Energy Conservation Program: Decision and Order Granting a Waiver to Norlake, Inc., dba Refrigerated Solutions Group, From the Department of Energy Walk-In Coolers and Walk-In Freezers Test Procedure
Primary source
Metadata and text below are from the Federal Register, a public-domain U.S. government work. Always verify the official published version before relying on it for any legal matter.
Issuing agencies
Abstract
The U.S. Department of Energy ("DOE") gives notification of a Decision and Order (Case Number 2022-004) that grants to Norlake, Inc., dba Refrigerated Solutions Group ("RSG") a waiver from specified portions of the DOE test procedure for determining the energy efficiency of specified walk-in cooler refrigeration systems. Under the Decision and Order, RSG is required to test and rate the specified basic models of its equipment in accordance with the alternate test procedure set forth in the Decision and Order.
Full Text
<html>
<head>
<title>Federal Register, Volume 88 Issue 224 (Wednesday, November 22, 2023)</title>
</head>
<body><pre>
[Federal Register Volume 88, Number 224 (Wednesday, November 22, 2023)]
[Notices]
[Pages 81385-81396]
From the Federal Register Online via the Government Publishing Office [<a href="http://www.gpo.gov">www.gpo.gov</a>]
[FR Doc No: 2023-25873]
=======================================================================
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
[Case Number 2022-004; EERE-2022-BT-WAV-0010]
Energy Conservation Program: Decision and Order Granting a Waiver
to Norlake, Inc., dba Refrigerated Solutions Group, From the Department
of Energy Walk-In Coolers and Walk-In Freezers Test Procedure
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Notification of decision and order.
-----------------------------------------------------------------------
SUMMARY: The U.S. Department of Energy (``DOE'') gives notification of
a Decision and Order (Case Number 2022-004) that grants to Norlake,
Inc., dba Refrigerated Solutions Group (``RSG'') a waiver from
specified portions of the DOE test procedure for determining the energy
efficiency of specified walk-in cooler refrigeration systems. Under the
Decision and Order, RSG is required to test and rate the specified
basic models of its equipment in accordance with the alternate test
procedure set forth in the Decision and Order.
DATES: The Decision and Order is effective on November 22, 2023. The
Decision and Order will terminate upon the date on which use of the
test procedure for walk-in coolers and walk-in freezers located at
title 10 of the Code of Federal Regulations (``CFR''), part 431,
subpart R, appendix C1 is required to determine compliance with energy
conservation standards. At such time, RSG must use the relevant test
procedure for this equipment for any testing to demonstrate compliance
with the applicable standards, and any other representations of energy
use.
FOR FURTHER INFORMATION CONTACT:
Ms. Julia Hegarty, U.S. Department of Energy, Office of Energy
Efficiency and Renewable Energy, Building Technologies Office, Mailstop
EE-5B, 1000 Independence Avenue SW, Washington, DC 20585-0121. Email:
<a href="/cdn-cgi/l/email-protection#7a3b29252d1b130c1f0825281f0b0f1f090e3a1f1f541e151f541d150c"><span class="__cf_email__" data-cfemail="7534262a22141c0310072a271004001006013510105b111a105b121a03">[email protected]</span></a>.
Mr. Matthew Schneider, U.S. Department of Energy, Office of the
General Counsel, GC-33, 1000 Independence Avenue SW, Washington, DC
20585-0121. Telephone: (240) 597-6265. Email: <a href="/cdn-cgi/l/email-protection#e885899c9c808d9fc69b8b80868d818c8d9aa88099c68c878dc68f879e"><span class="__cf_email__" data-cfemail="9cf1fde8e8f4f9ebb2effff4f2f9f5f8f9eedcf4edb2f8f3f9b2fbf3ea">[email protected]</span></a>.
SUPPLEMENTARY INFORMATION: In accordance with 10 CFR 431.401(f)(2), DOE
gives notification of the issuance of its Decision and Order as set
forth below. The Decision and Order grants RSG a waiver from the
applicable test procedure at 10 CFR part 431, subpart R, appendix C for
the specified basic models for which RSG petitioned for waiver and
provides that RSG must test and rate such equipment using the alternate
test procedure specified in the Decision and Order. RSG's
representations concerning the energy efficiency of the specified basic
models must be based on testing according to the provisions and
restrictions in the alternate test procedure set forth in the Decision
and Order, and the representations must fairly disclose the test
results. Distributors, retailers, and private labelers are held to the
same requirements when making
[[Page 81386]]
representations regarding the energy efficiency of this equipment. (42
U.S.C. 6314(d))
Any manufacturer of a basic model employing a technology or
characteristic for which a waiver was granted for another basic model
and that results in the need for a waiver (as specified by DOE in a
published decision and order in the Federal Register) must petition and
be granted a waiver for that basic model. (10 CFR 431.401(j))
Manufacturers may also submit a request for interim waiver pursuant to
the requirements of 10 CFR 431.401.
Case <greek-i>2022-004
Decision and Order
I. Background and Authority
The Energy Policy and Conservation Act, as amended (``EPCA''),\1\
authorizes the U.S. Department of Energy (``DOE'') to regulate the
energy efficiency of a number of consumer products and certain
industrial equipment. (42 U.S.C. 6291-6317) Title III, Part C \2\ of
EPCA established the Energy Conservation Program for Certain Industrial
Equipment, which sets forth a variety of provisions designed to improve
the energy efficiency for certain types of industrial equipment. This
equipment includes walk-in coolers and walk-in freezers (collectively,
``walk-ins''), the focus of this document. (42 U.S.C. 6311(1)(G))
---------------------------------------------------------------------------
\1\ All references to EPCA in this document refer to the statute
as amended through the Energy Act of 2020, Public Law 116-260 (Dec.
27, 2020), which reflect the last statutory amendments that impact
Parts A and A-1 of EPCA.
\2\ For editorial reasons, upon codification in the U.S. Code,
Part C was redesignated as Part A-1.
---------------------------------------------------------------------------
The energy conservation program under EPCA consists essentially of
four parts: (1) testing, (2) labeling, (3) Federal energy conservation
standards, and (4) certification and enforcement procedures. Relevant
provisions of EPCA include definitions (42 U.S.C. 6311), energy
conservation standards (42 U.S.C. 6313), test procedures (42 U.S.C.
6314), labeling provisions (42 U.S.C. 6315), and the authority to
require information and reports from manufacturers (42 U.S.C. 6316; 42
U.S.C. 6299).
The Federal testing requirements consist of test procedures that
manufacturers of covered equipment must use as the basis for: (1)
certifying to DOE that their equipment complies with the applicable
energy conservation standards adopted pursuant to EPCA (42 U.S.C.
