Proposed Rule2022-17075

Energy Conservation Program: Test Procedure for Water-Source Heat Pumps

Primary source

Metadata and text below are from the Federal Register, a public-domain U.S. government work. Always verify the official published version before relying on it for any legal matter.

Published
August 30, 2022

Issuing agencies

Energy Department

Abstract

The U.S. Department of Energy ("DOE") proposes to amend its test procedures for water-source heat pumps, with the main changes being ones to expand the scope of applicability of the test procedure, reference different industry standards than currently referenced, change to a seasonal cooling efficiency metric, and change the test conditions used for the heating metric. DOE has tentatively determined that the amended test procedure would produce results that are more representative of an average use cycle and more consistent with current industry practice without being unduly burdensome to conduct. DOE seeks comment from interested parties on this proposal.

Full Text

<html>
<head>
<title>Federal Register, Volume 87 Issue 167 (Tuesday, August 30, 2022)</title>
</head>
<body><pre>
[Federal Register Volume 87, Number 167 (Tuesday, August 30, 2022)]
[Proposed Rules]
[Pages 53302-53359]
From the Federal Register Online via the Government Publishing Office [<a href="http://www.gpo.gov">www.gpo.gov</a>]
[FR Doc No: 2022-17075]



[[Page 53301]]

Vol. 87

Tuesday,

No. 167

August 30, 2022

Part IV





 Department of Energy





-----------------------------------------------------------------------





10 CFR Parts 429 and 431





Energy Conservation Program: Test Procedure for Water-Source Heat 
Pumps; Proposed Rule

Federal Register / Vol. 87, No. 167 / Tuesday, August 30, 2022 / 
Proposed Rules

[[Page 53302]]


-----------------------------------------------------------------------

DEPARTMENT OF ENERGY

10 CFR Parts 429 and 431

[EERE-2017-BT-TP-0029]
RIN 1904-AE05


Energy Conservation Program: Test Procedure for Water-Source Heat 
Pumps

AGENCY: Office of Energy Efficiency and Renewable Energy, Department of 
Energy.

ACTION: Notice of proposed rulemaking and request for comment.

-----------------------------------------------------------------------

SUMMARY: The U.S. Department of Energy (``DOE'') proposes to amend its 
test procedures for water-source heat pumps, with the main changes 
being ones to expand the scope of applicability of the test procedure, 
reference different industry standards than currently referenced, 
change to a seasonal cooling efficiency metric, and change the test 
conditions used for the heating metric. DOE has tentatively determined 
that the amended test procedure would produce results that are more 
representative of an average use cycle and more consistent with current 
industry practice without being unduly burdensome to conduct. DOE seeks 
comment from interested parties on this proposal.

DATES: 
    Comments: DOE will accept comments, data, and information regarding 
this proposal no later than October 31, 2022. See section V, ``Public 
Participation,'' for details.
    Public Meeting: DOE will hold a public meeting via webinar on 
Wednesday, September 14, 2022, from 1:00 p.m. to 3:00 p.m. See section 
V, ``Public Participation,'' for webinar registration information, 
participant instructions, and information about the capabilities 
available to webinar participants.

ADDRESSES: Interested persons are encouraged to submit comments using 
the Federal eRulemaking Portal at <a href="http://www.regulations.gov">www.regulations.gov</a>, under docket 
number EERE-2017-BT-TP-0029. Follow the instructions for submitting 
comments. Alternatively, interested persons may submit comments, 
identified by docket number EERE-2017-BT-TP-0029 and/or RIN 1904-AE05, 
by any of the following methods:
    Email: <a href="/cdn-cgi/l/email-protection#0453574c543634353350543434363d4461612a606b612a636b72"><span class="__cf_email__" data-cfemail="0156524951333130365551313133384164642f656e642f666e77">[email&#160;protected]</span></a>. Include the docket number EERE-
2017-BT-TP-0029 and/or RIN 1904-AE05 in the subject line of the 
message.
    Postal Mail: Appliance and Equipment Standards Program, U.S. 
Department of Energy, Building Technologies Office, Mailstop EE-5B, 
1000 Independence Avenue SW, Washington, DC 20585-0121. If possible, 
please submit all items on a compact disc (``CD''), in which case it is 
not necessary to include printed copies.
    Hand Delivery/Courier: Appliance and Equipment Standards Program, 
U.S. Department of Energy, Building Technologies Office, 950 L'Enfant 
Plaza SW, 6th Floor, Washington, DC 20024. Telephone: (202) 287-1445. 
If possible, please submit all items on a CD, in which case it is not 
necessary to include printed copies.
    No telefacsimiles (``faxes'') will be accepted. For detailed 
instructions on submitting comments and additional information on this 
process, see section V of this document (Public Participation).
    Docket: The docket, which includes Federal Register notices, public 
meeting/webinar attendee lists and transcripts, comments, and other 
supporting documents/materials, is available for review at 
<a href="http://www.regulations.gov">www.regulations.gov</a>. All documents in the docket are listed in the 
<a href="http://www.regulations.gov">www.regulations.gov</a> index. However, some documents listed in the index, 
such as those containing information that is exempt from public 
disclosure, may not be publicly available.
    The docket web page can be found at <a href="http://www.regulations.gov/docket?D=EERE-2017-BT-TP-0029">www.regulations.gov/docket?D=EERE-2017-BT-TP-0029</a>. The docket web page contains 
instructions on how to access all documents, including public comments, 
in the docket. See section V (Public Participation) for information on 
how to submit comments through <a href="http://www.regulations.gov">www.regulations.gov</a>.

FOR FURTHER INFORMATION CONTACT: 
    Ms. Catherine Rivest, U.S. Department of Energy, Office of Energy 
Efficiency and Renewable Energy, Building Technologies Office, EE-5B, 
1000 Independence Avenue SW, Washington, DC 20585-0121. Telephone: 
(202) 586-7335. Email: <a href="/cdn-cgi/l/email-protection#aceddcdcc0c5cdc2cfc9ffd8cdc2c8cddec8dffdd9c9dfd8c5c3c2dfecc9c982c8c3c982cbc3da"><span class="__cf_email__" data-cfemail="cd8cbdbda1a4aca3aea89eb9aca3a9acbfa9be9cb8a8beb9a4a2a3be8da8a8e3a9a2a8e3aaa2bb">[email&#160;protected]</span></a>.
    Mr. Eric Stas, U.S. Department of Energy, Office of the General 
Counsel, GC-33, 1000 Independence Avenue SW, Washington, DC 20585-0121. 
Telephone: (202) 586-5827. Email: <a href="/cdn-cgi/l/email-protection#cd88bfa4aee39eb9acbe8da5bce3a9a2a8e3aaa2bb"><span class="__cf_email__" data-cfemail="9dd8eff4feb3cee9fceeddf5ecb3f9f2f8b3faf2eb">[email&#160;protected]</span></a>.
    For further information on how to submit a comment, review other 
public comments and the docket, or participate in the public meeting 
webinar, contact the Appliance and Equipment Standards Program staff at 
(202) 287-1445 or by email: <a href="/cdn-cgi/l/email-protection#531223233f3a323d30360027323d373221372002263620273a3c3d201336367d373c367d343c25"><span class="__cf_email__" data-cfemail="7c3d0c0c10151d121f192f081d12181d0e180f2d09190f081513120f3c191952181319521b130a">[email&#160;protected]</span></a>.

SUPPLEMENTARY INFORMATION: DOE proposes to incorporate by reference 
already-approved industry standards, an update to one of those 
standards, and a standard not previously-approved.
    ANSI/ASHRAE Standard 37-2009, ``Methods of Testing for Rating 
Electrically Driven Unitary Air-Conditioning and Heat Pump Equipment,'' 
including errata sheet issued March 27, 2019, ASHRAE approved June 24, 
2009.
    Copies of the American Society of Heating, Refrigerating, and Air-
Conditioning Engineers (``ASHRAE'') ANSI/ASHRAE Standard 37-2009 are 
available from the American National Standards Institute (``ANSI''), 25 
W. 43rd Street, 4th Floor, New York, NY 10036, (212) 642-4900, or 
online at: <a href="https://webstore.ansi.org/">https://webstore.ansi.org/</a>.
    ASHRAE errata sheet to ANSI/ASHRAE Standard 37-2009--Methods of 
Testing for Rating Electrically Driven Unitary Air-Conditioning and 
Heat Pump Equipment, ANSI/ASHRAE Approved March 27, 2019.
    Copies of ASHRAE errata sheet to ANSI/ASHRAE Standard 37-2009 are 
available from ASHRAE, 180 Technology Parkway NW, Peachtree Corners, GA 
30092, (404)-636-8400, or online at <a href="https://ashrae.org/">https://ashrae.org/</a>.
    ISO Standard 13256-1:1998, ``Water-source heat pumps--Testing and 
rating for performance--Part 1: Water-to-air and brine-to-air heat 
pumps,'' ISO approved 1998.
    Copies of ISO Standard 13256-1:1998 can be obtained from the 
International Organization for Standardization (``ISO''), Chemin de 
Blandonnet 8 CP 401, 1214 Vernier, Geneva, Switzerland, +41 22 749 01 
11, or online at: <a href="https://webstore.ansi.org/">https://webstore.ansi.org/</a>.
    AHRI Standard 340/360-2022 (I-P), ``2022 Standard for Performance 
Rating of Commercial and Industrial Unitary Air-conditioning and Heat 
Pump Equipment,'' AHRI-approved January 26, 2022.
    Copies of AHRI Standard 340/360-2022 (I-P) can be obtained from the 
Air-Conditioning, Heating, and Refrigeration Institute (``AHRI''), 2311 
Wilson Blvd., Suite 400, Arlington, VA 22201, (703) 524-8800, or online 
at: <a href="http://www.ahrinet.org/search-standards.aspx">www.ahrinet.org/search-standards.aspx</a>.
    See section IV.M of this document for further discussion of these 
standards.

