHMSA proposes in Sec.  193.503 that FERC jurisdictional LNG facilities 
design and implement their subpart F, PHA-based O&M programs consistent 
with the Guidelines.
B.6. Section 193.11--Plans and Procedures
    PHMSA proposes to revise the existing plans and procedures 
regulations in Sec.  193.2017. First, PHMSA proposes to redesignate the 
current Sec.  193.2017(a) as a new Sec.  193.11(a) and to modify the 
regulation to specify that operators must maintain written plans and 
procedures in accordance with part 193 and NFPA 59A-2026. Currently, 
Sec.  193.2017 requires operators to maintain plans and procedures and 
to make them available to PHMSA upon request. Each change to a plan or 
procedure must be available at the LNG plant for review and inspection 
within 20 days after the change is made. PHMSA's proposed modifications 
would retain the current requirements and adopt the provisions in NFPA 
59A-2026.
    PHMSA proposes to remove Sec.  193.2017(b). Section 193.2017(b) 
currently states that operators must amend their plans and procedures 
as necessary to ensure safety. The same obligation is also imposed by 
regulation in Sec.  190.206. To avoid unnecessary duplication, PHMSA 
proposes to delete Sec.  193.2107(b) and to maintain this requirement 
in Sec.  190.206.
    PHMSA proposes to redesignate the existing Sec.  193.2017(c) 
requirements for periodic review of plans and procedures with a new 
Sec.  193.11(b). PHMSA further notes that, on or before the effective 
date of a final rule in this proceeding, operators would need to 
review, and if necessary, to update their plans and procedures to 
reflect the requirements of the new part 193.
    PHMSA proposes in a new Sec.  193.11(c) to require operators to 
record and to maintain a change log detailing changes to plans and 
procedures, showing revisions from the previous version. This change 
log is consistent with widely employed quality control practices to 
ensure documentation of effective plans and procedures to facilitate 
continual process improvement, system integrity evaluation, and failure 
investigations. Unless a different timeframe for specific plans and 
procedures is required by another provision of part 193 (and, by 
extension, NFPA 59A-2026), PHMSA proposes that operators keep a record 
of the change log for the lifetime of the component(s) governed by the 
procedures.
B.7. Section 193.13--Mobile and Temporary LNG Facilities
    PHMSA proposes to update the regulations governing mobile and 
temporary LNG facilities currently found at Sec.  193.2019.\91\ These 
revisions involve a redesignation to a new Sec.  193.13, as well as 
editorial changes to enhance readability. PHMSA proposes to align these 
regulations with the latest safety standards by requiring operators of 
mobile and temporary LNG facilities to follow the governing provisions 
in chapter 14 of NFPA 59A-2026.
---------------------------------------------------------------------------

    \91\ PHMSA also solicits comment on whether to amend Sec.  
193.2019 (repeated in Sec.  193.13 as proposed) to communicate 
better that PHMSA has regulatory authority to ensure compliance of 
mobile and temporary facilities with the requirements of part 193 
(including those provisions of chapter 14 of NFPA 59A-2026 
incorporated therein).
---------------------------------------------------------------------------

    PHMSA is proposing these changes to address the ambiguity in the 
existing language of Sec.  193.2019. Similar to other provisions in 
part 193, Sec.  193.2019 currently includes a broad reference to 
``applicable sections of NFPA 59A-2001'' in describing the requirements 
applicable to mobile and temporary LNG facilities. The ``applicable'' 
provision of NFPA 59A-2001 (specifically, section 2.3.4) contains a 
limited set of personnel training, design, and operations requirements 
commensurate with the lower public safety risks posed by those 
facilities, but lacks threshold criteria defining which facilities are 
or are not eligible for those regulatory flexibilities. In fact, 
section 2.3.4 is directed principally at temporary LNG facilities, 
though NFPA 59A-2001 provides no criteria for distinguishing between 
``temporary'' and more permanent, ``stationary'' LNG facilities. In 
addition, the language at current Sec.  193.2019 is potentially 
overbroad in that it could be read to suggest mobile and temporary 
facilities are exempted from the entirety of part 193--including the 
provisions (regulatory definitions, statements of scope, etc.) of 
subpart A.
    Chapter 14 of the updated NFPA 59A-2026 addresses these omissions 
and enhances the safety requirements governing mobile and temporary LNG 
facilities. In addition to being explicitly directed toward temporary 
and mobile LNG facilities, chapter 14 introduces a default, six-month 
durational criteria for distinguishing between ``mobile and temporary'' 
and other (e.g., permanent) LNG facilities. Chapter 14 also includes a 
process that allows operators to extend that six-month period, either 
by requesting permission from PHMSA via a special permit application or 
by complying with additional safety and security requirements for 
permanent, small-scale LNG facilities.
    Further, NFPA 59A-2026 chapter 14 contains more robust safety 
requirements as compared to section 2.3.4 of NFPA 59A-2001. Chapter 14 
of

[[Page 69346]]

NFPA 59A-2026 retains all of its predecessor's content while 
introducing references to detailed new requirements for qualification 
and training of personnel; facility and process equipment design, 
construction and installation; fire protection systems and physical 
security; transfer operations; operation and maintenance; and corrosion 
protection.\92\ NFPA 59A-2026 also explicitly authorizes the use of 
cryogenic PIP systems within mobile and temporary LNG facilities.
---------------------------------------------------------------------------

    \92\ PHMSA notes that design, installation, and construction 
requirements in chapter 14 would--pursuant to the statutory 
retroactivity prohibitions at 49 U.S.C. 60103(c) and 60104(b)--not 
apply to existing mobile and temporary facilities as those 
facilities are relocated from place-to-place. However, PHMSA expects 
that the proposed spacing requirements at NFPA 59A-2026, Table 6.3.1 
would apply to these facilities each time they are relocated given 
that those facilities are (by definition) relocated throughout their 
lifecycles.
---------------------------------------------------------------------------

    Lastly, PHMSA proposes to make clear that the provisions of part 
193, subpart A apply to mobile and temporary LNG facilities in addition 
to the requirements in chapter 14 of NFPA 59A-2026. Consistent with 
current part 193 requirements, operators of mobile and temporary LNG 
facilities that meet the requirements of NFPA 59A-2026 would be exempt 
from the other requirements of part 193.
B.8. Section 193.15--Investigations of Failures
    PHMSA proposes to retain and to update the failure investigation 
requirements currently found at Sec.  193.2515. The proposed revisions 
include redesignating the current Sec.  193.2515 as a new Sec.  193.15 
and adding requirements to improve the quality of information on 
failures at LNG facilities. The current requirements in Sec.  193.2515 
are similar to the incident analysis and documentation requirement at 
section 18.2.2(7) of NFPA 59A-2026. However, the NFPA provision is 
limited to safety-related incidents and has no minimum property damage 
threshold. And though section 18.5 of NFPA 59A-2026 helpfully requires 
operators to establish incident investigation procedures, the language 
within that provision provides few specifics on the content that must 
be included in those procedures. PHMSA proposes the following revisions 
to address these concerns.
    First, in paragraph (a), PHMSA proposes to expand the scope of 
failure investigation requirements to include hazardous fluid releases. 
Section 193.2515(a) currently limits the failure investigation 
requirements to explosions, fires, LNG spills, or leaks. Adding 
hazardous fluid releases to the list will promote public safety and is 
consistent with the changes that PHMSA is proposing elsewhere to part 
193.
    Second, in paragraph (a), PHMSA proposes to expand the scope of the 
failure investigation requirements to include events that occur during 
commissioning or operation. This modification will ensure that 
investigations cover all phases of LNG facility development and 
operation and is consistent with the other changes that PHMSA is 
proposing elsewhere to part 193.
    Third, in paragraph (a)(2), PHMSA proposes to increase the property 
damage threshold for failure investigations from the current $10,000 to 
align with the incident reporting requirements in part 191. When PHMSA 
introduced the property damage threshold in the failure investigation 
requirements in 1980, the incident reporting criteria did not include 
any comparable limitation and set a $5,000 property damage threshold 
for serious leaks requiring prompt telephonic reporting.\93\ PHMSA 
subsequently amended the incident reporting requirements in part 191 to 
add a monetary property damage threshold, which is now adjusted on a 
periodic basis to account for inflation,\94\ but has never updated the 
property damage threshold at Sec.  193.2515. PHMSA proposes to address 
that omission by aligning the current language at Sec.  193.2515 with 
the property damage threshold for LNG facility incident reporting in 
part 191. This change would account both for historic and future 
inflation and address concerns expressed by some commenters in 
responding to the recent ANPRMs that expanding the failure 
investigation requirements to include hazard fluids releases could 
significantly increase their compliance burdens with little safety 
benefit.\95\
---------------------------------------------------------------------------