6316(a); 42 U.S.C. 6295(s)), and (2) making representations about the
efficiency of that equipment (42 U.S.C. 6314(d)). Similarly, DOE must
use these test procedures to determine whether the equipment complies
with relevant standards promulgated under EPCA. (42 U.S.C. 6316(a); 42
U.S.C. 6295(s))
Under 42 U.S.C. 6314, EPCA sets forth the criteria and procedures
DOE is required to follow when prescribing or amending test procedures
for covered equipment. EPCA requires that any test procedures
prescribed or amended under this section must be reasonably designed to
produce test results which reflect energy efficiency, energy use or
estimated annual operating cost of covered equipment during a
representative average use cycle and requires that test procedures not
be unduly burdensome to conduct. (42 U.S.C. 6314(a)(2)) The test
procedures for walk-in refrigeration systems are set forth at 10 CFR
part 431, subpart R, appendix C, Uniform Test Method for the
Measurement of Net Capacity and AWEF of Walk-in Cooler and Walk-in
Freezer Refrigeration Systems (``appendix C'') and appendix C1, Uniform
Test Method for the Measurement of Net Capacity and AWEF2 of Walk-In
Cooler and Walk-In Freezer Refrigeration Systems (``appendix C1'').\3\
---------------------------------------------------------------------------
\3\ Appendix C is the test procedure currently required for
walk-in refrigeration systems to demonstrate compliance with energy
conservation standards. Use of appendix C1 will be required
beginning on the compliance date of any amended energy conservation
standards for walk-ins published after January 1, 2022. DOE has
established separate test procedures for walk-in envelope components
at 10 CFR part 431, subpart R, appendices A and B. Appendix A is
used for testing the energy use of walk-in display panels, display
doors, and non-display doors; appendix B is used for testing
insulation R-value of non-display panels and non-display doors.
---------------------------------------------------------------------------
Any interested person may submit a petition for waiver from DOE's
test procedure requirements. 10 CFR 431.401(a)(1). DOE will grant a
waiver from the test procedure requirements if DOE determines either
that the basic model for which the waiver was requested contains a
design characteristic that prevents testing of the basic model
according to the prescribed test procedures, or that the prescribed
test procedures evaluate the basic model in a manner so
unrepresentative of its true energy consumption characteristics as to
provide materially inaccurate comparative data. 10 CFR 431.401(f)(2).
In granting a waiver or interim waiver, DOE will not change the energy
use or efficiency metric that the manufacturer must use to certify
compliance with the applicable energy conservation standard and to make
representations about the energy use or efficiency of the covered
equipment. 10 CFR 431.401(a). DOE may grant the waiver subject to
conditions, including adherence to alternate test procedures. 10 CFR
431.401(f).
As soon as practicable after the granting of any waiver, DOE will
publish in the Federal Register a notice of proposed rulemaking to
amend its regulations so as to eliminate any need for the continuation
of such waiver. 10 CFR 431.401(l). As soon thereafter as practicable,
DOE will publish in the Federal Register a final rule to that effect.
Id. When DOE amends the test procedure to address the issues presented
in a waiver, the waiver will automatically terminate on the date on
which use of that test procedure is required to demonstrate compliance.
10 CFR 431.401(h)(3).
II. RSG's Petition for Waiver: Assertions and Determinations
On February 17, 2022, DOE received from RSG a petition for waiver
and interim waiver from the DOE test procedure for walk-in
refrigeration systems set forth at 10 CFR part 431, subpart R, appendix
C. (RSG, No. 1, attachment 1, at pp. 1-3 \4\) Pursuant to 10 CFR
431.401(e)(i), DOE posted the petition on the DOE website. The petition
did not identify any of the information contained therein as
confidential business information.
---------------------------------------------------------------------------
\4\ A notation in this form provides a reference for information
that is in the docket for this test procedure waiver (Docket No.
EERE-2022-BT-WAV-0010) (available at <a href="http://www.regulations.gov/document/EERE-2022-BT-WAV-0010">www.regulations.gov/document/EERE-2022-BT-WAV-0010</a>). This notation indicates that the statement
preceding the reference is from document number 1 in the docket and
appears at pages 1-3 of attachment 1 of that document. There are two
attachments to document 1 of this docket. Attachment 1 is titled
``DOE Waiver 021722''. Attachment 2 is titled ``RSG DOE Single
Package System Alternate Test Procedure 021522''.
---------------------------------------------------------------------------
DOE's currently applicable test procedure for walk-in refrigeration
systems (i.e., appendix C) incorporates by reference Air-Conditioning,
Heating, and Refrigeration Institute (``AHRI'') Standard 1250-2009,
2009 Standard for Performance Rating of Walk-In Coolers and Freezers
(``AHRI 1250-2009''); AHRI Standard 420-2008, Performance Rating of
Forced-Circulation Free-Delivery Unit Coolers for Refrigeration (``AHRI
420-2008''); and American Society of Heating, Refrigerating, and Air-
Conditioning Engineers (``ASHRAE'') Standard 23.1-2010, Methods of
Testing for Rating the Performance of Positive Displacement Refrigerant
Compressors and Condensing Units that Operate at Subcritical
Temperatures of the Refrigerant (``ASHRAE 23.1-2010''). AHRI 1250-2009
is the industry test standard for refrigeration systems for
[[Page 81387]]
walk-in coolers and freezers, including unit coolers and dedicated
condensing units sold separately, as well as matched pairs. The
procedure describes the method for measuring the refrigeration capacity
and the electrical energy consumption for walk-in refrigeration
systems. Using the refrigeration capacity and electrical energy
consumption, AHRI 1250-2009 provides a calculation methodology to
compute AWEF, the applicable energy-performance metric for
refrigeration systems.
In its petition for waiver and interim waiver, RSG presented
several ways in which the currently prescribed test procedure would
evaluate the specified basic models in a manner so unrepresentative of
their true energy consumption as to provide materially inaccurate
comparative data. These issues are summarized below.
First, as presented in RSG's petition, the specified basic models
of walk-in refrigeration systems are single-packaged dedicated systems
that contain multiple refrigeration circuits that operate using a
single power feed. (RSG, No. 1, attachment 1, at p. 1) RSG claimed that
the specified basic models meet the definition of a single-packaged
dedicated system. Id. DOE defines a single-packaged dedicated system as
``a single-package assembly that includes one or more compressors, a
condenser, a means for forced circulation of refrigerated air, and
elements by which heat is transferred from air to refrigerant, without
any element external to the system imposing resistance to flow of the
refrigerated air''. See 10 CFR 431.302. As described by RSG, each
refrigeration circuit in the specified basic models is made up of a
compressor, expansion, device, condenser, and evaporator. (RSG, No. 1,
attachment 1, at p. 1) The separate refrigeration circuits may share
condenser fans, evaporator fans and a control system. Id. In its
request for waiver and interim waiver, RSG stated that neither appendix
C nor AHRI 1250-2009 provide a method for testing a single-packaged
dedicated system with multiple refrigeration circuits. Id.
Second, RSG stated that the current test procedure requires that
the unit under test be set up using a 25-foot line-set. Id. Section 3.3
of appendix C provides the test method for matched systems, single-
packaged dedicated systems, and unit coolers tested alone, which
references AHRI 1250-2009. Section C5 (Methods of Testing for Walk-In
Cooler and Freezer Systems that Have Matched Unit Coolers and
Condensing Units) of AHRI 1250-2009 references test setup requirements
that include the addition of a line-set that includes either one or two
mass flow meters. Under section C5 of AHRI 1250-2009, the gross
refrigeration capacity must be determined either by the dual
instrumentation refrigerant enthalpy method (section C5.1.1 of AHRI
1250-2009, Method 1) or by the calibrated box method (section C5.1.2 of
AHRI 1250-2009, Method 2). Both methods require installation of a
refrigerant mass flow meter in the system's liquid line to determine
the cooling capacity. Section C8.3 and Figure C1 of AHRI 1250-2009
specify the setup and measurements to be conducted for Method 1, for
which 25-feet of additional refrigerant line is added to connect the
condenser to the evaporator (unit cooler). Within this 25-foot line,
two mass flow meters are incorporated, and the heat balance calculated
from the two flow measurements must be within <plus-minus>5 percent.