Table of Contents

I. Authority and Background
    A. Authority
    B. Background
II. Synopsis of the Notice of Proposed Rulemaking
III. Discussion
    A. Scope of Applicability

[[Page 53303]]

    B. Definition
    C. Proposed Organization of the WSHP Test Procedure
    D. Industry Standards
    1. Applicable Industry Test Procedures
    a. ISO Standard 13256-1
    b. AHRI 340/360-2022 and ASHRAE 37-2009
    c. AHRI 600
    2. Comments Received on Industry Standards and DOE Responses
    3. Proposal for DOE Test Procedure
    E. Efficiency Metrics
    1. IEER
    a. General Discussion
    b. Determination of IEER Via Interpolation and Extrapolation
    2. COP
    a. General Discussion
    b. Determination of COP Via Interpolation
    3. Entering Air Conditions
    4. Operating Modes Other Than Mechanical Cooling and Heating
    5. Dynamic Load-Based Test Procedure
    F. Test Method
    1. Airflow and External Static Pressure
    a. Fan Power Adjustment and Required Air External Static 
Pressure
    b. Setting Airflow and ESP
    i. Ducted Units With Discrete-Step Fans
    ii. Non-Ducted Units
    2. Capacity Measurement
    a. Primary and Secondary Methods
    b. Compressor Heat
    3. Cyclic Degradation
    4. Pump Power Adjustment and Liquid External Static Pressure
    5. Test Liquid and Specific Heat Capacity
    6. Liquid Flow Rate
    a. Full-Load Cooling Tests
    b. Part-Load Cooling Tests
    c. Heating Tests
    d. Condition Tolerance
    7. Refrigerant Line Losses
    8. Airflow Measurement
    9. Air Condition Measurements
    10. Duct Losses
    11. Refrigerant Charging
    12. Voltage
    G. Configuration of Unit Under Test
    1. Specific Components
    2. Non-Standard Indoor Fan Motors
    H. Represented Values and Enforcement
    1. Multiple Refrigerants
    2. Cooling Capacity
    3. Enforcement of IEER
    I. Test Procedure Costs and Impact
    J. Compliance Date
IV. Procedural Issues and Regulatory Review
    A. Review Under Executive Orders 12866 and 13563
    B. Review Under the Regulatory Flexibility Act
    C. Review Under the Paperwork Reduction Act of 1995
    D. Review Under the National Environmental Policy Act of 1969
    E. Review Under Executive Order 13132
    F. Review Under Executive Order 12988
    G. Review Under the Unfunded Mandates Reform Act of 1995
    H. Review Under the Treasury and General Government 
Appropriations Act, 1999
    I. Review Under Executive Order 12630
    J. Review Under Treasury and General Government Appropriations 
Act, 2001
    K. Review Under Executive Order 13211
    L. Review Under Section 32 of the Federal Energy Administration 
Act of 1974
    M. Description of Materials Incorporated by Reference
V. Public Participation
    A. Participation in the Public Meeting Webinar
    B. Procedure for Submitting Prepared General Statements for 
Distribution
    C. Conduct of the Public Meeting Webinar
    D. Submission of Comments
    E. Issues on Which DOE Seeks Comment
VI. Approval of the Office of the Secretary

I. Authority and Background

    Water-source heat pumps (``WSHPs'') are a category of small, large, 
and very large commercial package air-conditioning and heating 
equipment,\1\ which are included in the list of ``covered equipment'' 
for which DOE is authorized to establish and amend energy conservation 
standards and test procedures. (42 U.S.C. 6311(1)(B)-(D)) DOE's energy 
conservation standards and test procedures for WSHPs are currently 
prescribed in title 10 of the Code of Federal Regulations (``CFR'') at 
10 CFR 431.97 and 10 CFR 431.96, respectively. The following sections 
discuss DOE's authority to establish and amend test procedures for 
WSHPs, as well as relevant background information regarding DOE's 
consideration of test procedures for this equipment.
---------------------------------------------------------------------------

    \1\ The Energy Policy and Conservation Act, as amended 
(``EPCA'') defines ``commercial package air conditioning and heating 
equipment'' as air-cooled, water-cooled, evaporatively-cooled, or 
water-source (not including ground-water-source) electrically 
operated unitary central air conditioners and central air 
conditioning heat pumps for commercial application. (42 U.S.C. 
6311(8)(A)) EPCA further defines ``small commercial package air 
conditioning and heating equipment'' as commercial package air 
conditioning and heating equipment that is rated below 135,000 Btu 
per hour (cooling capacity); ``large commercial package air 
conditioning and heating equipment'' as commercial package air 
conditioning and heating equipment that is rated at or above 135,000 
Btu per hour and below 240,000 Btu per hour (cooling capacity); and 
``very large commercial package air conditioning and heating 
equipment'' as commercial package air conditioning and heating 
equipment that is rated at or above 240,000 Btu per hour and below 
760,000 Btu per hour (cooling capacity). (42 U.S.C. 6311(8)(B)-(D))
---------------------------------------------------------------------------

A. Authority

    The Energy Policy and Conservation Act, as amended (``EPCA''),\2\ 
Public Law 94-163 (42 U.S.C. 6291-6317, as codified), among other 
things, authorizes DOE to regulate the energy efficiency of a number of 
consumer products and certain industrial equipment. Title III, Part C 
\3\ of EPCA, added by Public Law 95-619, Title IV, section 441(a), 
established the Energy Conservation Program for Certain Industrial 
Equipment, which sets forth a variety of provisions designed to improve 
energy efficiency. This equipment includes small, large, and very large 
commercial package air-conditioning and heating equipment, including 
WSHPs. (42 U.S.C. 6311(1)(B)-(D))
---------------------------------------------------------------------------

    \2\ All references to EPCA in this document refer to the statute 
as amended through the Energy Act of 2020, Public Law 116-260 (Dec. 
27, 2020), which reflects the last statutory amendments that impact 
Parts A and A-1 of EPCA.
    \3\ For editorial reasons, upon codification in the U.S. Code, 
Part C was redesignated Part A-1.
---------------------------------------------------------------------------

    The energy conservation program under EPCA consists essentially of 
four parts: (1) testing; (2) labeling; (3) Federal energy conservation 
standards, and (4) certification and enforcement procedures. Relevant 
provisions of EPCA specifically include definitions (42 U.S.C. 6311), 
energy conservation standards (42 U.S.C. 6313), test procedures (42 
U.S.C. 6314), labeling provisions (42 U.S.C. 6315), and the authority 
to require information and reports from manufacturers (42 U.S.C. 6316; 
42 U.S.C. 6296).
    The Federal testing requirements consist of test procedures that 
manufacturers of covered equipment must use as the basis for: (1) 
certifying to DOE that their equipment complies with the applicable 
energy conservation standards adopted pursuant to EPCA (42 U.S.C. 
6316(b); 42 U.S.C. 6296), and (2) making representations about the 
efficiency of that equipment (42 U.S.C. 6314(d)). Similarly, DOE uses 
these test procedures to determine whether the equipment complies with 
relevant standards promulgated under EPCA.
    Federal energy efficiency requirements for covered equipment 
established under EPCA generally supersede State laws and regulations 
concerning energy conservation testing, labeling, and standards. (42 
U.S.C. 6316(a) and (b); 42 U.S.C. 6297) DOE may, however, grant waivers 
of Federal preemption for particular State laws or regulations, in 
accordance with the procedures and other provisions of EPCA. (42 U.S.C. 
6316(b)(2)(D))
    Under 42 U.S.C. 6314, EPCA sets forth the criteria and procedures 
DOE must follow when prescribing or amending test procedures for 
covered equipment. EPCA requires that any test procedures prescribed or 
amended under this section must be reasonably designed to produce test 
results which reflect energy efficiency, energy use, or estimated 
annual operating cost of covered equipment during a representative 
average use cycle and requires that test procedures not be unduly 
burdensome to conduct. (42 U.S.C. 6314(a)(2))