    \93\ See MTB, Liquefied Natural Gas Facilities; Federal Safety 
Standards, 45 FR 70390, 70393-94 (Oct. 23, 1980).
    \94\ See RSPA, Transportation of Natural and Other Gas by 
Pipeline; Annual Reports and Incident Reports, 49 FR 18956 (May 3, 
1984); PHMSA, Pipeline Safety: Gas Pipeline Regulatory Reform, 86 FR 
2210 (Jan. 11, 2021).
    \95\ See, e.g., Williams Cos., Comments on the ANPRM, Docket ID 
PHMSA-2019-0091-7612.
---------------------------------------------------------------------------

    In a new Sec.  193.15(c), PHMSA proposes that operators maintain 
investigation records for a minimum of five years. The proposed five-
year recordkeeping requirement is consistent with Sec.  193.2521, which 
currently requires operators to maintain records from each inspection, 
test, and investigation for a period of at least five years. NFPA 59A 
requires tests, surveys, and inspection records to be maintained for 
the life of the facility but does not address the retention of 
investigation records. This five-year duration also aligns with the 
record retention requirements for maintenance activity on components 
prescribed in section 18.13.1 of NFPA 59A-2026, and the five-year 
incident investigation report recordkeeping requirements in the 
Occupational Safety and Health Administration (OSHA) process safety 
management (PSM) regulations at 29 CFR 1910.119(m)(7).

C. Subpart B--LNG Facility Siting

    PHMSA's siting requirements for LNG facilities date to a rulemaking 
proceeding initiated in the 1970s and completed in 1980. As with the 
other regulations adopted in that proceeding, PHMSA incorporated 
multiple levels of conservatism into the siting requirements to address 
uncertainties and limitations in the data available at that time. 
Although PHMSA has updated certain aspects of those requirements over 
time, including by approving more modern versions of the models used to 
determine the amount of property that must be owned or controlled to 
site an LNG facility at a particular location, the underlying 
conservatism embodied in the 1980 regulations has remained largely 
unchanged. That degree of conservatism is no longer justified given the 
significant advancements in LNG safety that have occurred in the past 
two decades, many of which are reflected in the enhanced safety 
requirements throughout recent editions of NFPA 59A.
    As discussed in more detail below, PHMSA is proposing substantial 
revisions to its siting requirements to address these concerns. First, 
PHMSA proposes adopting an updated version of the traditional, 
prescriptive approach for siting LNG facilities. The prescriptive 
approach would be consistent with the provisions in NFPA 59A-2026 
chapter 5 and would serve as the default set of siting requirements. 
Second, PHMSA proposes adopting a more sophisticated quantitative risk 
assessment (QRA)-based approach for siting LNG facilities. The QRA-
based approach would be consistent with the provisions in NFPA 59A-2026 
chapter 19 and would only apply on an elective basis.
    PHMSA believes that adopting these changes would eliminate much of 
the unnecessary conservatism embodied in the current regulations, 
generating significant cost savings without compromising safety. 
Additional information about the development of

[[Page 69347]]

PHMSA's siting regulations, and the proposed prescriptive and QRA-based 
siting approaches, is provided in the following sections.
C.1. Role of Siting in PHMSA's Safety Framework
    By way of background, the siting requirements in subpart B date to 
a rulemaking proceeding initiated by one of PHMSA's predecessor 
agencies, the Materials Transportation Board (MTB), in the late 1970s. 
MTB undertook that effort to address concerns with the then-current 
version of the Federal safety standards for LNG facilities, which 
relied almost entirely on the provisions in a historical edition of 
NFPA.\96\ MTB subsequently divided that rulemaking effort into two 
different proceedings, one of which focused on establishing O&M 
requirements for LNG facilities,\97\ and the other of which focused on 
establishing design, construction, installation, testing, and siting 
requirements for LNG facilities.\98\
---------------------------------------------------------------------------

    \96\ See MTB, LNG Facilities; Federal Safety Standards, 42 FR 
20776, 20778 (advanced proposal Apr. 21, 1977).
    \97\ See generally MTB, Liquefied Natural Gas Facilities; 
Federal Safety Standards, 45 FR 70390, 70391 (Oct. 23, 1980) 
(describing safety value of each of the different operations and 
maintenance proposals for the new part 193).
    \98\ See MTB, LNG Facilities; Federal Safety Standards, 44 FR 
8142, 8151 (proposed Feb. 8, 1979) (discussing the mutually-
reinforcing and (at times) redundant layers of design, construction, 
and installation requirements).
---------------------------------------------------------------------------

    Of particular importance for this proceeding, MTB took a very 
conservative approach in both proceedings, issuing final rules in 1980 
that included layers of mutually reinforcing requirements, many of 
which incorporated cautious assumptions or relied on near-worst-case 
scenarios selected to provide robust protective safety margins.\99\ MTB 
recognized that this approach imposed significant costs on operators, 
but concluded that those costs were justified by the limited historical 
release data for LNG facilities and the potential consequences of an 
incident.
---------------------------------------------------------------------------

    \99\ See RSPA, LNG Facilities: Federal Safety Standards, 45 FR 
9220, 9221-92 (proposed Feb. 11, 1980) (evaluating operations and 
maintenance requirements); RSPA, Liquefied Natural Gas Facilities; 
New Federal Safety Standards, 45 FR 9184, 9186-87, 9195 (Feb. 11, 
1980) (evaluating construction, design, installation, testing, and 
siting requirements).
---------------------------------------------------------------------------

    The original part 193 siting regulations were a product of that 
philosophy. Highlighting the lack of meaningful safety standards in 
effect at the time, MTB focused on addressing the risks associated with 
two hazards: (1) thermal radiation, i.e., the amount of heat that would 
be produced if an LNG spill ignited and (2) vapor-gas dispersion, i.e., 
the dimensions of the vapor-gas cloud that would form as a result of an 
LNG spill, which could ignite or act as an asphyxiant.\100\ MTB 
proposed an inherently conservative approach employed in regulating 
other high-consequence industrial facilities to address these risks. 
MTB required owners or operators to exercise control over an 
``exclusion zone,'' i.e., a buffer area around an LNG facility that 
could not be accessed by the public.\101\
---------------------------------------------------------------------------

    \100\ MTB, LNG Facilities; Federal Safety Standards, 42 FR 20776 
(advanced proposal Apr. 21, 1977).
    \101\ Notably, exclusion area boundaries employed in the context 
of commercial nuclear power facilities pursuant to 10 CFR 100.11, 
which were often characterized as posing similarly high-consequence 
public safety risks to those posed by LNG facilities. See, e.g., 
Comptroller General, Report No. EMD78-28, Liquefied Energy Gases 
Safety, Vol. 1, at 21-5 (July 31, 1978).
---------------------------------------------------------------------------