Section C9.2 and Figure C2 of AHRI 1250-2009 specify the setup and
measurements for Method 2, in which 26-feet of additional refrigerant
line is added to connect the condenser to the unit cooler (as for
Method 1), incorporating one mass flow meter. Air-side gross
refrigeration capacity and refrigerant-side gross refrigeration
capacity are determined and must be equal to within <plus-minus>5
percent for the test to be considered valid. The 25 feet and 26 feet
\5\ of additional liquid line and suction line piping used to set up
the test is termed a ``line-set''. In its petition for waiver and
interim waiver, RSG stated that single-packaged dedicated systems are
not intended to be remotely split via a line-set. (RSG, No. 1,
attachment 1, at p. 1)
---------------------------------------------------------------------------
\5\ AHRI 1250-2009 does not explain why Method 1 requires 25
feet of refrigeration line and Method 2 requires 26 feet of
refrigeration line during test set up.
---------------------------------------------------------------------------
In its request for waiver and interim waiver, RSG noted that DOE
has issued test procedure waivers for single-packaged dedicated
refrigeration systems using air enthalpy test methods. (RSG, No. 1,
attachment 1, at p. 2) DOE granted a waiver to Store It Cold for basic
models of single-packaged dedicated systems on August 9, 2019. 84 FR
39286. Store It Cold petitioned for a waiver after determining that the
dual instrumentation refrigerant enthalpy method specified in AHRI
1250-2009 was not providing consistent capacity measurements for its
single-packaged dedicated systems. 84 FR 39286, 39287. The alternate
test procedure associated with this prior waiver required that the
specified single-packaged dedicated system basic models shall be tested
using the Indoor Air Enthalpy Method and the Outdoor Air Enthalpy
Method in accordance with ASHRAE 37-2009, Methods of Testing for Rating
Electrically Driven Unitary Air-Conditioning and Heat-Pump Equipment
(``ASHRAE 37''). 84 FR 39286, 39292. DOE also granted waivers to Air
Innovations, CellarPro, Vinotemp, and Vinotheque for walk-in
refrigeration systems used in wine cellar applications, for which some
of the basic models included in these waivers were single-packaged
dedicated systems.\6\ The alternate test methods included in these
waivers require the specified basic models to be tested in accordance
with AHRI Standard 1250-2020 (2020 Standard for Performance Rating of
Walk-In Coolers and Freezers, ``AHRI 1250-2020''), which references the
air enthalpy methods in ASHRAE 37 for testing single-packaged dedicated
systems.\7\ Use of air enthalpy methods for testing a single-packaged
dedicated system capture the impact of thermal loss and the
infiltration of warm air into the evaporator portion of these systems,
which increases the refrigerant load on the system. In its petition for
waiver and interim waiver, RSG stated that its laboratory is not set up
to conduct air enthalpy testing, and that it would require substantial
time and expense to set up its laboratory to conduct air enthalpy
testing. (RSG, No. 1, attachment 1, at p. 2) Additionally, RSG
explained that it contacted third-party labs to inquire about testing
single-packaged dedicated systems using the air enthalpy method, but
these labs responded that they are not currently able to conduct air
enthalpy testing. Id.
---------------------------------------------------------------------------
\6\ See Waiver Decision and Orders for Air Innovations (86 FR
23702 (May 4, 2021)), CellarPro (86 FR 26496 (May 14, 2021)),
Vinotheque (86 FR 26504 (May 14, 2021)), and Vinotemp (86 FR 36732
(Jul. 13, 2021)).
\7\ Subsequent to DOE's grant of waiver to Store It Cold, AHRI
published an updated version of AHRI 1250 (i.e., AHRI 1250-2020)
that provides testing provisions for single-packaged dedicated
systems that incorporate by reference the approach used in ASHRAE 37
with some modification.
---------------------------------------------------------------------------
Third, in its request for waiver and interim waiver from the DOE
test procedure, RSG stated that the current tolerance requirement of
0.5 [deg]F for the on-coil temperature in section C3.3.3 of AHRI 1250-
2009 is unrealistic. Id. RSG stated that indoor air temperature
tolerances impact the on-coil temperatures, and that the test procedure
currently prescribes a 1 [deg]F indoor air temperature test condition
tolerance.\8\ Id. RSG therefore suggested
[[Page 81388]]
that the on-coil temperature tolerance should also be 1 [deg]F. Id. RSG
noted further that it can be difficult to repeatedly achieve an on-coil
temperature tolerance of 0.5 [deg]F when units are shut down, re-
plumbed, and recharged for testing. Id.
---------------------------------------------------------------------------
\8\ Test condition tolerance is the maximum allowed deviation of
the average of the measurements of a parameter made during a test
period as compared with its target value. The indoor air dry-bulb
test condition tolerance is specified as 1 [deg]F in Table 2 of AHRI
1250-2009.
---------------------------------------------------------------------------
RSG also requested an interim waiver from the existing DOE test
procedure, explaining that if DOE were to deny its application for
waiver and interim waiver, it would experience economic hardship in the
form of lost sales and/or a significant delay in the distribution into
commerce of the specified basic models. Id.
On July 22, 2022, DOE published a notification announcing its
receipt of the petition for waiver and interim waiver and granted RSG
an interim waiver. 87 FR 43808 (``Interim Waiver Order''). In the
Interim Waiver Order, DOE initially determined that the alternate test
procedure--with certain minor modifications as discussed in the Interim
Waiver Order--appears to allow for the accurate measurement of the
energy efficiency of the specified basic models, while alleviating the
testing problems cited by RSG in its attempts to implement the DOE test
procedure for these basic models. Id. at 87 FR 43814. The alternate
test procedure established in the Interim Waiver Order is based on the
calibrated box method (i.e., Method 2 of AHRI 1250-2009) with
modifications to the refrigerant enthalpy test provisions of this
method. Id. at 87 FR 43813. Using the calibrated box method, the
measured capacity includes the thermal loss through the evaporator of
the single-packaged dedicated system under test. Id. The calibrated box
method serves as the primary test method. A modified version of the
single-packaged refrigerant enthalpy method is specified in the
alternate test procedure for use as a secondary test method.\9\ Id.
Under the modified refrigerant enthalpy method, the refrigerant liquid
line length is reduced from 25 feet (as prescribed in AHRI 1250-2009)
to a maximum of 5 feet, allows for the capacity measurements of
multiple refrigerant circuits, and adds a calculation to estimate the
single-packaged thermal loss of the unit under test. Id. The capacity
as measured by the primary and secondary test methods must be within 6
percent of one another for a valid test. Id. at 87 FR 43814.
---------------------------------------------------------------------------
\9\ A secondary test method's results are used to ensure the
capacity tolerance is met when compared to the capacity determined
by a primary test method, but are not used for rating performance.