[[Page 53304]]

    With respect to WSHPs, EPCA requires that the test procedures shall 
be those generally accepted industry testing procedures or rating 
procedures developed or recognized by the Air-Conditioning, Heating, 
and Refrigeration Institute (``AHRI'') or by the American Society of 
Heating, Refrigerating and Air-Conditioning Engineers (``ASHRAE''), as 
referenced in ASHRAE Standard 90.1, ``Energy Standard for Buildings 
Except Low-Rise Residential Buildings'' (``ASHRAE Standard 90.1''). (42 
U.S.C. 6314(a)(4)(A)) Further, if such an industry test procedure is 
amended, DOE must amend its test procedure to be consistent with the 
amended industry test procedure, unless DOE determines, by rule 
published in the Federal Register and supported by clear and convincing 
evidence, that the amended test procedure would not produce test 
results that reflect the energy efficiency, energy use, and estimated 
operating costs of that equipment during a representative average use 
cycle or would be unduly burdensome to conduct. (42 U.S.C. 
6314(a)(4)(B))
    EPCA also requires that, at least once every 7 years, DOE evaluate 
test procedures for each type of covered equipment, including WSHPs, to 
determine whether amended test procedures would more accurately or 
fully comply with the requirements for the test procedures to not be 
unduly burdensome to conduct and be reasonably designed to produce test 
results that reflect energy efficiency, energy use, and estimated 
operating costs during a representative average use cycle. (42 U.S.C. 
6314(a)(1))
    In addition, if the Secretary determines that a test procedure 
amendment is warranted, DOE must publish proposed test procedures in 
the Federal Register and afford interested persons an opportunity (of 
not less than 45 days duration) to present oral and written data, 
views, and comments on the proposed test procedures. (42 U.S.C. 
6314(b)) If DOE determines that test procedure revisions are not 
appropriate, DOE must publish in the Federal Register its determination 
not to amend the test procedures. (42 U.S.C. 6314(a)(1)(A)(ii))
    In this notice of proposed rulemaking (``NOPR''), DOE is proposing 
amendments to the test procedures for WSHPs in satisfaction of the 7-
year-lookback obligations under EPCA. (42 U.S.C. 6314(a)(1))

B. Background

    DOE's existing test procedure for WSHPs is specified at 10 CFR 
431.96 (``Uniform test method for the measurement of energy efficiency 
of commercial air conditioners and heat pumps''). The Federal test 
procedure currently incorporates by reference International 
Organization for Standardization (``ISO'') Standard 13256-1 (1998), 
``Water-source heat pumps--Testing and rating for performance--Part 1: 
Water-to-air and brine-to-air heat pumps,'' (``ISO 13256-1:1998''). 
This is the test procedure specified by ASHRAE Standard 90.1 for water-
source heat pumps.
    DOE initially incorporated ISO 13256-1:1998 as the referenced test 
procedure for WSHPs on October 21, 2004 (69 FR 61962), and DOE last 
reviewed the test procedure for WSHPs as part of a final rule for 
commercial package air conditioners and heat pumps published in the 
Federal Register on May 16, 2012 (``May 2012 final rule''; 77 FR 
28928). In the May 2012 final rule, DOE retained the reference to ISO 
13256-1:1998 but adopted additional provisions for equipment set-up at 
10 CFR 431.96(e), which provide specifications for addressing key 
information typically found in the installation and operation manuals. 
Id at 77 FR 28991.
    On June 22, 2018, DOE published a request for information (``RFI'') 
in the Federal Register to collect information and data to consider 
amendments to DOE's test procedures for WSHPs. 83 FR 29048 (``June 2018 
RFI'').\4\ As part of the June 2018 RFI, DOE identified and requested 
comment on several issues associated with the currently applicable 
Federal test procedures, in particular concerning methods that are 
adopted through incorporation by reference of the applicable industry 
standard; efficiency metrics and calculations; additional 
specifications for the test methods; and any additional topics that may 
inform DOE's decisions in a future test procedure rulemaking, including 
methods to reduce regulatory burden while ensuring the test procedure's 
accuracy. Id.
---------------------------------------------------------------------------

    \4\ An extension of the comment period for the June 2018 RFI was 
published in the Federal Register on July 9, 2018. 83 FR 31704.
---------------------------------------------------------------------------

    DOE received comments in response to the June 2018 RFI from the 
interested parties listed in Table I-1.

  Table I-1--List of Commenters With Written Submissions in Response to
                            the June 2018 RFI
------------------------------------------------------------------------
                                Reference in this
         Commenter(s)                  NOPR            Commenter type
------------------------------------------------------------------------
Air-Conditioning, Heating, and  AHRI.............  IR.
 Refrigeration Institute.
Appliance Standards Awareness   Joint Advocates..  EA.
 Project, American Council for
 an Energy-Efficient Economy,
 Natural Resources Defense
 Council.
Northwest Energy Efficiency     NEEA.............  EA.
 Alliance.
Pacific Gas and Electric        CA IOUs..........  U.
 Company, San Diego Gas and
 Electric, and Southern
 California Edison;
 collectively referred to as
 the California Investor-Owned
 Utilities.
Trane Technologies............  Trane............  M.
WaterFurnace International....  WaterFurnace.....  M.
------------------------------------------------------------------------
EA: Efficiency/Environmental Advocate; IR: Industry Representative; M:
  Manufacturer; U: Utility.

    A parenthetical reference at the end of a comment quotation or 
paraphrase provides the location of the item in the public record.\5\
---------------------------------------------------------------------------

    \5\ The parenthetical reference provides a reference for 
information located in the docket of DOE's rulemaking to develop 
test procedures for WSHPs. (Docket No. EERE-2017-BT-TP-0029, which 
is maintained at <a href="http://www.regulations.gov">www.regulations.gov</a>). The references are arranged 
as follows: (commenter name, comment docket ID number, page of that 
document).
---------------------------------------------------------------------------

    In May 2021, ISO published an updated version of Standard 13256-1, 
ISO Standard 13256-1 (2021), ``Water-source heat pumps--Testing and 
rating for performance--Part 1: Water-to-air and brine-to-air heat 
pumps,'' (``ISO 13256-1:2021''). ISO 13256-1:2021 is discussed further 
in section III.D of this NOPR.

II. Synopsis of the Notice of Proposed Rulemaking

    In this NOPR, DOE is proposing to amend the Federal test procedures 
for WSHPs as follows: (1) expand the scope of the test procedure to 
include WSHPs

[[Page 53305]]

with capacities between 135,000 and 760,000 British thermal units per 
hour (``Btu/h''); (2) incorporate by reference AHRI Standard 340/360-
2022 (I-P), ``2022 Standard for Performance Rating of Commercial and 
Industrial Unitary Air-conditioning and Heat Pump Equipment'' (``AHRI 
340/360-2022''), and ANSI/ASHRAE Standard 37-2009, ``Methods of Testing 
for Rating Electrically Driven Unitary Air-Conditioning and Heat Pump 
Equipment'' (``ANSI/ASHRAE 37-2009'') as the applicable test procedures 
for WSHPs, instead of the currently referenced industry test procedure 
ISO 13256-1:1998; (3) establish provisions for a new cooling efficiency 
metric, integrated energy efficiency ratio (``IEER''), for WSHPs and 
provide an alternative method of calculating IEER using interpolation 
from test conditions commonly used for WSHPs; (4) modify the test 
conditions for measuring the heating coefficient of performance 
(``COP'') and provide an alternative method of calculating COP using 
interpolation from test conditions commonly used for WSHPs; (5) include 
additional specification of setting airflow and external static 
pressure (``ESP'') for non-ducted units and ducted units with discrete-
step fans; (6) specify liquid ESP requirements for units with integral 
pumps and include a method to account for total pumping effect for 
units without integral pumps; (7) specify components that must be 
present for testing; and (8) amend certain provisions related to 
representations and enforcement in 10 CFR part 429.
    DOE proposes to implement these changes by adding new appendices C 
and C1 to subpart F of part 431, with both to be titled ``Uniform Test 
Method for Measuring the Energy Consumption of Water-Source Heat 
Pumps,'' (``appendix C'' and ``appendix C1,'' respectively). The 
current DOE test procedure for WSHPs would be relocated to appendix C 
without change, and the new test procedure adopting AHRI 340/360-2022 
and ANSI/ASHRAE 37-2009 and any other amendments would be set forth in 
proposed appendix C1 for determining IEER. As discussed elsewhere in 
this NOPR, DOE has tentatively concluded, supported by clear and 
convincing evidence, that the proposed amended test procedure in 
appendix C1 (relying on AHRI 340/360-2022 and ASHRAE 37-2009) would 
provide more representative results and more fully comply with the 
requirements of 42 U.S.C. 6314(a)(2) than testing with the current 
Federal test procedure (relying on ISO 13256-1:1998). However, use of 
proposed appendix C1 would not be required until such time as 
compliance is required with amended energy conservation standards for 
WSHPs based on IEER, should DOE adopt such standards, although a 
manufacturer would need to make any voluntary early representations of 
IEER in accordance with appendix C1.
    DOE's proposed actions are summarized in Table II-1 and addressed 
in detail in section III of this document.