    To provide broad safety margins, MTB required operators to use 
conservative assumptions (e.g., emissive heat flux, flame length, flame 
tilt angle, and radiant heat exposure levels; neglect of active 
mitigation measures; assumption of 100 percent fatality or harm within 
exclusion zones) in calculating the extent of the exclusion zone for 
thermal radiation. The calculation needed to be made either by using a 
simple, default mathematical model that would yield ``conservatively 
safe exclusion zone[s]'' or by using an alternative, MTB-approved model 
that incorporated ``additional and more valid information when it 
becomes available.'' \102\ MTB employed a similar approach in setting 
the boundaries of the exclusion zone for flammable vapor-gas 
dispersion, requiring the use of near-worst case assumptions (e.g., a 
uniform concentration of methane half its actual lower flammable limit 
(LFL); default worst-case wind and atmospheric stability and design 
spill parameters) in response to an ignition scenario that MTB admitted 
was far less likely than the localized fire risk addressed in its 
thermal radiation hazard analysis.\103\ This approach addressed 
probability of release characteristics and operating conditions by 
selecting assumptions MTB judged appropriately conservative in light of 
occurrence frequency and potential consequence magnitude.
---------------------------------------------------------------------------

    \102\ See MTB, LNG Facilities; Federal Safety Standards, 44 FR 
8142, 8149-50 (proposed Feb. 8, 1979); RSPA, Liquefied Natural Gas 
Facilities; New Federal Safety Standards, 45 FR 9184, 9191-94 (Feb. 
11, 1980); MTB, Liquefied Natural Gas Facilities; Reconsideration of 
Safety Standards for Siting, Design, and Construction, 45 FR 57402, 
57406-08 (Aug. 28, 1980).
    \103\ See MTB, LNG Facilities; Federal Safety Standards, 44 FR 
8142, 8150-51 (proposed Feb. 8, 1979); RSPA, Liquefied Natural Gas 
Facilities; New Federal Safety Standards, 45 FR 9184, 9195 (Feb. 11, 
1980); MTB, Liquefied Natural Gas Facilities; Reconsideration of 
Safety Standards for Siting, Design, and Construction, 45 FR 57401, 
57047 (Aug. 28, 1980).
---------------------------------------------------------------------------

    Although subject to minor adjustments over time, the underlying 
approach of layering conservativism upon conservatism is still embodied 
in the current siting regulations. Subsequent rulemakings have adopted 
newer, and more accurate, models for calculating exclusion zones--even 
as they rejected stakeholder calls to update some of the conservative 
parameters that had been employed in addressing historical 
uncertainties.\104\ PHMSA has continued to rely on legacy editions of 
NFPA 59A that incorporate additional layers of conservatism within the 
modeling of hazard distances (which subpart B regulations then 
translate into exclusion zones). Specifically, subpart B has since 2004 
referenced NFPA 59A-2001 chapter 2's prescriptive siting requirements, 
which employ many of the conservative assumptions for modeling thermal 
radiation (section 2.2.3.2) and flammable vapor-gas (sections 2.2.3.3 
and 2.2.3.4) hazards that PHMSA's predecessors had previously adopted 
in regulation.\105\ In other places where NFPA 59A-2001 departed from 
historical, conservative modeling assumptions, PHMSA and its 
predecessors either retained those assumptions in subpart B text or 
supplemented them in FAQs.\106\ These extra layers of conservatism 
affect the design and layout of LNG facilities, either by constraining 
the configuration or spacing of components and systems within a site or 
requiring the installation of additional onsite mitigation measures 
(e.g., vapor shields) to accommodate the exclusion zone requirements.
---------------------------------------------------------------------------

    \104\ See RSPA, Liquefied Natural Gas Regulations--Miscellaneous 
Amendments, 62 FR 8402 (Feb. 27, 1997) (adopting the LNGFIRE I 
computer model for thermal radiation hazards and the DEGADIS model 
for flammable vapor dispersion hazards); RPSA, Pipeline Safety: 
Incorporation of Standard NFPA 59A in the Liquefied Natural Gas 
Regulations, 65 FR 10950, 10952-53 (Mar. 1, 2000) (adopting LNGFIRE 
III for thermal radiation modeling while rejecting less demanding 
thermal radiation wind speed and flammable vapor cloud explosive 
limit assumptions).
    \105\ Sec. Sec.  193.2051, 2057(a), 2059(a).
    \106\ See, e.g., Sec.  193.2059(b)(1) (assuming a safety factor 
of 2--or a 2.5 percent concentration of methane--when calculating 
hazard distances for flammable vapor cloud dispersion). PHMSA 
initially issued its LNG FAQs March 2014, and has supplemented or 
revised them ten times since, most recently in September 2025. PHMSA 
notes that even as it is proposing to discard some of the historical 
assumptions in LNG FAQs, operators would retain discretion to use 
those conservative, proven assumptions going forward as appropriate 
for their facility.
---------------------------------------------------------------------------

    Finally, PHMSA and its predecessors have supplemented the subpart B 
exclusion zone framework with additional siting requirements. For

[[Page 69348]]

example, RSPA's incorporation by reference in 2004 of the siting 
requirements within chapter 2 of NFPA 59A-2001 introduced prescriptive 
requirements covering everything from soil and geotechnical site 
investigation (section 2.1.4) to process equipment spacing (section 
2.2.6). PHMSA has also read broad language at section 2.1.1(d) of NFPA 
59A-2001 to require operators to consider ``[o]ther [siting-related] 
factors,'' including releases of hazardous fluids other than LNG, in 
conducting their exclusion zone analyses.\107\ These changes, when 
combined with the inherent conservatism used in developing the 
exclusion zone requirements, have resulted in a siting regime for LNG 
facilities that no longer appropriately reflects the risks to public 
safety, particularly given the significant advancements in industry 
standards and practices that have occurred in the past four decades.
---------------------------------------------------------------------------

    \107\ LNG FAQs, H1-H3. The expansion of part 193 siting 
requirements over time has been accompanied by expansion of other 
part 193 elements enhancing defense-in-depth from the safety risks 
of releases.
---------------------------------------------------------------------------