---------------------------------------------------------------------------
The alternate test procedure established in the Interim Waiver
Order differed from the alternate test procedure proposed by RSG with
regard to the condenser air entering wet-bulb temperature test
condition. Id. RSG proposed that the condenser air entering wet-bulb
temperature test condition be 68 [deg]F for single-packaged dedicated
systems that do not use evaporative dedicated condensing units, for
which all or part of the equipment is located in the outdoor room. Id.
Whereas, the alternate test procedure established in the Interim Waiver
Order specifies the condensing air entering wet-bulb temperature as 65
[deg]F, which maintains consistency with the requirements in Table 8 of
AHRI 1250-2020. Id.
In the Interim Waiver Order, DOE solicited comments from interested
parties on all aspects of the petition and the specified alternate test
procedure. 87 FR 43808, 43809. DOE did not receive any comments in
response to the Interim Waiver Order.
On May 4, 2023, DOE published a test procedure final rule (``May
2023 Final Rule'') that established a new test procedure for walk-in
coolers and walk-in freezers at appendix C1, in addition to specifying
minor amendments to appendix C. 88 FR 28780, 28810. Appendix C1
includes test provisions for multi-circuit single-package dedicated
systems that are substantively the same as the methodology granted in
the Interim Waiver Order. Use of appendix C1 is not required until the
compliance date of any amended energy conservation standards based on
the test procedure in appendix C1. Until such time, use of appendix C
is required to demonstrate compliance with current standards. As
discussed in the May 2023 Final Rule, the amendments to appendix C did
not include provisions for multi-circuit single-package dedicated
systems.\10\ As such, for the basic models subject to the Interim
Waiver Order, the need for the waiver from appendix C will continue
until such time as use of appendix C1 is required.
---------------------------------------------------------------------------
\10\ DOE notes a typographical error in Table III.8 of the May
2023 Final Rule. 88 FR 28780, 28827. In that table, the interim
waiver granted to RSG was indicated as being addressed by amendments
to appendix C, with compliance beginning October 31, 2023. Id. The
table should have indicated the RSG interim waiver as being
addressed by appendix C1, with a compliance date corresponding to
``Compliance date of updated standards.''
---------------------------------------------------------------------------
For the reasons explained here and in the Interim Waiver Order,
absent a waiver the basic models identified by RSG in its petition
cannot be tested and rated for energy consumption on a basis
representative of their true energy consumption characteristics.
Therefore, DOE has determined that the current test procedure for walk-
in cooler refrigeration systems would evaluate the subject basic models
in a manner so unrepresentative of its true energy consumption
characteristics as to provide materially inaccurate comparative data.
DOE has reviewed the recommended procedure suggested by RSG and
concludes that, with minor modification to the condenser air entering
wet bulb temperature as discussed previously, it will allow for the
accurate measurement of the energy use of the equipment, while
alleviating the testing problems associated with RSG's implementation
of DOE's applicable walk-in test procedure for the specified basic
models.
Thus, DOE is requiring that RSG test and rate specified walk-in
basic models according to the alternate test procedure specified in
this Decision and Order, which is identical to the alternate test
procedure specified in the Interim Waiver Order.\11\
---------------------------------------------------------------------------
\11\ DOE notes that while the test provisions of this Decision
and Order are identical to those presented in the Interim Waiver
Order, the section numbering of the test provisions specified in
this Decision and Order are slightly different than those sections
specified in the Interim Waiver Order due to other section numbering
changes made to appendix C by the May 2023 Final Rule.
---------------------------------------------------------------------------
This Decision and Order is applicable only to the basic models
listed and does not extend to any other basic models. DOE evaluates and
grants waivers for only those basic models specifically set out in the
petition, not future models that may be manufactured by the petitioner.
RSG may request that DOE extend the scope of this waiver to include
additional basic models that employ the same technology as those listed
in this waiver. 10 CFR 431.401(g). RSG may also submit another petition
for waiver from the test procedure for additional basic models that
employ a different technology and meet the criteria for test procedure
waivers. 10 CFR 431.401(a)(1).
DOE notes that it may modify or rescind the waiver at any time upon
DOE's determination that the factual basis underlying the petition for
waiver is incorrect, or upon a determination that the results from the
alternate test procedure are unrepresentative of the basic models' true
energy consumption characteristics. 10 CFR 431.401(k)(1). Likewise, RSG
may request that DOE rescind or modify the waiver if the company
discovers an error in the information provided to DOE as part of its
petition, determines that the waiver is no longer needed, or for other
[[Page 81389]]
appropriate reasons. 10 CFR 431.401(k)(2).
III. Order
After careful consideration of all the material that was submitted
by RSG, in this matter, it is ordered that:
(1) RSG must test and rate the following Norlake- and Masterbilt-
branded basic models with the test procedure set forth in paragraph
(2).
------------------------------------------------------------------------
Cooler basic models Freezer basic models
------------------------------------------------------------------------
CPB050PC-S-0.............................. CPF050PC-S-0
CPB075PC-S-0.............................. CPF075PC-S-0
CPB100PC-S-0.............................. CPF100PC-S-0
CPF150PC-S-4
CPF200PC-S-4
------------------------------------------------------------------------
(2) The alternate test procedure for the RSG basic models
identified in paragraph (1) of this Order is the test procedure for
walk-in refrigeration systems prescribed by DOE at 10 CFR part 431,
subpart R, appendix C (``appendix C'') as amended by the May 2023 Final
Rule, except that multiple-circuit single-packaged dedicated systems
shall use: (1) either the calibrated box method or an indoor air
enthalpy test as the primary test method, as detailed below; (2) the
modified refrigerant enthalpy method as the secondary test method, as
detailed below; (3) the net capacity from the primary and secondary
test methods must agree within <plus-minus> 6 percent, as detailed
below; and (4) reported values for the overall system shall be the
summation of the gross capacities obtained from the modified
refrigerant enthalpy method conducted for each refrigeration circuit
included in the unit under test, as detailed below. All other
requirements of appendix C as amended by the May 2023 Final Rule and
DOE's regulations remain applicable.
In appendix C:
Revise section 3.1.1 to read as follows:
3.1.1. In Table 1 of AHRI 1250-2009, Instrumentation Accuracy,
refrigerant temperature measurements shall have a tolerance of <plus-
minus>0.5 [deg]F for unit cooler in/out. Temperature measurements used
to determine water vapor content of the air shall be accurate to within
<plus-minus>0.4 [deg]F. All other temperature measurements shall be
accurate to <plus-minus>1.0 [deg]F.
Revise section 3.1.4 to read as follows:
3.1.4. In Tables 2 through 14 of AHRI 1250-2009, the Test Condition
Outdoor Wet Bulb Temperature requirement and its associated tolerance
apply only to units with evaporative cooling and single-packaged
dedicated systems.
Insert new section 3.1.8 as follows:
3.1.8 Tables 3, 4, 7 and 8 of AHRI 1250-2009 shall be modified to
read as follows:
Table 3--Fixed Capacity Matched Refrigerator System, Condensing Unit Located Indoor
--------------------------------------------------------------------------------------------------------------------------------------------------------
Unit
Unit cooler air Condenser
cooler air entering air Condenser air entering
Test description entering relative entering wet-bulb, [deg]F Compressor capacity Test objective
dry-bulb, humidity, dry-bulb,
[deg]F (%) ([deg]F)
--------------------------------------------------------------------------------------------------------------------------------------------------------
Off Cycle Fan Power............. 35 <50 ........... ........................ Compressor Off............. Measure fan input
wattage during
compressor off cycle.