 Table II-1--Summary of Changes in the Proposed Test Procedure Relative
                 to the Current Test Procedure for WSHPs
------------------------------------------------------------------------
                                     Proposed test
  Current DOE test procedure     procedure in Appendix     Attribution
                                          C1
------------------------------------------------------------------------
Scope is limited to units with  Expands the scope of    Harmonize with
 cooling capacity less than      the test procedure to   scope of test
 135,000 Btu/h.                  additionally include    procedure for
                                 units with cooling      water-cooled
                                 capacity greater than   commercial
                                 or equal to 135,000     unitary air
                                 Btu/h and less than     conditioners.
                                 760,000 Btu/h.
Incorporates by reference ISO   Incorporates by         Improve
 13256-1:1998.                   reference AHRI 340/     representativen
                                 360-2022 and ANSI/      ess of test
                                 ASHRAE 37-2009.         procedure.
Includes provisions for         Includes provisions     Improve
 determining EER metric.         for determining IEER,   representativen
                                 and specifies an        ess of test
                                 alternative method of   procedure.
                                 calculating IEER
                                 using interpolation
                                 and extrapolation
                                 from results of
                                 testing at ISO 13256-
                                 1:1998 temperatures.
Specifies test condition of 68  Changes the test        Improve
 [deg]F for measuring COP.       condition for COP to    representativen
                                 55 [deg]F and           ess of test
                                 provides an             procedure.
                                 alternative method of
                                 calculating COP using
                                 interpolation from
                                 results of testing at
                                 ISO 13256-1:1998
                                 temperatures.
Does not include specification  Includes additional     Improve
 of setting airflow and ESP      specification of        representativen
 for non-ducted units or         setting airflow and     ess of test
 ducted units with discrete-     ESP for non-ducted      procedure.
 step fans.                      units and for ducted
                                 units with discrete-
                                 step fans.
Allows for testing at any       Specifies liquid ESP    Improve
 liquid ESP with an adjustment   requirements for        representativen
 to include the pump power to    units with integral     ess of test
 overcome liquid internal        pumps, and includes a   procedure.
 static pressure.                method for accounting
                                 for the total pumping
                                 effect for units
                                 without integral
                                 pumps.
Does not include WSHP-specific  Includes provisions in  Establish WSHP-
 provisions for determination    10 CFR 429.43           specific
 of represented values in 10     specific to WSHPs to    provisions for
 CFR 429.43.                     prevent cooling         determination
                                 capacity over-rating    of represented
                                 and to determine        values.
                                 represented values
                                 for models with
                                 specific components.
Does not include WSHP-specific  Adopts product-         Establish
 enforcement provisions in 10    specific enforcement    provisions for
 CFR 429.134.                    provisions for WSHPs    DOE testing of
                                 regarding               WSHPs.
                                 verification of
                                 cooling capacity,
                                 testing of systems
                                 with specific
                                 components, and DOE
                                 IEER testing.
------------------------------------------------------------------------

    DOE has tentatively determined that the proposed amendments 
described in section III of this NOPR regarding the establishment of 
appendix C would not alter the measured efficiency of WSHPs or require 
retesting solely as a result of DOE's adoption of the proposed 
amendments to the test procedure, if made final. DOE has tentatively 
determined that the proposed test procedure amendments in appendix C1 
would, if adopted, alter the measured efficiency of WSHPs. DOE has 
tentatively determined that the proposed amendments would increase the 
cost of testing relative to the current Federal test procedure. Use of 
the proposed appendix C1 and the proposed

[[Page 53306]]

amendments to the representation requirements in 10 CFR 429.43 would 
not be required until the compliance date of amended standards 
denominated in terms of IEER, although manufacturers would need to use 
appendix C1 if they choose to make voluntary representations of IEER 
prior to the compliance date. DOE's proposed actions are discussed in 
further detail in section III of this NOPR.

III. Discussion

    In the following sections, DOE proposes certain amendments to the 
Federal test procedure for WSHPs. For each proposed amendment, DOE 
provides relevant background information, explains why the amendment 
merits consideration, discusses any relevant public comments, and 
proposes a potential approach.

A. Scope of Applicability

    This rulemaking applies to WSHPs, which are a category of small, 
large, and very large commercial package air-conditioning and heating 
equipment. (See 42 U.S.C. 6311(1)(B)-(D)) In its regulations, DOE 
defines WSHP as ``a single-phase or three-phase reverse-cycle heat pump 
that uses a circulating water loop as the heat source for heating and 
as the heat sink for cooling. The main components are a compressor, 
refrigerant-to-water heat exchanger, refrigerant-to-air heat exchanger, 
refrigerant expansion devices, refrigerant reversing valve, and indoor 
fan. Such equipment includes, but is not limited to, water-to-air 
water-loop heat pumps.'' 10 CFR 431.92.
    The current Federal test procedure and energy conservation 
standards apply to WSHPs with a rated cooling capacity below 135,000 
Btu/h. 10 CFR 431.96, Table 1 and 431.97, Table 3. However, DOE has 
identified WSHPs on the market with cooling capacities equal to or 
greater than 135,000 Btu/h.\6\ In the June 2018 RFI, DOE sought data 
and information on the size of the market for WSHPs with a cooling 
capacity over 135,000 Btu/h and any potential limitations to testing 
such units. 83 FR 29048, 29050 (June 22, 2018).
---------------------------------------------------------------------------

    \6\ For simplicity in this NOPR, DOE refers to cooling capacity 
equal to or greater than 135,000 Btu/h as ``over 135,000'' Btu/h.
---------------------------------------------------------------------------