C.2. Prescriptive Siting Requirements (NFPA 59A-2026, Chapter 5)
    This rulemaking proposes to modernize PHMSA's default, prescriptive 
siting requirements in subpart B. These requirements are currently 
governed by a patchwork of industry standards, part 193 regulatory 
provisions, and non-binding guidance--all of which magnify the inherent 
conservatism already provided through the other requirements (design, 
installation, testing, construction, operations, and maintenance) in 
part 193. Although the LNG industry has an excellent safety record as 
discussed in section II.A.3.c above, PHMSA does not agree that the 
conservative approach traditionally used in the siting requirements is 
necessary to maintain that level of safety. Rather, PHMSA believes that 
a more modern approach consistent with the enhanced safety provisions 
in NFPA 59A-2026 can be used to determine whether an LNG facility can 
be safely sited at a particular location.
    PHMSA therefore proposes to incorporate by reference into subpart B 
the prescriptive siting requirements in chapter 5 of NFPA 59A-2026. 
Those requirements would serve as the default siting provisions in lieu 
of the current reference to chapter 2 of NFPA 59A-2001. PHMSA also 
proposes to supplement the provisions in NFPA 59A-2026 chapter 5 with a 
handful of additional regulatory requirements in subpart B. Adopting 
these changes would align the siting requirements with the latest 
hazard modeling techniques and current standards and practices in the 
LNG industry. In addition, PHMSA proposes to codify or to eliminate 
current non-binding guidance on LNG facility siting to improve 
regulatory certainty and to reduce unnecessary compliance burdens. 
PHMSA expects the proposed changes to the default, prescriptive siting 
requirements in subpart B will reduce public safety risks, particularly 
when combined with the other safety-enhancing proposals discussed 
elsewhere in this NPRM.
a. Sections 193.101 and 193.103(a)--Improved Hazard Modeling Under NFPA 
59A-2026
    PHMSA proposes to incorporate by reference into new Sec. Sec.  
193.101 and 193.103 certain enhanced hazard assessment and modeling 
requirements from chapter 5 of NFPA-2026. Specifically, PHMSA proposes 
to incorporate sections 5.2.1, 5.2.2, and 5.3.2 of NFPA 59A-2026 into 
these regulations, subject to certain exceptions and supplemental 
provisions as discussed below. PHMSA proposes to incorporate by 
reference into other subparts of part 193 provisions in chapter 5 of 
NFPA 59A-2026 that are better understood as design, rather than siting, 
requirements. PHMSA's discussion of those proposals is included in 
section IV.D of this NPRM.
    The hazard modeling requirements in subpart B are currently based 
on the provisions in chapter 2 of NFPA 59A-2001 and certain additional 
regulatory requirements. NFPA 59A-2001 at section 2.1.1(d)--and, by 
extension, PHMSA's subpart B regulations at Sec.  193.2051--requires 
operators to evaluate all ``factors . . . that have a bearing on the 
safety of plant personnel and the surrounding public'' when siting a 
new LNG facility or making significant expansions or other alterations 
to an existing LNG facility. PHMSA guidance at LNG FAQ H1 characterizes 
that regulatory language as requiring evaluation of releases from 
systems containing any hazardous fluid.
    In addition, Sec.  193.2051 requires operators to consider the 
effects of failure of certain equipment (e.g., storage tank 
penetrations, piping ruptures) resulting in the release of LNG in 
conducting a siting analysis. The specific LNG releases that must be 
considered, otherwise known as ``design spills,'' generally reflect 
industry understanding of (in some cases) worst-case, plausible 
failures based on historical data. Sections 193.2057 and 193.2059 
require operators to use certain models to predict the extent of the 
thermal radiation and flammable vapor-gas dispersion that would result 
from such a failure. The models, authorized by regulation or approved 
by PHMSA after an evaluation, calculate ``hazard distances'' bounding a 
``hazard footprint'' at certain prescribed thresholds or ``endpoints.'' 
\108\ NFPA 59A-2001 (at sections 2.2.3.2 and 2.2.3.3) assigns 
escalating safety requirements based on the magnitude of safety 
consequence associated with different endpoints. Operators must 
establish (or otherwise maintain) legal control of all activities 
within hazard footprints bounded by endpoints correlating to the most 
consequential risks: fatality and irreversible harm. The exclusion zone 
requirements in subpart B incorporate these concepts from NFPA 59A-
2001.
---------------------------------------------------------------------------

    \108\ <a href="https://www.phmsa.dot.gov/pipeline/liquified-natural-gas/lng-exclusion-zones">https://www.phmsa.dot.gov/pipeline/liquified-natural-gas/lng-exclusion-zones</a>. PHMSA has developed model evaluation protocols 
(MEPs) for source term calculation, flammable vapor cloud dispersion 
hazards, toxic vapor cloud dispersion hazards, vapor cloud explosion 
hazards, and boiling liquid expanding vapor cloud explosion hazards. 
PHMSA expects to issue an MEP for thermal radiation hazards in 
spring 2026.
---------------------------------------------------------------------------

    The hazard modeling requirements in chapter 5 of NFPA 59A-2026 are 
more advanced than the comparable provisions in NFPA 59A-2001, improve 
subpart B's hazard analyses with the risk profiles of modern facilities 
(many of which can contain large quantities of hazardous fluids other 
than LNG), and provide a more robust evaluation of hazard phenomena. 
For example, rather than providing that operators merely ``consider'' 
unspecified siting-related factors potentially affecting safety as 
provided by NFPA 59A-2001, NFPA 59A-2026 section 5.2.1 specifies 
illustrative factors (process hazards, security threats, adjacent 
facility hazards, weather and geological conditions, and safety 
measures incorporated in facility design and operational practices) for 
operators to consider in conducting site evaluations. In addition, 
section 5.3.2.13 of NFPA 59A-2026 provides more detailed requirements 
for qualitative consideration of the potential for cascading damage 
than the analogous provisions in section 2.2.3.6 of NFPA 59A-2001.\109\
---------------------------------------------------------------------------

    \109\ Although PHMSA has approved an MEP and MVD for boiling 
liquid expanding vapor explosion (BLEVE) hazards, PHMSA understands 
that neither NFPA 59A-2026 chapter 5, nor Sec.  193.103 as proposed 
in this NPRM, necessarily require operators to model such hazards. 
Nor would each operator need to address the BLEVE hazards 
qualitatively in its siting evaluation pursuant to Sec.  193.103 
unless the characteristics of its facility suggest that the 
probability of a BLEVE hazard merits discussion among other 
cascading damage scenarios as required by NFPA 59A-2026 section 
5.3.2.13. PHMSA understands that the probability of BLEVEs at LNG 
facilities is typically low and would in any event be exemplary of 
cascading damage rather than an independent hazard; as such, the 
probability (and consequence magnitude) associated with BLEVEs would 
also be mitigated by the suite of part 193 defense-in-depth 
requirements. PHMSA also understands the more specific language in 
those NFPA 59A-2026 provisions must be understood against a rule of 
reason: operators' written siting evaluations could briefly and 
qualitatively reference information on the factors identified within 
other documentation supporting regulatory compliance or approvals 
for their facilities without having to include an exhaustive 
(quantitative or qualitative) evaluation of those or other factors 
within a siting analysis.

---------------------------------------------------------------------------

[[Page 69349]]

    Chapter 5 of NFPA 59A-2026 expands the requirements for hazard 
modeling as well. Rather than requiring that operators ``consider'' 
most releases of LNG and other hazardous fluids, section 5.3.2.1 of 
NFPA 59A-2026 explicitly requires modeling of additional hazards 
(including overpressure effects from vapor cloud explosions (VCEs), 
toxic effects from toxic vapor dispersion, and thermal radiation 
effects from fireballs) from releases of hazardous fluids generally. 
Chapter 5 also provides that such modeling should be informed by 
specific endpoints correlating to fatality and irreversible harm for 
each of these new hazard modeling requirements.\110\
---------------------------------------------------------------------------