Refrigeration Capacity.......... 35 <50 90 75 \1\ or 65 \2\........ Compressor On.............. Determine Net
Refrigeration Capacity
of Unit Cooler, input
power, and EER at
Rating Condition.
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ Required only for evaporative Dedicated Condensing Units
\2\ Maximum allowable value for Single-Packaged Dedicated Systems that do not use evaporative Dedicated Condensing Units, where all or part of the
equipment is located in the outdoor room.
Table 4--Fixed Capacity Matched Refrigerator System, Condensing Unit Located Outdoor
--------------------------------------------------------------------------------------------------------------------------------------------------------
Unit
Unit cooler air Condenser
cooler air entering air Condenser air entering
Test description entering relative entering wet-bulb, [deg]F Compressor capacity Test objective
dry-bulb, humidity, dry-bulb,
[deg]F (%) ([deg]F)
--------------------------------------------------------------------------------------------------------------------------------------------------------
Off Cycle Fan Power............. 35 <50 ........... ........................ Compressor Off............. Measure fan input
wattage during
compressor off cycle.
Refrigeration Capacity A........ 35 <50 95 75 \1\ or 68 \2\........ Compressor On.............. Determine Net
Refrigeration Capacity
of Unit Cooler, input
power, and EER at
Rating Condition.
Refrigeration Capacity B........ 35 <50 59 54 \1\ or 46 \2\........ Compressor On.............. Determine Net
Refrigeration Capacity
of Unit Cooler, and
system input power at
moderate condition.
Refrigeration Capacity C........ 35 <50 35 34 \1\ or 29 \2\........ Compressor On.............. Determine Net
Refrigeration Capacity
of Unit Cooler, and
system input power at
cold condition.
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ Required only for evaporative Dedicated Condensing Units.
\2\ Maximum allowable value for Single-Packaged Dedicated Systems that do not use evaporative Dedicated Condensing Units, where all or part of the
equipment is located in the outdoor room.
Table 7--Fixed Capacity Matched Freezer System, Condensing Unit Located Indoor
--------------------------------------------------------------------------------------------------------------------------------------------------------
Unit
Unit cooler air Condenser
cooler air entering air Condenser air entering
Test description entering relative entering wet-bulb, [deg]F Compressor capacity Test objective
dry-bulb, humidity, dry-bulb,
[deg]F (%) ([deg]F)
--------------------------------------------------------------------------------------------------------------------------------------------------------
Off Cycle Fan Power............. -10 <50 ........... ........................ Compressor Off............. Measure fan input
wattage during
compressor off cycle.
Refrigeration Capacity.......... -10 <50 90 75 \1\ or 65 \2\........ Compressor On.............. Determine Net
Refrigeration Capacity
of Unit Cooler, input
power, and EER at
Rating Condition.
Defrost Frost Load.............. -10 Various 90 75 \1\ or 65 \2\........ System Dependent........... Test according to
section C11 of AHRI
1250-2009.
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ Required only for evaporative Dedicated Condensing Units.
[[Page 81390]]
\2\ Maximum allowable value for Single-Packaged Dedicated Systems that do not use evaporative Dedicated Condensing Units, where all or part of the
equipment is located in the outdoor room.
Table 8--Fixed Capacity Matched Freezer System, Condensing Unit Located Outdoor
--------------------------------------------------------------------------------------------------------------------------------------------------------
Unit
Unit cooler air Condenser
cooler air entering air Condenser air entering
Test description entering relative entering wet-bulb, [deg]F Compressor capacity Test objective
dry-bulb, humidity, dry-bulb,
[deg]F (%) ([deg]F)
--------------------------------------------------------------------------------------------------------------------------------------------------------
Off Cycle Fan Power............. -10 <50 ........... ........................ Compressor Off............. Measure fan input
wattage during
compressor off cycle.
Refrigeration Capacity A........ -10 <50 95 75 \1\ or 68 \2\........ Compressor On.............. Determine Net
Refrigeration Capacity
of Unit Cooler, input
power, and EER at
Rating Condition.
Refrigeration Capacity B........ -10 <50 59 54 \1\ or 46 \2\........ Compressor On.............. Determine Net
Refrigeration Capacity
of Unit Cooler, input
power, and EER at
Rating Condition.
Refrigeration Capacity C........ -10 <50 35 34 \1\ or 29 \2\........ Compressor On.............. Determine Net
Refrigeration Capacity
of Unit Cooler, input
power, and EER at
Rating Condition.
Defrost Frost Load.............. -10 Various 95 75 \1\ or 68 \2\........ System Dependent........... Test according to
section C11 of AHRI
1250-2009.
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ Required only for evaporative Dedicated Condensing Units.
\2\ Maximum allowable value for Single-Packaged Dedicated Systems that do not use evaporative Dedicated Condensing Units, where all or part of the
equipment is located in the outdoor room.
Remove section 3.2.5.
Add a new section 4, following section 3.5 Hot Gas Defrost
Refrigeration Systems
4.0 Multiple-Circuit Single-Packaged Dedicated Systems
When conducting testing in accordance with AHRI 1250-2009
(incorporated by reference; see 10 CFR 431.303), the following
modifications must be made.
4.1 Specific Modifications: Test Conditions and Tolerance
4.1.1 Replace section C3.1.2 of AHRI 1250-2009 with the following:
Air wet-bulb and dry-bulb temperatures entering the Single-Packaged
Dedicated System at its evaporator return and condenser air inlet shall
be measured based on the airflow area at the point of measurement. One
measuring station is required for each 2.0 ft\2\ of the first 10.0
ft\2\ of airflow area and one additional measuring station is required
for each 4.0 ft\2\ of airflow area above 10.0 ft\2\. A minimum of two
stations shall be used and the number of measuring stations shall be
rounded up to the next whole number.
4.1.2 Replace section C3.1.5 of AHRI 1250-2009 with the following:
If sampling tubes are used, each tube opening may be considered a
temperature measuring station provided the openings are uniformly
spaced along the tube, the airflow rates entering each port are
relatively uniform (<plus-minus>15%) and the arrangement of tubes
complies with the location requirements of section C3.1.2 of AHRI 1250-
2009. Additionally, a one-time temperature traverse shall be made over
the measurement surface, prior to the tests to assess the temperature
variation and ensure it complies with the allowable deviation specified
in section C3.1.4 of AHRI 1250-2009. (Refer to ANSI/ASHRAE Standard
41.1 for more information and diagrams). If sampling tubes are not used
for single-packaged dedicated systems that do not use evaporative
dedicated condensing units, a single air wet-bulb or RH sensor may be
used. When used, this sensor shall be located at the geometric center
of the largest condenser coil face and 6-12 inches from the condenser
coil.