    The Joint Advocates encouraged DOE to include WSHPs over 135,000 
Btu/h within the scope of the test procedure. (Joint Advocates, No. 10 
at p. 1)
    AHRI, Trane, and WaterFurnace stated that the market for WSHPs over 
135,000 Btu/h is very small--around 0.7 percent of the market--and that 
finding a lab to test these units would be difficult for the reasons 
that follow. AHRI commented that manufacturers have limitations on the 
size of units that can be tested in their own labs, so the proposed 
expanded scope of the WSHP test procedure to encompass units with 
higher rated capacities would necessitate the use of third-party labs, 
resulting in additional costs for testing. AHRI and WaterFurnace 
further commented that WSHPs in this capacity range are highly 
customized for their application and asserted that testing them would 
incur significant costs. Trane added that no independent test labs are 
currently certified to test WSHPs over 135,000 Btu/h. (Trane, No. 8 at 
p. 2; AHRI, No. 12 at pp. 3-4; WaterFurnace, No. 7 at pp. 2-3)
    Furthermore, AHRI and WaterFurnace argued that units with capacity 
over 135,000 Btu/h are out of the scope of ISO 13256-1:1998. (AHRI, No. 
12 at p. 4; WaterFurnace, No. 7 at p.2) WaterFurnace also commented 
that AHRI certification costs would be extreme for such a small market 
due to the need to test three larger and more expensive units for 
sampling selection of each basic model group, and the likely need to 
scrap the units after testing due the significant extent of 
customization of larger units. (WaterFurnace, No. 7 at pp. 2-3)
    In response, DOE notes that contrary to the assertions of AHRI and 
WaterFurnace, no capacity limitation is expressed in ISO 13256-1:1998--
the industry standard currently incorporated by reference--or ISO 
13256-1:2021. Once again, DOE has identified numerous model lines of 
WSHPs with cooling capacity over 135,000 Btu/h from a wide variety of 
manufacturers. The manufacturer literature for all identified model 
lines includes efficiency representations that are explicitly based on 
ISO 13256-1:1998.
    Additionally, DOE is aware of several independent test labs that 
have the capability to test WSHPs with cooling capacity over 135,000 
Btu/h. DOE conducted investigative testing on multiple WSHP models with 
cooling capacity over 135,000 Btu/h at one such independent test lab 
and did not encounter any difficulties specific to units in this 
capacity range.
    Further, AHRI 340/360-2022 and ANSI/ASHRAE 37-2009 include 
provisions for testing units with capacities over 135,000 Btu/h. Both 
ASHRAE Standard 90.1 and DOE regulations cover other categories of 
commercial air conditioning and heating equipment, including water-
cooled commercial unitary air conditioners (``WCUACs''), with cooling 
capacity up to 760,000 Btu/h. DOE has tentatively determined that 
testing WSHPs with cooling capacity over 135,000 Btu/h would be of 
comparable burden to testing other commercial air conditioning and 
heating equipment of similar capacity.
    Regarding WaterFurnace's comment that an expansion of test 
procedure scope would mean that many large units would need to be 
tested, DOE notes that expanding the scope of the test procedure would 
not necessitate certification unless DOE were to establish standards 
for such equipment. Until such a time, an expansion of scope for the 
test procedure would simplify require that if manufacturers choose to 
make optional representations of WSHPs with cooling capacity over 
135,000 Btu/h, that such optional representations be made in accordance 
with the DOE test procedure. Further, representations for WSHPs can be 
made either based on testing (in accordance with 10 CFR 429.43(a)(1)) 
or based on alternative efficiency determination methods (``AEDMs'') 
(in accordance with 10 CFR 429.43(a)(2)). An AEDM is a computer 
modeling or mathematical tool that predicts the performance of non-
tested basic models. These computer modeling and mathematical tools, 
when properly developed, can provide a means to predict the energy 
usage or efficiency characteristics of a basic model of a given covered 
product or equipment and reduce the burden and cost associated with 
testing. Whereas DOE requires at least two units to be tested per basic 
model when represented values are determined through testing, DOE 
requires each AEDM to be validated by tests of only two WSHP basic 
models of any capacity (in accordance with 10 CFR 429.70(c)(2)). 
Therefore, an expansion of scope for the DOE test procedure would not 
necessitate the testing of many large units.
    For these reasons, DOE has tentatively concluded that testing units 
with cooling capacity over 135,000 Btu/h is feasible. Moreover, based 
on the presence on the market of units over 135,000 Btu/h with 
efficiency ratings and the identification of laboratories capable of 
testing such units, DOE has tentatively determined that such testing 
would not be unduly burdensome. Additionally, expanding the scope of 
DOE's test procedure for WSHPs to include equipment with cooling 
capacity between 135,000 Btu/h and 760,000 Btu/h would ensure that 
representations for all WSHPs are made using the same test procedure 
and that ratings for equipment in this cooling

[[Page 53307]]

capacity range are appropriately representative. Therefore, DOE 
proposes in this NOPR to expand the scope of applicability of the test 
procedure to include WSHPs with a cooling capacity between 135,000 and 
760,000 Btu/h. Specifically, DOE proposes to update table 1 to 10 CFR 
431.96 to include WSHPs with cooling capacity greater than or equal to 
135,000 Btu/h and less than 240,000 Btu/h under Large Commercial 
Package Air-Conditioning and Heating Equipment; and to include WSHPs 
with cooling capacity greater than or equal to 240,000 Btu/h and less 
than 760,000 Btu/h under Very Large Commercial Package Air-Conditioning 
and Heating Equipment. For both capacity ranges, the specified test 
procedure would be the proposed appendix C, and DOE proposes that any 
voluntary representations with respect to the energy use or energy 
efficiency must be made in accordance with appendix C starting 360 days 
after a test procedure final rule is published in the Federal Register. 
DOE also proposes that, starting 360 days after a test procedure final 
rule is published in the Federal Register, any voluntary 
representations of IEER must be made in accordance with the proposed 
appendix C1.
    DOE does not currently specify energy conservation standards for 
WSHPs with cooling capacity over 135,000 Btu/h. DOE would consider any 
future standards applicable to WSHPs over 135,000 Btu/h in a separate 
energy conservation standards rulemaking. Manufacturers of WSHPs with 
cooling capacity over 135,000 Btu/h would not be required to test WSHPs 
with a cooling capacity over 135,000 Btu/h until such time as 
compliance with standards for this equipment were required, should DOE 
adopt such standards, although any voluntary EER representations would 
need to be based on the test procedure in appendix C, and any voluntary 
IEER representations would need to be based on the test procedure in 
appendix C1 starting 360 days after the publication of a test procedure 
final rule. Additionally, if DOE were to adopt standards for WSHPs in 
terms of IEER, after the compliance date for those standards, any 
representations for WSHPs would be required to be made according to 
appendix C1.
    Issue 1: DOE requests comments on the proposed expansion of the 
scope of applicability of the Federal test procedure to include WSHPs 
with cooling capacity between 135,000 and 760,000 Btu/h.

B. Definition

    As discussed, WSHPs are a category of commercial package air-
conditioning and heating equipment. The current definition for ``water-
source heat pump'' does not explicitly state that it is ``commercial 
package air-conditioning and heating equipment.'' This is inconsistent 
with the definitions of most other categories of commercial package 
air-conditioning and heating equipment (e.g., computer room air 
conditioner, single package vertical air conditioner, variable 
refrigerant flow multi-split air conditioner). 10 CFR 431.92. To 
provide consistency with other definitions of specific categories of 
commercial package air-conditioning and heating equipment, DOE proposes 
to amend the definition of ``water-source heat pump'' to explicitly 
indicate that WSHPs are a category of commercial package air-
conditioning and heating equipment. This proposed clarification to the 
``water-source heat pump'' definition would not change the scope of 
equipment covered by the definition.
    In addition, DOE is proposing to amend the WSHP definition to 
clarify that an indoor fan is not an included component for coil-only 
WSHPs. The current definition lists the main components of a WSHP, and 
it includes ``indoor fan'' on that list. However, DOE has identified 
coil-only WSHPs on the market that rely on a separately installed 
furnace or modular blower for indoor air movement. To clarify that 
coil-only WSHPs are indeed covered under the WSHP definition, DOE is 
proposing to include the parenthesized statement ``except that coil-
only units do not include an indoor fan'' in the sentence listing the 
main components in the WSHP definition.
    In summary, DOE proposes to amend the definition of WSHP as 
follows:
    ``Water-source heat pump means commercial package air-conditioning 
and heating equipment that is a single-phase or three-phase reverse-
cycle heat pump that uses a circulating water loop as the heat source 
for heating and as the heat sink for cooling. The main components are a 
compressor, refrigerant-to-water heat exchanger, refrigerant-to-air 
heat exchanger, refrigerant expansion devices, refrigerant reversing 
valve, and indoor fan (except that coil-only units do not include an 
indoor fan). Such equipment includes, but is not limited to, water-to-
air water-loop heat pumps.''
    Issue 2: DOE requests comments on the proposed change to the 
definition of WSHP to explicitly indicate that WSHP is a category of 
commercial package air-conditioning and heating equipment and to 
clarify that the presence of an indoor fan does not apply to coil-only 
units.

C. Proposed Organization of the WSHP Test Procedure

    DOE is proposing to relocate and centralize the current test 
procedure for WSHPs to a new appendix C to subpart F of part 431. As 
proposed, appendix C would maintain the substance of the current test 
procedure. The test procedure as proposed in newly proposed appendix C 
would continue to reference ISO 13256-1:1998 and provide for 
determining energy efficiency ratio (``EER'') and COP. The proposed 
appendix C would centralize the additional test provisions currently 
applicable under 10 CFR 431.96, i.e., additional provisions for 
equipment set-up (10 CFR 431.96(e)). As proposed, WSHPs would be 
required to be tested according to appendix C until such time as 
compliance is required with an amended energy conservation standard 
that relies on the IEER metric, should DOE adopt such a standard.
    DOE is also proposing to establish a test procedure for WSHPs in a 
new appendix C1 to subpart F of part 431 that would incorporate by 
reference AHRI 340/360-2022 and ASHRAE 37-2009 along with additional 
provisions, as discussed in greater detail in the following sections. 
As proposed, WSHPs would not be required to test according to the test 
procedure in proposed appendix C1 until such time as compliance is 
required with an amended energy conservation standard that relies on 
the IEER metric, should DOE adopt such a standard, although any 
voluntary representations of IEER prior to the compliance date must be 
based on testing according to appendix C1.