    \110\ PHMSA solicits stakeholder comment on whether existing 
hazard modeling focused on thermal radiation and flammable vapor 
cloud dispersion provides adequate protection of public safety such 
that its proposed expansion of modeling to account for new hazards 
as contemplated by NFPA 59A-2026 would be unnecessary. PHMSA also 
solicits comment on the appropriateness of the NFPA 59A-2026 
endpoints for each of the hazards for which that standard requires 
modeling. Finally, PHMSA solicits stakeholder comment on whether and 
to what extent any new hazard modeling requirement should be limited 
based on the quantity or type of hazardous fluids other than LNG 
present at a particular facility.
---------------------------------------------------------------------------

b. Enhancements on NFPA 59A-2026 Hazard Modeling Requirements
    PHMSA proposes a series of additional enhancements to the expanded 
hazard modeling requirements of chapter 5 of NFPA 59A-2026 through 
targeted subpart B provisions that are intended to address safety risks 
and lessons learned from recent LNG facility incidents, to ensure 
continuity with longstanding PHMSA guidance, and to facilitate 
implementation by operators.
Section 193.103(a)--Siting Package Submission
    Consistent with the documentation requirements at NFPA 59A-2026 
section 5.2.2, PHMSA proposes to codify LNG FAQ G7, which directs 
operators to submit a Design Spill Package to PHMSA with engineering 
drawings, piping and instrument drawings, reports from hazard analyses 
(including an exclusion zone), and similar items that will inform its 
review of siting analyses. In codifying this requirement, PHMSA 
proposes a comprehensive list of information needed in ensuring 
compliance with subpart B to provide additional regulatory certainty. 
PHMSA expects that, when submitting the information specified in Sec.  
193.103(a), operators will provide it in the form and manner consistent 
with LNG FAQ DS3.
    PHMSA has clarified in its proposed regulatory text codifying the 
LNG FAQ DS3 submission requirement that operators must submit a written 
assessment of the effect of active and passive mitigation measures on 
their hazard analysis. PHMSA acknowledges that operators and hazard 
modeling practitioners are generally in the best position to identify 
precisely how a particular mitigation measure will affect the risk 
profile of an LNG facility. PHMSA will exercise continuing regulatory 
oversight in reviewing operator submissions.
Section 193.103(b)--Design Spill Criteria
    PHMSA proposes to codify in Sec.  193.103(b) the design spill 
criteria in LNG FAQ DS2 in lieu of the analogous criteria in Table 
5.3.2.3 of NFPA 59A-2026. PHMSA's experience is that the undefined term 
``single accidental leakage source'' (SALS) at Table 2.2.3.5 of NFPA 
59A-2001 (for spills from process and transfer systems) has been a 
source of confusion. PHMSA, FERC, and NFPA have developed a series of 
clarifications characterizing (in some cases) worst-case, plausible 
spills from different types of transfer and process systems, including 
the design spill criteria in current LNG FAQs DS2(A) (hole size on 
process & transfer systems), DS2(B) (full-bore ruptures of single-ply 
construction expansion bellows), DS2(C) (hole size for pipe-in-pipe 
systems), and DS2(D) (hole size for truck transfer hoses). Each of 
these assumptions has been employed in subpart B siting analyses for 
multiple LNG facilities in the last decade.
    First, LNG FAQ DS2(A) provides that a design spill should assume 
full-bore (or guillotine break) ruptures on transfer and process piping 
with a diameter less than six inches (i.e., assuming a hole equal to 
the diameter of the pipe), while operators need only assume a two-inch 
hole on piping of six inches in diameter and larger. This line-drawing 
is based on identifying the largest plausible failures on such piping, 
since historical failure data demonstrates that full-bore ruptures are 
plausible failure modes on smaller piping, but not on large piping--
failures of two inches or smaller hole size represent most of all 
failure data on piping of six inches or larger. PHMSA acknowledges that 
NFPA 59A-2026 (at section 5.3.2.3, referencing Table 5.3.2.3) employs 
different assumptions requiring full-bore ruptures only for piping 
smaller than three inches in diameter. Having objected to that 
provision during the standards development process as inconsistent with 
the results of PHMSA research,\111\ PHMSA proposes to adopt the 
criteria in LNG FAQ DS2(A) instead of the provisions in Table 5.2.3.2 
of NFPA 59A-2026.
---------------------------------------------------------------------------

    \111\ Gas Tech. Inst. (GTI), Contract No. DTPH56-15-T-00008, 
Statistical Review and Gap Analysis of LNG Failure Rate Table (Jan. 
2017).
---------------------------------------------------------------------------

    Second, NFPA 59A-2001 does not include provisions for cryogenic PIP 
technology, and more recent editions of NFPA 59A exempt PIP transfer 
systems from the design spill requirements in favor of using (in Table 
6.3.1) setback distances. PHMSA recommends in its LNG FAQ DS2(C) that 
operators evaluate design spills from a one-inch hole on all PIP 
transfer systems, regardless of diameter. That design spill parameter 
reflects PHMSA's understanding that, while unlikely, releases from PIP 
transfer systems are nevertheless possible--as evinced by the failure 
of such a system in the 2022 Freeport incident. PHMSA therefore 
proposes to codify its one-inch hole design spill requirement for PIP 
transfer systems within the new Sec.  193.103(b).\112\
---------------------------------------------------------------------------

    \112\ PHMSA is not proposing codification of other prescriptive 
criteria in LNG FAQs DS2(C)(1)-(3) addressed in provisions of NFPA 
59A-2026 setting forth design requirements for pipe-in-pipe systems.
---------------------------------------------------------------------------

    Third, for single-ply construction expansion bellows and truck 
transfer hoses, PHMSA proposes to codify at the new Sec.  193.103(b) 
current guidance in LNG FAQ DS2(B) and (C). That guidance requires 
modeling of a hole size equivalent to a full-bore rupture for all 
single-ply construction expansion bellows and truck transfer hoses, 
regardless of diameter. PHMSA understands these conservative 
assumptions are warranted as single-ply construction expansion bellows 
and truck transfer hoses are less robust components with a higher 
likelihood of full-bore ruptures than fixed piping of equivalent size. 
Moreover, a fatal incident in September 2023 in Toppenish, Washington, 
in which a full-bore rupture occurred after a transfer hose detached as 
a truck pulled away from an LNG facility during transfer operations, 
demonstrates the

[[Page 69350]]

importance of adopting this modeling requirement.\113\
---------------------------------------------------------------------------

    \113\ Wash. Utils. & Transp. Comm'n v. Cascade Nat. Gas Co., 
Docket No. PG-230800, Compl., at ] 16 (Mar. 27, 2025).
---------------------------------------------------------------------------

Section 193.103(c)--Models for Calculating Source Terms and Hazard 
Footprints Reviewed Against PHMSA Reference Materials
    PHMSA proposes to consolidate and to enhance within a new Sec.  
193.103(c) current guidance at LNG FAQs H6 and H7 for the modeling of 
release source terms (the characterization of immediate-post release 
parameters) and hazard footprints. Specifically, PHMSA proposes to 
require that operators perform source term calculation and hazard 
modeling pursuant to computer programs reviewed against PHMSA-approved 
MEPs and data sets (MVDs). PHMSA understands that evaluation of those 
computer models by a software developer or a facility operator (rather 
than PHMSA) against PHMSA-approved MEPs and MVDs will satisfy the 
comparable provisions in NFPA 59A-2026 at sections 5.3.2.6 and 5.3.2.7.
    Subpart B initially required the use of certain specific models for 
calculating endpoints (and, by extension, hazard footprints) for 
thermal radiation and flammable vapor-gas hazards from LNG 
releases.\114\ RSPA subsequently revised subpart B to allow approval of 
alternative hazard models,\115\ and sections 193.2057(a) and 
193.2059(a) provide criteria that inform such reviews. Subpart B does 
not prescribe an analogous process for reviewing and approving source 
term models.
---------------------------------------------------------------------------

    \114\ MTB, Liquefied Natural Gas Facilities: New Federal Safety 
Standards, 45 FR 9184 (Feb. 11, 1980) (codifying Sec. Sec.  
193.2057(c) (thermal exclusion zones) and 193.2059(c) (flammable 
vapor-gas exclusion zones)).
    \115\ See RSPA, Incorporation of NFPA 59A in the Liquefied 
Natural Gas Regulations, 65 FR 10950 (Mar. 1, 2000).
---------------------------------------------------------------------------