4.1.3 Replace section 3.1.6 of AHRI 1250-2009 with the following:
Refrigerant temperatures entering and leaving the evaporator section of
the Single-Packaged Dedicated System shall be measured by a temperature
measuring instrument placed in a thermometer well and inserted into the
refrigerant stream. These wells shall be filled with non-solidifying,
thermal conducting liquid or paste to ensure the temperature sensing
instrument is exposed to a representative temperature. The entering
temperature of the refrigerant shall be measured within six pipe
diameters upstream of the expansion device. If the refrigerant tube
outer diameter is less than \1/2\-inch, the refrigerant temperature may
be measured using the average of two temperature measuring instruments
with a minimum accuracy of <plus-minus>0.5 [deg]F placed on opposite
sides of the refrigerant tube surface. In this case, the refrigerant
tube shall be insulated with 1-inch-thick insulation from a point 6
inches upstream of the measurement location to a point 6 inches
downstream of the measurement location. Also, the entering measurement
location may be moved to a location 6 inches upstream of the expansion
device.
4.2 Refrigerant Properties Measurement
4.2.1 Replace section C3.3.1 of AHRI 1250-2009 with the following:
With the equipment operating at the desired test conditions, the
temperature and pressure of the refrigerant leaving the unit cooler,
entering the expansion device, and entering and leaving the compressor
shall be measured. For cases where the calibrated box method or indoor
air enthalpy method is also conducted, data used to calculate capacity
according to the single-package refrigerant enthalpy method and the
additional method shall be collected over the same intervals.
4.2.2 Replace section C3.3.3 of AHRI 1250-2009 with the following:
For Single-Packaged Dedicated Systems tested using either the
calibrated box method or the indoor air enthalpy method as the primary
measurement and the single-package refrigerant enthalpy method as the
secondary method, a preliminary test for Rating Condition A using the
primary method is required prior to setting up the refrigerant enthalpy
method measurements. In preparation for this preliminary test,
temperature sensors shall be attached to the equipment's evaporator and
condenser coils. The sensors shall be located at points that are not
affected by vapor superheat or liquid subcooling. Placement near the
midpoint of the coil, at a return bend, is recommended. The preliminary
test shall be conducted with the requirement that the temperatures of
the on-coil sensors be included with the regularly recorded data. After
the preliminary test is completed, the refrigerant shall be removed
from the equipment, and the refrigerant enthalpy measurement setup
shall be completed. The equipment
[[Page 81391]]
shall be evacuated and recharged with refrigerant. The test shall then
be repeated. Once steady-state operation is achieved, refrigerant shall
be added or removed until, as compared to the average values from the
preliminary test, the following conditions are achieved: (1) each on-
coil temperature sensor indicates a reading that is within <plus-
minus>1.0 [deg]F, (2) the temperatures of the refrigerant entering and
leaving the compressor are within <plus-minus>4 [deg]F, and (3) the
refrigerant temperature entering the expansion device is within <plus-
minus>1 [deg]F. Once these conditions have been achieved over an
interval of at least ten minutes, refrigerant charging equipment shall
be removed, and the remaining tests shall be conducted.
4.2.3 When conducting the refrigerant enthalpy method for a Single-
Packaged Dedicated System, the length of the added liquid line
conducting refrigerant out of the system, to the flow meter, and back
into the system shall be no more than 5 feet. No such modification to
the suction line shall be made.
4.3 Methods for Testing for Walk-In Cooler and Freezer Systems That
Have Matched Unit Coolers and Condensing Units
Disregard section C5 of AHRI 1250-2009 and instead test according
to the following method:
4.3.1 The Refrigeration Capacity for Single-Packaged Dedicated
Systems shall be determined using either the Calibrated Box method or
the Indoor Air Enthalpy method as a primary test method and the Single-
Package Refrigerant Enthalpy method as the secondary test method.
4.3.1.1 Single-Package Refrigerant Enthalpy method shall determine
gross refrigeration capacity by measuring the enthalpy change and the
mass flow rate of the refrigerant using a single set of measurements.
4.3.1.2 Calibrated Box method shall determine net refrigeration
capacity by measuring the heat input to the calibrated box, including
thermal transfer through the calibrated box walls.
4.3.2 Indoor Air Enthalpy method shall determine net refrigeration
capacity of Single-Packaged Dedicated System and input power in
accordance with ASHRAE 37-2009, Figure C4 of AHRI 1250-2020, and the
following modifications.
4.3.2.1 Net refrigeration capacity is determined by measuring
airflow rate and the dry-bub temperature and water vapor content of the
air that enters and leaves the coil.
4.3.2.2 Air enthalpies shall be determined in accordance with ANSI/
ASHRAE 41.6. Entering air is to be sufficiently dry as to not produce
frost on the evaporator coil. Therefore, only sensible capacity
measured by dry bulb change shall be used to calculate capacity.
4.3.3 Testing Sequence. The primary test method shall be used to
measure the capacity for Rating Condition A prior to set-up of the
Single-Package Refrigerant Enthalpy Measurement. After set-up of the
Refrigerant Enthalpy method, the Net Capacity shall be measured using
both the primary test method and the Refrigerant Enthalpy method. The
Net Capacity measurement using the Refrigerant Enthalpy method shall be
within 6 percent of the net capacity measurement using the primary
method.
If a capacity balance within tolerance is not initially achieved,
take steps to reduce the thermal losses of the Single-Packaged
Dedicated System evaporator compartment by sealing air gaps and
potentially adding more external insulation. If using the Calibrated
Box method as the primary method, achieving a capacity balance may
require conducting the calibration with calibrated box insulation
material at the same average temperature as during capacity
measurement, or using multiple calibrations conducted at different
average insulation material temperatures and using these data to
construct a correlation for the calibration coefficient,
K<INF>cb</INF>, as a function of average insulation temperature. The
official performance measurements are based on the primary method
testing without any air gap sealing and additional external insulation
used to achieve the 6 percent energy balance in place.
4.3.4 The refrigerant enthalpy method Net Capacity shall be
calculated from the Gross Capacity Measurement as follows.
qss,2 = Qref - 3.412 x EFcomp,on-Qsploss
Where Qsploss represents the Single-Packaged Dedicated System thermal
losses through the walls of the evaporator side of the Single-Packaged
Dedicated System to the condenser side and to the exterior ambient, and
shall be calculated as follows.
Qsploss = UAcond x (Tcondside-Tevapside) + UAamb x (Tamb-Tevapside)
Where:
UAcond and UAamb are, for the condenser/evaporator partition and the
evaporator compartment walls exposed to ambient air, respectively,
the product of the overall heat transfer coefficient and surface
area of the unit as manufactured, i.e., without external insulation
that might have been added during the test;
Tevapside is the air temperature in the evaporator compartment;
Tcondside is the air temperature in the condenser compartment; and
Tamb is the air temperature outside the Single-Packaged Dedicated
System.
The Net Capacity to be used in AWEF calculations shall be the net
capacity measured using the primary method.
4.3.5 Upon the completion of the Rating Condition A steady state
test, an off-cycle evaporator fan power test shall be conducted to
measure the evaporator fan power consumption during a compressor-off
period in accordance with section C10 of AHRI 1250-2009.
4.3.6 Upon the completion of the Rating Condition A steady state
test for walk-in freezer systems, a mandatory defrost test shall be
conducted to establish the energy input for a defrost cycle.