D. Industry Standards

1. Applicable Industry Test Procedures
a. ISO Standard 13256-1
    As noted in section I.B of this document, the DOE test procedure 
currently incorporates by reference ISO 13256-1:1998 and includes 
additional provisions for equipment set-up at 10 CFR 431.96(e), which 
provide specifications for addressing key information typically found 
in the installation and operation manuals.
    ISO 13256-1:1998 specifies the cooling efficiency metric, EER,\7\ 
which is the ratio of the net total cooling capacity to the effective 
power input at

[[Page 53308]]

a single set of operating conditions. Table 1 of ISO 13256-1:1998 
specifies six sets of operating conditions for determining EER values 
based on variation in entering water temperature (``EWT'') \8\ and, for 
models with capacity control (i.e., multiple compressor stages), 
whether the test is a full-load or part-load test. The initial three 
sets, referred to as ``standard rating test'' conditions in Table 1 of 
ISO 13256-1:1998, are used to determine full-load EER values, which 
represent the cooling efficiency for a WSHP operating at its maximum 
capacity in the most demanding conditions (i.e., highest EWT) that the 
WSHP would regularly encounter. The three standard rating test 
conditions in Table 1 of ISO 13256-1:1998 differ in terms of EWT, in 
that they represent the highest EWT that would be regularly encountered 
in different specific applications (i.e., 86 [deg]F for water-loop, 59 
[deg]F for ground-water, and 77 [deg]F for ground-loop heat pumps).\9\ 
The standard rating test conditions specified for water-loop heat pumps 
are used in the current DOE test procedure.
---------------------------------------------------------------------------

    \7\ DOE defines ``EER'' at 10 CFR 431.92 as the ratio of the 
produced cooling effect of an air conditioner or heat pump to its 
net work input, expressed in BTU/watt-hour.
    \8\ ``EWT'' is used to describe the entering liquid temperature 
for WSHPs, which may be water or a brine solution, depending on the 
liquid temperature used for test.
    \9\ EWTs are specified in degrees Celsius in ISO 13256-1:1998, 
but they are referred to by their equivalent values of degrees 
Fahrenheit in this NOPR to ease comparison with other temperatures 
discussed elsewhere in this document.
---------------------------------------------------------------------------

    The next three sets of operating conditions for determining EER, 
referred to as ``part-load rating test'' conditions in Table 1 of ISO 
13256-1:1998, are specified to determine EER values at less than full 
capacity for models with capacity control. As with the standard rating 
test conditions, Table 1 of ISO 13256-1:1998 specifies part-load rating 
test conditions for different specific applications (i.e., 86 [deg]F 
for water-loop, 59 [deg]F for ground-water, and 68 [deg]F for ground-
loop heat pumps). None of the part-load rating test conditions are used 
in the current DOE test procedure. Although Table 1 of ISO 13256-1:1998 
specifies conditions for determining EER for multiple applications and 
(as applicable) capacity levels, ISO 13256-1:1998 does not include any 
seasonal cooling efficiency metrics.
    Additionally, unlike the test methods for other categories of 
commercial package air conditioners and heat pumps (e.g., AHRI 340/360-
2022 for commercial unitary air conditioners and heat pumps (``CUAC/
HPs''); AHRI Standard 1230-2021, ``2021 Standard for Performance Rating 
of Variable Refrigerant Flow (VRF) Multi-Split Air-Conditioning and 
Heat Pump Equipment'' (``AHRI 1230-2021''), for variable refrigerant 
flow air conditioners (``VRF multi-split systems''); AHRI Standard 390-
2021, ``2021 Standard for Performance Rating of Single Package Vertical 
Air-Conditioners and Heat Pumps'' (``AHRI 390-2021''), for single 
package vertical units (``SPVUs''); and AHRI Standard 210/240-2023, 
``2023 Standard for Performance Rating of Unitary Air-conditioning & 
Air-source Heat Pump Equipment'' (``AHRI 210/240-2023''), for central 
air conditioners and heat pumps (``CAC/HPs'')), for ducted units ISO 
13256-1:1998 does not produce ratings that reflect indoor fan power 
needed to overcome ESP from ductwork. Instead, section 4.1.3 of ISO 
13256-1:1998 includes a fan power adjustment (which assumes a fan 
efficiency of 0.3 for all units) to be applied such that only the fan 
power required to overcome the internal static pressure (``ISP'') of 
the unit is taken into account. The exclusion of fan power to overcome 
ESP from ductwork in ISO 13256-1:1998 ratings results in higher EER 
ratings than would be measured if ratings reflected fan power to 
overcome ESP, thereby being more representative of field applications.
    Similar to the treatment of fan power, ISO 13256-1:1998 does not 
produce ratings that reflect the pump power needed to overcome liquid 
ESP from the water loop that pipes water to and from the WSHP. Instead, 
section 4.1.4 of ISO 13256-1:1998 includes a pump power adjustment 
(which assumes a pump efficiency of 0.3 for all units) to be applied 
such that only the pump power required to overcome the liquid ISP of 
the unit is taken into account. ISO 13256-1:1998 also does not specify 
any liquid ESP requirements for testing. The exclusion of pump power to 
overcome ESP from system water loop piping in ISO 13256-1:1998 ratings 
results in higher EER ratings than would be measured if ratings 
reflected pump power to overcome ESP, thereby being more representative 
of field applications.
    An updated version of ISO Standard 13256-1 (i.e., ISO 13256-1:2021) 
was published in 2021. While there are numerous changes in ISO 13256-
1:2021 (discussed in detail in subsequent sections of this NOPR), the 
2021 version maintains provisions for determining EER, and it does not 
include provisions for determining a seasonal metric that incorporates 
tests at multiple conditions. ISO 13256-1:2021 also maintains the same 
indoor fan power adjustment and pump power adjustment as in the 1998 
version (see sections 5.1.3 and 5.1.4 of ISO 13256-1:2021), thus 
continuing to produce ratings that do not reflect fan power and pump 
power associated with overcoming ESP. As discussed in subsequent 
sections of this document, DOE is proposing provisions in its test 
procedures for WSHPs to address the identified shortcomings in ISO 
13256-1:1998 and ISO 13256-1:2021.
b. AHRI 340/360-2022 and ASHRAE 37-2009
    AHRI 340/360-2022 is the industry test procedure used for testing 
CUAC/HPs. AHRI 340/360-2022 includes the seasonal cooling metric IEER 
(see section 6.2 of AHRI 340/360-2022), which reflects cooling 
performance across a range of operating conditions and load levels. 
Specifically, IEER is a weighted average of the EER at full-load and 
several part-load conditions intended to represent the range of 
conditions that a unit would encounter over a full cooling season. The 
vast majority of operating hours for commercial air conditioners and 
heat pumps (including CUAC/HPs and WSHPs) occur when conditions are 
less demanding than full-load conditions. For example, the IEER metric 
in section 6.2.2 of AHRI 340/360-2022 specifies that full-load 
conditions account for only 2 percent of operation. AHRI 340/360-2022 
also includes minimum ESP requirements that are intended to reflect 
ESPs in field installations and includes all indoor fan power needed to 
overcome the tested ESP in the calculation of IEER (see section 6.1.3.3 
of AHRI 340/360-2022). AHRI 340/360-2022 also includes a power adder to 
account for the power of cooling tower fan motor(s) and circulating 
water pump(s). Similar to other industry test procedures for commercial 
package air-conditioning and heating equipment, AHRI 340/360-2022 
references ANSI/ASHRAE 37-2009 (see section 5.1.1 of AHRI 340/360-
2022), which provides a method of test applicable to many categories of 
air conditioning and heating equipment. In particular, sections 5 and 6 
and appendices C, D, E, and I of AHRI 340/360-2022 reference methods of 
test in ANSI/ASHRAE 37-2009. As discussed in subsequent sections of 
this notice, DOE has tentatively concluded that AHRI 340/360-2022 
addresses many of the identified shortcomings in ISO 13256-1:1998 and 
ISO 13256-1:2021.
c. AHRI 600
    AHRI is in the process of developing a new industry test standard 
for WSHPs titled ``AHRI Standard 600 IEER & SCHE Performance Rating of 
Water/Brine Source Heat Pumps'' (``AHRI 600''). This was formerly 
designated as AHRI Standard 500P (``AHRI 500P''). DOE has