    To address that gap, PHMSA has provided guidance in the form of an 
Advisory Bulletin (ADB-10-07) and LNG FAQs (initially H5-H6) for model 
developers to use in seeking PHMSA approval of flammable vapor cloud 
dispersion models evaluated against MEPs and experimental data.\116\ 
PHMSA declined in LNG FAQ H7 to prescribe particular software for 
calculating source terms for flammable vapor-gas dispersion hazards. 
PHMSA has continued to work with subject matter experts to develop MEPs 
and MVDs appropriate for use in reviewing and approving computer models 
for calculating source terms and hazard footprints with respect to each 
of the hazards identified in NFPA 59A-2026 section 5.3.2.1. PHMSA's 
website provides links to those MEPs and the MVD data sets against 
which the MEPs require models be validated.\117\ PHMSA's website also 
lists the handful of alternative models approved for use in modeling 
flammable vapor-gas dispersion hazards--each of which were approved 
only after protracted delay.\118\ To date, no one has sought PHMSA 
approval for software for calculating source terms or for use in 
modeling other hazards identified in section 5.3.2.1 of NFPA 59A-2026.
---------------------------------------------------------------------------

    \116\ See PHMSA, ADB-10-07, Obtaining Approval for Alternative 
Vapor-Gas Dispersion Models, 75 FR 33771 (Aug. 31, 2010); LNG FAQs, 
H5-H6 (Dec. 7, 2015). ADB-10-07 was itself the result of extensive 
work effort by PHMSA and subject matter experts within the Federal 
Government and industry on developing robust MEPs and MVDs.
    \117\ <a href="https://www.phmsa.dot.gov/pipeline/liquified-natural-gas/lng-exclusion-zones">https://www.phmsa.dot.gov/pipeline/liquified-natural-gas/lng-exclusion-zones</a>.
    \118\ PHMSA review of each of the three alternative models 
listed on its web page lasted a year or longer--with one (Phast 8.4) 
review lasting nearly three years.
---------------------------------------------------------------------------

    PHMSA proposes to establish a developer-and-operator-led review and 
approval process at Sec.  193.103(c). Software developers will need to 
review source term and hazard modeling software against the PHMSA-
approved MEPs and MVDs; however, such software will no longer require 
explicit PHMSA approval before use.\119\ This approach will ensure the 
more efficient use of PHMSA's limited resources. PHMSA notes this 
concern about diversion of resources is particularly acute given this 
NPRM's proposed expansion of modeling requirements to hazards that had 
formerly only been addressed qualitatively.
---------------------------------------------------------------------------

    \119\ In the interests of regulatory certainty, PHMSA does not 
propose that Sec.  193.103(c) would be construed either (1) to 
require operators to re-validate their computer models should the 
MEP or MVD for a particular hazard be updated during regulatory 
review (either in preliminary or final design phases) or subsequent 
construction and pre-operational phases of a project; or (2) to 
prohibit operators from validating their computer models against 
older versions of PHMSA-approved MEPs or MVDs unless PHMSA 
explicitly prohibits the use of older versions of the MEPs or MVDs 
when approving updated versions of the same. Should the continued 
use of a historical MEP or MVD entail unacceptable safety risk, 
PHMSA (or another cognizant regulatory authority) may exercise its 
statutory authority to restrict the use of that particular MEP or 
MVD either generically or in connection with a specific LNG facility 
project.
---------------------------------------------------------------------------

    PHMSA also expects that its proposed approach will encourage 
industry investment in more sophisticated source term and hazard models 
by eliminating the delays associated with the PHMSA review and approval 
process, which have served as a barrier to innovation and investment. 
PHMSA does not expect this approach to have an adverse effect on public 
safety. Each source term and hazard model would still need to be 
evaluated by operators against robust, PHMSA-approved, hazard-specific 
MEPs and comprehensive MVDs, and PHMSA--as well as other (Federal or 
State) regulators--will continue to have the ability to take 
appropriate action through the enforcement and oversight process to 
address any safety concerns.
    Lastly, PHMSA acknowledges that pertinent language in NFPA 59A-2026 
(at sections 5.3.2.6 and 5.3.2.7) and within the MEPs and MVDs reflect 
the existing Sec.  190.9 approval process. Should this proposal be 
adopted, PHMSA will interpret those provisions of NFPA 59A-2026 and its 
MEPs and MVDs as if they memorialized this updated approach. In 
parallel, PHMSA will work with other stakeholders to ensure that each 
of NFPA 59A and its MEPs and MVDs are updated to conform with revised 
regulatory text.
Section 193.103(d)--Cloud Height for Vapor Dispersion Modeling
    PHMSA proposes to retain, but to redesignate as a new Sec.  
193.103(d), language at existing Sec.  193.2059(b)(3) requiring that 
operators use an elevation parameter of 0.5 meters when modeling vapor 
dispersion hazard footprints. This requirement ensures that vapor 
dispersion modeling focuses on impacts at ground level where members of 
the public will be located. NFPA 59A-2026 chapter 5 does not address 
this modeling consideration. Accordingly, PHMSA proposes to maintain 
the existing requirement.
Section 193.103(e)--Modeling Duration for Vapor Dispersion
    PHMSA proposes to adopt within a new Sec.  193.103(e) the duration 
assumptions for modeling flammable vapor cloud dispersion hazards in 
LNG FAQ DS8(B). Pursuant to section 5.3.2.4 of NFPA 59A-2026, design 
spill duration can be capped at 10 minutes--and potentially less when 
an LNG facility is equipped with automatic shutdown systems--consistent 
with an expectation that vapor clouds will typically reach a maximum 
extent well before 10 minutes following initiation of a spill. But 
vapor clouds may continue expanding after the 10-minute spill duration 
ends in certain scenarios (e.g., spills from long and large-bore piping 
with widely spaced isolation valves, or from process and storage 
vessels). Therefore, PHMSA proposes to qualify incorporation by 
reference of NFPA 59A-2026 section 5.3.2.4 to require operators 
continue flammable and toxic vapor dispersion simulation modeling until 
the vapor cloud reaches its maximum extent--even if that is longer than 
the design spill duration.

[[Page 69351]]

Notwithstanding this regulatory language, PHMSA expects operators may 
continue to use a 10-minute modeling cut-off time as a placeholder 
during the preliminary design phase, since the final modeling will 
depend on factors that are determined later in the design process.
Section 193.103(f)--Uncertainty Factors for Hazard Modeling
    Subpart B regulations do not prescribe a safety factor for use in 
modeling thermal radiation hazards. In contrast, subpart B regulations 
at Sec.  193.2059(b)(1) require that operators incorporate a safety 
factor in calculating flammable vapor-gas dispersion footprints: 
operator modeling of flammable vapor-gas hazards must be based not on 
the LFL of methane (5.0 percent concentration in air), but half of that 
value--2.5 percent methane concentration in air (or a safety factor of 
``2''). The LFL safety factor of 2 was consistent with then-current 
edition of NFPA 59A when adopted in 1980 and addressed historical 
concerns with the limitations of contemporaneous modeling 
approaches.\120\ But subsequent NFPA 59A editions no longer incorporate 
a specific, universally-applicable safety factor,\121\ and the PHMSA-
approved MEPs contain a methodology for calculating model-specific 
uncertainty factors based on evaluation of a model results against 
experimental data within PHMSA-approved MVDs--an approach consistent 
with NFPA 59A-2026 section 5.3.2.12.
---------------------------------------------------------------------------

    \120\ See MTB, Liquefied Natural Gas Facilities: New Federal 
Safety Standards, 45 FR 9184, 9185 (Feb. 11, 1980).
    \121\ See, e.g., RSPA, Incorporation of NFPA 59A in the 
Liquefied Natural Gas Regulations, 65 FR 10950, 10953 (Mar. 1, 
2000).
---------------------------------------------------------------------------