4.3.7 Upon the completion of the Rating Condition A steady state
test, off-cycle evaporator fan power test, and defrost test (for walk-
in freezer systems), the Rating Condition B and C steady state tests
shall be conducted. Capacity balance as described in section C9.2 of
AHRI 1250-2020 for Rating Condition A is not required for Rating
Conditions B and C.
4.4 Test Chamber Requirements
Disregard section C6 of AHRI 1250-2009 and instead test according
to the following method:
4.4.1 For single-packaged dedicated systems, test chamber
requirements shall be as follows:
a. For the calibrated box method, follow ASHRAE 16-2016 Section 6.1
for calibrated type calorimeters excluding water and water energy
inputs for the indoor-side compartment.
b. For the indoor air enthalpy method, follow ASHRAE 37-2009.
4.5 Single-Packaged Dedicated System Refrigerant Enthalpy Method
4.5.1 General Description. In this method, capacity is determined
from the refrigerant enthalpy change and flow rate. Enthalpy changes
are determined from measurements of entering and leaving pressures and
temperatures of the refrigerant, and the flow rate is determined by a
suitable flow meter in the liquid line. This method shall not be used
for tests in which the refrigerant liquid leaving the flow meter is
subcooled less than 3 [deg]F or for tests in which any instantaneous
measurement of the superheat of the vapor leaving the evaporator coil
is less than 5 [deg]F. Supplementary cooling may be artificially
provided for the liquid line to ensure enough subcooling when
[[Page 81392]]
making measurements to establish the capacity balance for Rating
Condition A, however, no official measurements used to calculate AWEF
may be made while providing such supplementary cooling.
4.5.2 Measurements. Refer to Section 4.1 of this appendix and
section C3 of AHRI 1250-2009 for requirements of air-side and
refrigerant-side measurements.
4.5.3 Test Setup and Procedure. Refer to Section 4.4 of this
appendix, section C7 of AHRI 1250-2009, and Figure C3 of this section
for specific test setup. The length of the added liquid line shall be 5
feet, maximum.
BILLING CODE 6450-01-P
[GRAPHIC] [TIFF OMITTED] TN22NO23.258
4.5.4 Data to be Measured and Recorded. Refer to ``Refrigerant
Enthalpy Method'' in Table C2 in section C7.2 of AHRI 1250-2009 for the
required data that need to measured and recorded, except as follows.
4.5.4.1 Water vapor content of air entering the unit cooler
(evaporator) and condensing unit may be measured using a wet bulb
temperature measurement or a relative humidity sensor, but both are not
required.
4.5.4.2 Wet bulb temperature of air leaving the unit cooler
(evaporator) and condensing unit need not be measured.
4.5.4.3 Required refrigerant pressure measurement includes only
subcooled liquid entering the expansion valve and superheated vapor
exiting the unit cooler (evaporator).
4.5.4.4 Only one refrigerant mass flow measurement is required.
4.5.4.5 Measurement of Refrigerant oil flow rate and oil/
refrigerant mass ratio are not required.
4.5.5 Refrigeration Capacity Calculation.
[[Page 81393]]
4.5.5.1 The refrigerant-side gross capacity is calculated by
Qref = mref(hout-hin)
4.5.5.2 Measurement of Capacity for a Single-Packaged Dedicated
System with Multiple Refrigeration Circuits.
For a Single-Packaged Dedicated System with multiple refrigeration
circuits, apply the refrigerant enthalpy method separately for each
circuit and sum the separately-measured gross refrigeration capacities.
4.6 Calibrated Box Test Procedure
4.6.1 Measurements. Refer to section 4.1 of this section and
section C3 of AHRI 1250-2009 for requirements of air-side and
refrigerant-side measurements.
4.6.2 Apparatus setup for Calibrated Box Calibration and Test.
Refer to section 4.4 of this section, section C7 of AHRI 1250-2009, and
Figure C4 of this section for specific test setup.
BILLING CODE 6510-01-C
[GRAPHIC] [TIFF OMITTED] TN22NO23.259
4.6.2.1 The calibrated box shall be installed in a temperature-
controlled enclosure in which the temperature can be maintained at a
constant level. When using the calibrated box method for Single-
Packaged Dedicated Systems, the enclosure air temperature shall be
maintained such that the condenser air entering conditions are as
specified for the test.
4.6.2.2 The temperature-controlled enclosure shall be of a size
that will provide clearances of not less than 18 in at all sides, top
and bottom, except that clearance of any one surface may be reduced to
not less than 5.5 inches.
4.6.2.3 The heat leakage of the calibrated box shall be noted in
the test report.
4.6.2.4 Refrigerant lines within the calibrated box shall be well
insulated to avoid appreciable heat loss or gain.
4.6.2.5 Instruments for measuring the temperature around the
outside of the calibrated box to represent the enclosure temperature
T<INF>en</INF> shall be located at the center of each wall, ceiling,
and floor.
Exception: in the case where a clearance around the outside of the
calibrated box, as indicated above, is reduced to less than 18 inches,
the number of temperature-measuring devices on the outside of that
surface shall be increased to six, which shall be treated as a single
temperature to be averaged with the temperature of each of the other
five surfaces. There will be six rectangular sections of equal area,
and each of these six sections will have a temperature-measuring
instrument located at its center. If the refrigeration system is
mounted at the location that would cover the center of the face on
which it is mounted, up to four temperature measurements shall be used
on that face to represent its temperature. Each sensor shall be aligned
with the center of the face's nearest outer edge and centered on the
distance between that edge and the single-packaged unit (this is
illustrated in Figure C5 when using surface temperature sensors), and
they shall be treated as a single temperature to be averaged with the
temperature of each of the other five surfaces. However, any of these
sensors shall be omitted if either (a) the distance between the outer
[[Page 81394]]
edge and the single-packaged unit is less than one foot or (b) if the
sensor location would be within two feet of any of the foot-square
surfaces discussed below representing a warm discharge air impingement
area. In this case, the remaining sensors shall be used to represent
the average temperature for the surface.
One of the following two approaches shall be used for the box
external temperature measurement. Box calibration and system capacity
measurement shall both be done using the same one of these approaches.
4.6.2.5.1 Air temperature sensors. Each temperature sensor shall be
at a distance of 6 inches from the calibrated box. If the clearance
from a surface of the box (allowed for one surface only) is less than
12 inches, the temperature measuring instruments shall be located
midway between the outer wall of the calibrated box and the adjacent
surface.
4.6.2.5.2 Surface temperature sensors. Surface temperature sensors
shall be mounted on the calibrated box surfaces to represent the
enclosure temperature, T<INF>en</INF>.
Additional surface temperature sensors may be used to measure
external hot spots during refrigeration system testing. If this is
done, two temperature sensors shall be used to measure the average
temperature of the calibrated box surface covered by the condensing
section--they shall be centered on equal-area rectangles comprising the
covered calibrated box surface whose common sides span the short
dimension of this surface. Additional surface temperature sensors may
be used to measure box surfaces on which warm condenser discharge air
impinges. A pattern of square surfaces measuring one foot square shall
be mapped out to represent the hot spot upon which the warm condenser
air impinges. One temperature sensor shall be used to measure surface
temperature at the center of each square (see Figure C5 of this
section). A drawing showing this pattern and identifying the surface
temperature sensors shall be provided in the test report. The average
surface temperature of the overall calibrated box outer surface during
testing shall be calculated as follows.