[[Page 53309]]

participated in AHRI committee meetings working to develop AHRI 600 
since 2019. Based on its interactions with the AHRI committee, DOE 
understands that AHRI 600 would not include any provisions for testing, 
but rather would provide a method for calculation of a seasonal cooling 
efficiency metric for WSHPs (i.e., IEER) based on testing conducted 
according to ISO 13256-1:1998. Specifically, DOE understands that AHRI 
600 would provide for the calculation of IEER for WSHPs via 
interpolation and extrapolation of test results reflecting the testing 
temperatures specified in Table 1 of ISO 13256-1:1998, and the rating 
conditions for the IEER calculation would be based on the EWTs and 
weighting factors specified in Table 9 and section 6.2 of AHRI 340/360-
2022 for determining IEER for water-cooled CUACs. AHRI 600 is still in 
development and has not yet published. As discussed in subsequent 
sections of this notice, DOE has tentatively concluded that the general 
methodology in AHRI 600 for determining IEER is appropriate, although 
DOE has identified several aspects of the methodology that warrant 
further modifications.
2. Comments Received on Industry Standards and DOE Responses
    In the June 2018 RFI, DOE discussed how the test method used in ISO 
13256-1:1998 is similar to ANSI/ASHRAE 37-2009 and that ANSI/ASHRAE 37-
2009 is the method referenced by the 2015 version of AHRI 340/360 (the 
most current version at the time; ``AHRI 340/360-2015''). 83 FR 29048, 
29052 (June 22, 2018). DOE also discussed how AHRI 340/360-2015 is 
referenced by ASHRAE Standard 90.1 for testing WCUACs, and that DOE was 
considering whether using the same method of test for WSHPs and WCUACs 
would be appropriate, given the similarities in the design of WSHPs and 
WCUACs. Id. DOE requested comment on whether a single test method could 
be used for both WSHPs and WCUACs. Id. DOE also sought comment on any 
aspects of design, installation, and application of WSHPs that would 
make the use of ANSI/ASHRAE 37-2009 infeasible for WSHPs. Id.
    In response to the June 2018 RFI, AHRI and Trane stated that 
because ASHRAE Standard 90.1 reaffirmed the ISO 13256-1:1998 standard 
on October 26, 2018, the statutory trigger provisions of 42 U.S.C. 
6314(a)(4)(B) do not provide a basis for DOE to review its WSHP test 
procedure at that time. (AHRI, No. 12 at p. 1, Trane, No. 8 at p. 1)
    In response, DOE notes that in addition to the statutory trigger 
provisions of 42 U.S.C. 6314(a)(4)(B), the Department is statutorily 
required to review its test procedures every seven years per the 7-
year-lookback requirements at 42 U.S.C. 6314(a)(1), as outlined in 
section I.A of this NOPR.
    AHRI, WaterFurnace, and Trane recommended that DOE wait for the ISO 
revision process to be completed and adopt the revised version of ISO 
13256-1:1998 following a second RFI. (AHRI, No. 12 at p. 6; 
WaterFurnace, No. 7 at p. 2; Trane, No. 8 at p. 3) AHRI and 
WaterFurnace further commented that the next version of ISO 13256-1 was 
expected to publish in early 2019, and these commenters recommended 
that DOE should support the development of the next version of ISO 
13256-1:1998. (AHRI, No. 12 at pp. 3, 12-13; WaterFurnace, No. 7 at pp. 
2, 10) AHRI and WaterFurnace also stated that many key authors of ANSI/
ASHRAE 37-2009 are on the ISO working group, and that the working group 
was planning to add clarity to the test method with the next revision 
of ISO 13256-1:1998. The commenters also stated that minimum ESPs were 
being considered for inclusion in the revised version of ISO 13256-
1:1998. Id.
    AHRI and WaterFurnace further stated that for international 
standards, each nation requires slight deviations from the written ISO 
standard and that the AHRI WSHP/Geothermal Operations Manual \10\ 
provides the U.S. national deviations from ISO 13256-1:1998. (AHRI, No. 
12 at p. 2; WaterFurnace, No. 7 at p. 2) They further stated that the 
AHRI WSHP/Geothermal Operations Manual addresses multiple issues raised 
by DOE in the June 2018 RFI. Id.
---------------------------------------------------------------------------

    \10\ DOE notes that the AHRI geothermal operations manual is 
available at: <a href="https://www.ahrinet.org/App_Content/ahri/files/Certification/OM%20pdfs/WSHP_OM.pdf">https://www.ahrinet.org/App_Content/ahri/files/Certification/OM%20pdfs/WSHP_OM.pdf</a> (Last accessed July 29, 2022).
---------------------------------------------------------------------------

    In response, DOE notes that ISO 13256-1:2021 also lacks a seasonal 
cooling efficiency metric and does not produce ratings that reflect fan 
power and pump power associated with overcoming ESP. As discussed, a 
seasonal cooling efficiency metric would account for the range of 
conditions that a unit would encounter over a full cooling season. In 
addition, the inclusion of fan and pump power associated with 
overcoming ESP would provide ratings that would be more representative 
of the power consumption in field applications needed to overcome 
pressure from ductwork and water piping. Section III.D.3 of this 
document provides further discussion of these considerations and DOE's 
preliminary conclusion that alternate test methods that address these 
key issues would provide a more representative measure of a WSHP's 
overall energy efficiency.
    While an updated version of ISO Standard 13256-1 has published 
(i.e., ISO 13256-1:2021), DOE is not aware of a deviation process being 
initiated for the U.S. (i.e., development of the version designated 
with ``AHRI/ASHRAE'' that is intended for use for testing in the U.S.). 
DOE understands that the national deviation process will be initiated 
by a WSHP industry committee, but DOE does not know when that will 
begin or how long the national deviation process will take. DOE notes 
that in the past, the WSHP industry committees have taken years longer 
than expected to develop the revised version of ISO 13256-1, as well as 
AHRI 600. Specifically, in their RFI comments, AHRI and WaterFurnace 
stated that they expected the revised ISO 13256-1 to publish in ``early 
2019'' and AHRI 600 to publish in 2019, whereas in reality, the revised 
ISO 13256-1 published in 2021 and AHRI 600 remains as yet unpublished. 
Therefore, DOE expects that the national deviation process will not be 
completed for several years, and the Department cannot speculate as to 
the substantive output of those efforts or a final completion date. 
Given EPCA's statutory requirement to review the appropriate test 
procedures for WSHPs every seven years, DOE has tentatively concluded 
that it would be neither appropriate nor permissible to delay the 
current rulemaking for the WSHP test procedure until after the 
completion of the national deviation process (which the Department 
understands has not yet even begun).
    DOE further notes that the AHRI WSHP/Geothermal Operations Manual 
is not incorporated by reference into the DOE test procedure, nor is it 
referenced in ASHRAE Standard 90.1. Therefore, the deviations from the 
ISO standard included in the AHRI WSHP/Geothermal Operations Manual are 
not reflected in the current DOE test procedure. However, DOE has 
nonetheless reviewed the AHRI WSHP/Geothermal Operations Manual as part 
of its consideration of potential amended test procedure provisions in 
this NOPR.
    With regards to use of a part-load efficiency metric, Trane, AHRI, 
and WaterFurnace commented that industry is currently developing an 
IEER metric for WSHPs. (Trane, No. 8 at p. 4; AHRI, No. 12 at p. 11; 
WaterFurnace, No. 7 at p. 9) AHRI and WaterFurnace commented further 
that the IEER metric

[[Page 53310]]

is included in the draft of AHRI 500P \11\ and is calculated using 
performance data from ISO 13256-1:1998. In addition, AHRI and 
WaterFurnace stated that WSHPs in water-loop applications (i.e., 
installed with cooling towers) operate with similar water-loop 
conditions to WCUACs. Therefore, the commenters argued that the 
provisions used for determining IEER for WSHPs in the draft of AHRI 
500P are similar to those included in AHRI 340/360 and AHRI 1230; 
specifically, the commenters included a table showing that the IEER EWT 
conditions in the draft of AHRI 500P align with those specified in AHRI 
340/360. Both AHRI and WaterFurnace commented that they anticipated 
AHRI 500P to be completed in 2019. (AHRI, No. 12 at pp. 11-12; 
WaterFurnace, No. 7 at p. 9)
---------------------------------------------------------------------------

    \11\ As discussed, after DOE received comments in response to 
the June 2018 RFI, the draft AHRI Standard 500P was redesignated as 
the draft AHRI Standard 600.
---------------------------------------------------------------------------

    Once again, DOE notes that AHRI 600 \12\ has not yet published, and 
the Department is unaware as to when that document will be completed. 
Accordingly, for this NOPR, in addition to proposing a method to 
determine IEER by testing at the IEER test points specified in Table 9 
of AHRI 340/360-2022, DOE is proposing an alternate method of 
calculating IEER (based on interpolation and extrapolation from results 
of testing to EWTs specified in Table 1 of ISO 13256-1:1998, rather 
than testing directly at the EWTs specified for the IEER metric in 
Table 9 of AHRI 340/360-2022) that DOE understands to be consistent 
with the approach in the current draft version of AHRI 600. Section 
III.E.1.b of this NOPR includes further details on the proposed 
optional approach for calculation of IEER based on interpolation and 
extrapolation.
---------------------------------------------------------------------------