    PHMSA proposes to adopt at a new Sec.  193.103(f) a requirement to 
use uncertainty factors derived from application of PHMSA-approved MEPs 
and MVDs. That approach is consistent with the comparable provisions in 
NFPA 59A-2026. PHMSA expects that the robust, hazard-specific 
evaluation processes and data sets for calculation of uncertainty 
factors will ensure adequate conservatism in the calculation of hazard 
endpoints. PHMSA also expects that software developers will have a 
commercial incentive to improve the accuracy of their computer models 
to capture increasingly lower uncertainty factors after evaluation 
against PHMSA-approved MEPs and MVDs.
Section 193.103(g)--Consideration of Active Mitigation Measures in 
Hazard Modeling
    PHMSA proposes a new Sec.  193.103(g) adopting the approach in 
section 5.3.2.2.1 of NFPA 59A-2026 for adjusting calculated hazard 
endpoints to reflect the installation of active mitigation measures. 
PHMSA has historically allowed operators to adjust modeled hazard 
endpoints to reflect certain passive design features (e.g., vapor 
fences). But PHMSA has been reluctant to allow an adjustment for active 
mitigation measures, an issue not addressed in NFPA 59A-2001.\122\ 
Subsequent editions of NFPA 59A (including NFPA 59A-2026) permit 
operators to take credit for active mitigation measures in calculating 
hazard footprints.
---------------------------------------------------------------------------

    \122\ See LNG FAQ, H8. PHMSA acknowledges that some ``active'' 
mitigation measures may involve both procedural elements requiring 
human intervention as well as design (passive) elements.
---------------------------------------------------------------------------

    PHMSA therefore proposes within a new Sec.  193.103(g) a process 
for considering active mitigation measures in calculating hazard 
footprints. This updated approach should align calculated hazard 
footprints more appropriately with genuine risks and incentivize 
operators to deploy novel, robust mitigation measures enhancing 
safety--a particularly valuable result given that PHMSA is elsewhere 
proposing to expand its hazard modeling requirements to address new 
hazards (e.g., toxic vapor dispersion) that may warrant different 
mitigation strategies.
    PHMSA has drafted Sec.  193.103(g) to ensure that consideration of 
active mitigation measures in hazard modeling will be based on a sound, 
proven basis consistent with evolution of industry best practices and 
lessons learned. Specifically, the proposal would require each active 
mitigation measure to be incorporated into the documentation submitted 
to PHMSA in the Sec.  193.103(a) siting package. Adequate supporting 
documentation could consist of test or experimental results, reference 
to the use of the same or a similar active mitigation measure at 
another LNG facility, or a special permit issued either for that or 
another facility.\123\ Although this may place a burden on first 
adopters of active mitigation measures, PHMSA expects that burden to be 
reduced for subsequent users of the same measures, because PHMSA will 
have already considered whether and how an active mitigation measure 
should be accounted for in hazard modeling. Adequate supporting 
documentation could also reference any active mitigation measures 
accounted for in calculating exclusion zones for approved LNG 
facilities pursuant to the alternative QRA-based approach in proposed 
Sec.  193.107. PHMSA expects that this requirement will ensure that use 
of active mitigation techniques within Sec.  193.103 hazard modeling 
will be supported by robust quantification of the safety value of such 
measures that have been endorsed by a cognizant regulatory authority.
---------------------------------------------------------------------------

    \123\ PHMSA will also consider stakeholder input on whether it 
should accept active mitigation measures for releases of certain 
(specifically, toxic chemicals appearing in an LNG facility) 
hazardous fluids incorporated into offsite consequence analyses 
supporting EPA-approved risk management plans pursuant to 49 CFR 
part 68.
---------------------------------------------------------------------------

    Lastly, PHMSA will (as discussed above) defer to an operator's 
assessment of precisely how an active mitigation measure would affect 
the performance (or output) of its hazard modeling, provided such 
assessment is documented in the siting package as contemplated by Sec.  
193.103(a). Operators--and not PHMSA--are generally best-positioned to 
evaluate the facility-specific factors (including, but not limited to, 
the characteristics of the hazard and the technical/operational 
practicability and cost of mitigation measures) demonstrating the value 
of particular mitigation measures.
c. Rescission of LNG FAQs and Miscellaneous Clarifications of NFPA 59A-
2026 Hazard Modeling Boundaries
    PHMSA proposes to rescind its LNG FAQs if the proposals in this 
NPRM are adopted in a final rule. Some of those LNG FAQs (in 
particular, those discussed above) will be redundant with, or 
superseded by, changes in the hazard modeling methods provided for in 
the revised subpart B. Other LNG FAQs prescribe a one-size-fits-all 
(and, in some cases, worst-case) approach on the choice of hazard 
evaluation parameters that may not resemble plausible release scenarios 
for particular facilities or hazards.\124\ In lieu of following those 
parameters, operators should adhere to provisions in NFPA 59A-2026; for 
other parameters on which NFPA 59A-2026 is silent or explicitly allows 
flexibility, operators should use sound engineering judgment in 
selecting plausible, conservative parameters and document their 
reasoning as required by proposed

[[Page 69352]]

Sec.  193.103(a) and NFPA 59A-2026 section 5.2.2.
---------------------------------------------------------------------------

    \124\ Among those LNG FAQs are those demanding the use of high-
consequence assumptions regarding hole size (DS4), release height 
and location (DS5), release location (DS6), process conditions 
(DS7), system inventory (DS8), and pump configuration and operation 
(DS10-11).
---------------------------------------------------------------------------