[GRAPHIC] [TIFF OMITTED] TN22NO23.260
Where:
Ai is the surface area of the i\th\ of the six calibrated box
surfaces;
Ti is the average temperature measured for the i\th\ surface;
Aj is half of the surface area of the calibrated box covered by the
condensing section;
T'j is the j\th\ of the two temperature measurements underneath the
condensing section;
T1 is the average temperature of the four or fewer measurements
representing the temperature of the face on which the single-
packaged system is mounted, prior to adjustments associated with hot
spots based on measurements Tj and/or Tk;
Ak is the area of the k\th\ of n 1-square-foot surfaces used to
measure the condenser discharge impingement area hot spot; and,
T''k is the k\th\ of the n temperature measurements of the condenser
discharge impingement area hot spot.
BILLING CODE 6450-01-P
[[Page 81395]]
[GRAPHIC] [TIFF OMITTED] TN22NO23.261
BILLING CODE 6450-01-C
4.6.2.6 Heating means inside the calibrated box shall be shielded
or installed in a manner to avoid radiation to the Single-Packaged
Dedicated System, the temperature measuring instruments, and to the
walls of the box. The heating means shall be constructed to avoid
stratification of temperature, and suitable means shall be provided for
distributing the temperature uniformly.
4.6.2.7 The average air dry-bulb temperature in the calibrated box
during Single-Packaged Dedicated System tests and calibrated box heat
leakage tests shall be the average of eight temperatures measured at
the corners of the box at a distance of 2 inches to 4 inches from the
walls. The instruments shall be shielded from any cold or warm surfaces
except that they shall not be shielded from the adjacent walls of the
box. The Single-Packaged Dedicated System under test shall be mounted
such that the temperature instruments are not in the direct air stream
from the discharge of the Single-Packaged Dedicated System.
4.6.3 Calibration of the Calibrated Box. Calibration of the
Calibrated Box shall occur prior to installation of the Single-Packaged
Dedicated System. This shall be done either (a) prior to cutting the
opening needed to install the Single-Packaged Dedicated System, or (b)
with an insulating panel with the same thickness and thermal resistance
as the box wall installed in the opening intended for the Single-
Packaged Dedicated System installation. Care shall be taken to avoid
thermal shorts in the location of the opening either during calibration
or during subsequent installation of the Single-Packaged Dedicated
System. A calibration test shall be made for air movements comparable
to those expected for Single-Packaged Dedicated System capacity
measurement, i.e., with air volume flow rate within 10 percent of the
air volume flow rate of the Single-Packaged Dedicated System
evaporator.
4.6.3.1 The heat input shall be adjusted to maintain an average box
temperature not less than 25.0 [deg]F above the test enclosure
temperature.
4.6.3.2 The average dry-bulb temperature inside the calibrated box
shall not vary more than 1.0 [deg]F over the course of the calibration
test.
4.6.3.3 A calibration test shall be the average of eleven
consecutive hourly readings when the box has reached a steady-state
temperature condition.
4.6.3.4 The box temperature shall be the average of all readings
after a steady-state temperature condition has been reached.
4.6.3.5 The calibrated box has reached a steady-state temperature
condition when:
[[Page 81396]]
4.6.3.5.1 The average box temperature is not less than 25 [deg]F
above the test enclosure temperature.
4.6.3.5.2 Temperature variations do not exceed 5.0 [deg]F between
temperature-measuring stations.
4.6.3.5.3 Temperatures do not vary by more than 2 [deg]F at any one
temperature-measuring station.
4.6.4 Data to be Measured and Recorded. Refer to Table C2 in
section C7.2 of AHRI 1250-2020 for the required data that need to
measured and recorded.
4.6.5 Refrigeration Capacity Calculation.
4.6.5.1 The heat leakage coefficient of the calibrated box is
calculated by
[GRAPHIC] [TIFF OMITTED] TN22NO23.262
4.6.5.2 For each Dry Rating Condition, calculate the Net Capacity:
qss = Kcb (Ten-Tcb) + 3.412 x Ec
(3) Representations. RSG may not make representations about the
efficiency of a basic model listed in paragraph (1) of this Order for
compliance, marketing, or other purposes unless that basic model has
been tested in accordance with the provisions set forth in this
alternate test procedure and such representations fairly disclose the
results of such testing.
(4) This Order shall remain in effect until the date upon which use
of appendix C1 is required to demonstrate compliance with any amended
energy conservation standards based on the test procedure in appendix
C1.
(5) This Order is issued on the condition that the statements and
representations provided by RSG are valid. If RSG makes any
modifications to the controls or configurations of any basic model
subject to this Order, such modifications will render the waiver
invalid with respect to that basic model, and RSG will either be
required to use the current Federal test method or submit a new
application for a test procedure waiver. DOE may rescind or modify this
waiver at any time if it determines the factual basis underlying the
petition for the waiver is incorrect, upon a determination that the
results from the alternate test procedure are unrepresentative of a
basic model's true energy consumption characteristics, or for other
appropriate reasons. 10 CFR 431.401(k)(1). Likewise, RSG may request
that DOE rescind or modify the waiver if RSG discovers an error in the
information provided to DOE as part of its petition, determines that
the waiver is no longer needed, or for other appropriate reasons. 10
CFR 431.401(k)(2).
(6) Issuance of this Order does not release RSG from the applicable
requirements set forth at 10 CFR part 429.
DOE makes decisions on waivers and interim waivers for only those
basic models specifically set out in the petition, not future models
that may be manufactured by the petitioner. RSG may submit a new or
amended petition for waiver and request for grant of interim waiver, as
appropriate, for additional basic models of single-packaged dedicated
systems with multiple refrigeration circuits. Alternatively, if
appropriate, RSG may request that DOE extend the scope of a waiver or
an interim waiver to include additional basic models employing the same
technology as the basic models set forth in the original petition
consistent with 10 CFR 431.401(g).
Signing Authority
This document of the Department of Energy was signed on November
17, 2023, by Jeffrey Marootian, Principal Deputy Assistant Secretary
for Energy Efficiency and Renewable, pursuant to delegated authority
from the Secretary of Energy. That document with the original signature
and date is maintained by DOE. For administrative purposes only, and in
compliance with requirements of the Office of the Federal Register, the
undersigned DOE Federal Register Liaison Officer has been authorized to
sign and submit the document in electronic format for publication, as
an official document of the Department of Energy. This administrative
process in no way alters the legal effect of this document upon
publication in the Federal Register.
Signed in Washington, DC, on November 17, 2023.
Treena V. Garrett,
Federal Register Liaison Officer, U.S. Department of Energy.
[FR Doc. 2023-25873 Filed 11-21-23; 8:45 am]
BILLING CODE 6450-01-P
</pre><script data-cfasync="false" src="/cdn-cgi/scripts/5c5dd728/cloudflare-static/email-decode.min.js"></script></body>
</html>This is legal information, not legal advice. Laws vary by jurisdiction and change frequently. Always verify current law with official sources and consult a licensed attorney in your jurisdiction for advice on your specific situation.