    PHMSA discusses below two issues regarding the scope of subpart B 
hazard modeling analyses that merit additional clarification.
Exemption of Feed Gas and Send-Out Gas Lines From Subpart B Hazard 
Modeling
    LNG facilities are typically connected to pipelines that either 
supply gas for liquefaction (called ``feed gas'' lines) or receive gas 
after regasification (called ``send out'' lines). These pipelines are 
collectively referred to as ``supply lines'' and have historically been 
considered subject to PHMSA's part 192 requirements rather than its 
part 193 regulations (and by extension, NFPA 59A). Although neither 
NFPA 59A-2001 nor current subpart B regulations address the boundary 
between these regulatory regimes, PHMSA's practice has been to give 
operators discretion in designating the precise boundary--the ``spec 
break''--where each of the part 192 and 193 regulatory regimes would 
begin to apply. Operators in practice have typically chosen the first 
aboveground segment of a supply line within the LNG facility boundary 
as the ``spec break'' marking the boundary of part 193 regulations. 
This approach is consistent with the practical realities that most 
modeled hazards are pertinent to aboveground (rather than buried) 
piping and that operators are unlikely to have legal control of areas 
outside the property lines of their facilities as may be required if 
they were to draw exclusion zones as supply piping crossed into their 
facility.
    Consistent with that historical practice, NFPA 59A-2026 at section 
5.3.2.1 (as well as section 1.1.2(6)) now explicitly excludes ``feed 
gas and send out gas lines'' from hazard modeling requirements--but 
remains silent regarding the meaning of those terms. PHMSA proposes to 
continue its current policy of deferring to operators in determining 
the precise boundary between part 193-regulated piping (which would be 
subject to subpart B hazard modeling requirements) and part 192-
regulated as supply lines (which would not be subject to subpart B 
hazard modeling requirements). This approach ensures continuity with 
PHMSA's historical approach, which has proven effective in ensuring 
public safety. Because PHMSA is merely affirming its longstanding 
approach on this issue, PHMSA does not propose regulatory text 
memorializing that understanding.
d. Sections 193.5 and 193.105--Retention of Exclusion Zone Framework 
and Extension to Newly Modeled Hazards
    PHMSA proposes in redesignated and revised Sec. Sec.  193.5 and 
193.105 to apply the subpart B ``exclusion zone'' framework to 
additional hazards. Consistent with the current definition of 
``exclusion zone'' at Sec.  193.2007, an operator or a governmental 
authority would be required by the redesignated Sec.  193.5 to have 
legal control for the life of an LNG facility over activities within 
certain modeled hazards' footprints--not merely at initial siting as 
contemplated by the letter of NFPA 59A-2026. PHMSA also proposes to 
codify at Sec.  193.105(b) longstanding and common-sense guidance 
providing certain exceptions to the Sec.  193.5 requirement that an 
operator or a governmental authority maintain legal control over all 
activities within certain hazard footprints. Specifically, LNG FAQ H5 
recognizes exceptions to the default legal control requirement--for 
exclusion zones that would otherwise extend past a property line onto a 
public road or a navigable waterway--as a concession to the practical 
reality that legal control may not be possible in some cases and may 
not meaningfully contribute to safety given that those areas are not 
typically locations of prolonged activity by individuals.
    In addition, PHMSA proposes a new Sec.  193.105 that would 
reference NFPA 59A-2026 provisions providing for exclusion zones based 
on the modeled thermal radiation and flammable vapor dispersion hazard 
footprints, similar to current regulations at Sec. Sec.  193.2057 and 
193.2059. PHMSA also proposes that Sec.  193.105 would extend PHMSA's 
traditional exclusion zone framework to the newly modeled hazards 
discussed above. This proposed expansion will ensure LNG facilities are 
sited in a manner minimizing risk to nearby commercial, residential, or 
sensitive establishments.
    PHMSA proposes in Sec.  193.105(a) to limit extension of its 
exclusion zone approach to some hazard endpoints that are newly modeled 
and that correlate to the most compelling risks of fatality or 
irreversible harm. Other, less consequential hazard endpoints will be 
subject to the occupancy and other restrictions set forth in tables 
(Tables 5.2.9, 5.2.10, and 5.2.11) in NFPA 59A-2026. For toxic vapor 
dispersion, exclusion zones and occupancy restrictions will (consistent 
with the approach taken in the quantitative risk assessment siting 
framework at NFPA 59A-2026 Table 19.8.4.1.1) be based on exposure times 
of one hour or less for each of AEGL-2 and AEGL-3. Longer exposure 
times for AEGL-2 and AEGL-3, as well as all AEGL-1 exposure times, 
would require development of public notification procedures in 
consultation with applicable State and local emergency response 
organizations that are consistent with LNG facility emergency response 
plans.
    Extension of the exclusion zone approach to lower consequence (or, 
for AEGL-2 and AEGL-3, duration-determined) endpoints as contemplated 
by NFPA 59A-2026 could provide additional safety margin; however, PHMSA 
expects any incremental benefits would not outweigh the potentially 
significant additional compliance costs for several reasons. First, the 
particular public safety risks at issue are either less severe or more 
contingent (e.g., for AEGL-2 and AEGL-3, time intervals allowing for 
public notification and evacuation/sheltering) than the acute fatality 
and irreversible harm risks associated with endpoints to which PHMSA 
proposes extension of its exclusion zone framework. Second, the 
incremental safety benefit from broader application of exclusion zones 
would likely be mitigated by the universe of other elements (e.g., 
exclusion zones for other hazards; design, construction, O&M 
requirements) providing defense-in-depth from public safety risks. 
Third, should the characteristics of any particular LNG facility 
warrant broader exclusion zones, other regulatory authorities (e.g., 
FERC within certificate conditions) may apply such requirements on an 
as-needed basis.
    PHMSA has not compared the differences between the size of the 
exclusion zones that would be produced under the current regulations at 
Sec. Sec.  193.2057 and 193.2059 and changes proposed in the NPRM. 
PHMSA expects that some of the changes (e.g., codification of 
conservative FAQ design spill assumptions) may increase the size of 
exclusion zones for currently modeled hazards, while others (e.g., 
consideration of active mitigation measures) may reduce them. The 
cumulative effect of any such changes will turn on the unique 
characteristics of each LNG facility and the results of computer models 
for source term and hazard footprint calculation that PHMSA has not yet 
reviewed.
    PHMSA also understands that a before-and-after comparison would 
provide a poor measure of the safety impact of the proposed amendments; 
as discussed above, exclusion zones are a single, conservative element 
within a multi-layer defense-in-depth strategy for addressing public 
safety risks. PHMSA

[[Page 69353]]

subject matter experts expect that largest exclusion zones calculated 
pursuant to the default, prescriptive subpart B approach proposed in 
Sec. Sec.  193.103 and 193.105 could be comparable in size to those 
calculated under current regulations. Moreover, PHMSA's proposed 
changes to hazard modeling and exclusion zones would provide a more 
accurate evaluation of public safety risks than current regulations, as 
PHMSA's proposals would require operators to model and to develop 
exclusion zones for additional hazards using more realistic 
assumptions.
C.3. Risk-Based Siting Alternative Using Quantitative Risk Analysis 
(NFPA 59A-2026, Chapter 19)
    PHMSA proposes to retain a set of default, prescriptive siting 
requirements for all PHMSA-regulated LNG facilities at Sec.  193.103. 
For operators willing to invest more resources, PHMSA also proposes at 
Sec.  193.107 to adopt an alternative, QRA-based siting approach 
consistent with the provisions in NFPA 59A-2026 chapter 19.
    As explained in more detail below, the QRA-based approach leverages 
decades of industry experience to provide a modern, comprehensive 
siting framework for LNG facilities. It also complements PHMSA's 
extensive experience administering risk-based regulatory frameworks for 
other pipeline facilities, including through gas transmission integrity 
management (part 192, subpart O), gas distribution integrity management 
(part 192, subpart P), and hazardous liquid pipeline integrity 
management (Sec.  195.452) programs. As discussed further in section 
IV.G, those risk-based regulatory regimes have resulted in improved 
safety outcomes since their adoption. And chapter 19 itself is the 
product of 15 years of effort to establish and refine a QRA-based 
alternative to historical, prescriptive siting requirements elsewhere 
within NFPA 59A, with the first attempt at a QRA-based siting 
alternative included within an optional Annex E to the 2009 edition of 
NFPA 59A.
    The table below summarizes anticipated benefits of PHMSA's proposed 
QRA-based siting approach compared to the default, prescriptive siting 
requirements at Sec.  193.103:

------------------------------------------------------------------------
                                            Sec.   193.107--QRA-based
 Sec.   193.103--Default, prescriptive   siting approach (NFPA 59A-2026,
 siting approach (NFPA 59A-2026, ch. 5)              ch. 19)
------------------------------------------------------------------------
Primarily qualitative consideration of   Explicit quantification of
 probability employing conservative,      probabilities (e.g., component
 simplified assumptions (e.g.,            failure, release parameters)
 homogenous risk with a hazard            when evaluating siting risks.
 footprint) when evaluating siting
 risks.
Rigid exclusion zones that constrain     Enhanced flexibility to adjust
 spacing of key equipment and systems     dimensions of exclusion zones
 within the facility--thereby limiting    by adopting active and passive
 expanded capacity.                       mitigation measures--thereby
                                          facilitating expanded
                                          capacity.
Obscures policy judgments regarding      Identifies consensus,
 acceptable levels of siting risks and    quantified values for
 trade-offs between mitiga

[…truncated; see source link]
Indexed from Federal Register on November 3, 2026.