    \12\ As discussed, after DOE received comments in response to 
the June 2018 RFI, the draft AHRI Standard 500P was redesignated as 
the draft AHRI Standard 600.
---------------------------------------------------------------------------

    DOE also received comments from AHRI, Trane, and WaterFurnace that 
cautioned against using a different test standard, such as AHRI 340/
360, for testing WSHPs instead of ISO 13256-1 as currently specified. 
(Trane, No. 8 at p. 4; AHRI, No. 12 at p. 12; WaterFurnace, No. 7 at p. 
10) AHRI, Trane, and WaterFurnace argued that AHRI 340/360 does not 
include several important features that are included in ISO 13256-
1:1998 such as: provisions for heating performance, performance mapping 
\13\ across a wide temperature range, part-load ratings, application 
ratings for well water and geothermal, and provisions for testing units 
with variable-speed compressors. (Trane, No. 8 at p. 4; AHRI, No. 12 at 
p. 12; WaterFurnace, No. 7 at p. 10) Trane stated that AHRI 340/360 
covers only cooling-mode operation of water-cooled units, and that 
WSHPs require a test procedure that includes both cooling and heating 
cycle operation. (Trane, No. 8 at p. 4) AHRI and WaterFurnace 
additionally stated that certain aspects of ISO 13256-1:1998, such as 
standard rating conditions, are not included in ANSI/ASHRAE 37-2009 
because ANSI/ASHRAE 37-2009 is a method of test rather than a test 
standard. (AHRI, No. 12 at pp. 12-13; WaterFurnace, No. 7 at pp. 10-11) 
AHRI, Trane, and WaterFurnace further commented that that many aspects 
of ANSI/ASHRAE 37-2009 are accounted for in ISO 13256-1:1998. (AHRI, 
No. 12 at p. 13; Trane, No. 8 at p. 4; WaterFurnace, No. 7 at p. 10) 
AHRI and WaterFurnace also stated that several Environmental Protection 
Agency (``EPA''), State, utility, and building code requirements 
reference ISO 13256-1:1998, and they asserted that removing reference 
to it would have a significant negative impact on the industry and 
consumers who use efficiency programs and tax credits when selecting 
equipment. (AHRI, No. 12 at p. 12; WaterFurnace, No. 7 at p. 10)
---------------------------------------------------------------------------

    \13\ DOE understands use of the term ``performance mapping'' as 
referring to making representations of performance across a range of 
temperature conditions, typically achieved by interpolating or 
extrapolating from test results obtained at specifically defined 
test conditions.
---------------------------------------------------------------------------

    The following paragraphs provide DOE's responses to concerns 
expressed by commenters that AHRI 340/360 and ANSI/ASHRAE 37-2009 lack 
certain provisions that are present in ISO 13256-1 and that are needed 
for testing WSHPs.
    Regarding provisions for heating tests, DOE acknowledges that AHRI 
340/360-2022 does not include certain provisions needed for heating-
mode testing of WSHPs because WCUACs, the water-cooled units for which 
AHRI 340/360-2022 is intended to apply, are not heat pumps. 
Specifically, AHRI 340/360-2022 does not specify the following 
provisions for a heating test: an EWT test condition, provisions for 
setting liquid flow rate, or how pump effects are accounted for. 
Therefore, DOE is proposing additional provisions that would address 
these aspects of heating-mode tests of WSHPs, as discussed further in 
sections III.E.2, III.F.4, III.F.5, and III.F.6 of this document. DOE 
notes that AHRI 340/360-2022 does include provisions appropriate for 
air-side measurements in heating tests because AHRI 340/360-2022 covers 
air-cooled commercial unitary heat pumps. Furthermore, ANSI/ASHRAE 37-
2009 provides appropriate provisions for a method of test for WSHPs. 
DOE has tentatively concluded that its proposals for heating provisions 
for WSHPs would, when combined with the provisions in AHRI 340/360-
2022, produce test results representative of an average use cycle.
    Regarding performance mapping across a wide temperature range, 
part-load ratings, and ratings for ground-water and geothermal 
applications, DOE acknowledges that AHRI 340/360-2022 does not include 
EWTs specific to multiple applications of WSHPs. By contrast, Table 1 
of ISO 13256-1:1998 provides separate EWTs for water-loop, ground-
water, and ground-loop WSHP applications (see discussion in section 
III.D.1.a of this NOPR). AHRI 340/360-2022 includes full-load and part-
load cooling EWTs for only water-loop applications of WCUACs, but the 
EWT for water-loop applications in Table 1 of ISO 13256-1:1998 is the 
only EWT test condition used in the current DOE test procedure. As 
discussed in sections III.D.3 and III.E.1 of this NOPR, DOE has 
tentatively concluded that the seasonal integrated cooling metric IEER 
specified in section 6.2 of AHRI 340/360-2022 would be more 
representative of field applications and provide consumers with a 
better understanding of year-round performance of WSHPs than the EER 
metric measured at a single temperature and load level. However, DOE 
recognizes the potential benefits to consumers of allowing 
manufacturers to continue to provide performance ratings at the 
temperatures and load levels specified in Table 1 of ISO 13256-1:1998, 
in addition to providing the proposed IEER ratings which are more 
representative of year-round performance. Therefore, as discussed in 
section III.E.1.a of this NOPR, DOE is proposing in section 5.2 of 
proposed appendix C1 to provide for optional representations of EER at 
the EWTs and load levels specified in Table 1 of ISO 13256-1:1998. 
Consequently, DOE has tentatively concluded that the proposals in this 
NOPR would continue to provide manufacturers the flexibility to offer 
full-load and part-load EER ratings at multiple temperatures that can 
be used for performance mapping, representations of part-load 
performance, and representations of performance for ground-water and 
geothermal applications.
    Regarding variable-speed compressors, section 6.2 of AHRI 340/360-
2022 includes appropriate provisions for testing and determining IEER 
for units with all compressor

[[Page 53311]]

types, including variable-speed compressors. Specifically, Section 
6.2.6 of AHRI 340/360-2022 includes provisions addressing 
``proportionally capacity controlled units,'' which is defined in 
section 3.22 of AHRI 340/360-2022 to include units incorporating one or 
more variable-capacity compressors where the compressor capacity can be 
modulated continuously or in steps not more than 5 percent of the full-
load cooling capacity. Section 6.2.6 of AHRI 340/360-2022 includes 
steps for setting capacity of these units for each IEER test point.
    With regards to EPA, State, utility, and building code requirements 
that reference ISO 13256-1:1998, DOE does not expect that an update to 
the DOE test procedure for WSHPs would create any particular challenges 
for any other agency or organization that references the performance 
ratings as measured by the DOE test procedure. EPCA directs DOE to 
establish and amend test procedures to be reasonably designed to 
produce test results which reflect energy efficiency, energy use, and 
estimated operating costs of covered equipment during a representative 
average use cycle (as determined by the Secretary), and not be unduly 
burdensome to conduct. (42 U.S.C. 6314(a)(2)) DOE test procedures are 
updated regularly, across many products and equipment types, and other 
agencies and organizations have historically updated their requirements 
as needed in response to those changes. With regard to EPA 
specifically, DOE has responsibility for developing and revising the 
test procedures that provide the basis for ratings under EPA's ENERGY 
STAR program. DOE and EPA work closely together to update ENERGY STAR 
specifications in response to any changes to the relevant DOE test 
procedure. Furthermore, DOE is proposing that the amended test 
procedure would not be required for use until the effective date of any 
future energy conservation standards based on the IEER metric, thereby 
providing sufficient advance notice for any agency or organization to 
adapt program requirements accordingly.
3. Proposal for DOE Test Procedure
    As discussed, EPCA requires that test procedures for covered 
equipment, including WSHPs, be reasonably designed to produce test 
results which reflect energy efficiency, energy use, and estimated 
operating costs of a type of industrial equipment (or class thereof) 
during a representative average use cycle (as determined by the 
Secretary), and shall not be unduly burdensome to conduct. (42 U.S.C. 
6314(a)(2))
    For the reasons presented in the remainder of this section, DOE has 
tentatively determined that the test procedure for WSHPs as proposed 
would improve the representativeness of the current Federal test 
procedure for WSHPs and would not be unduly burdensome. Specifically, 
DOE has tentatively concluded, supported by clear and convincing 
evidence as discussed in the following paragraphs, that testing WSHPs 
in accordance with the industry test standards AHRI 340/360-2022 and 
ASHRAE 37-2009 would provide more representative results and more fully 
comply with the requirements of paragraph (2) of 42 U.S.C. 6314(a) than 
testing in accordance with the currently referenced standard ISO 13256-
1:1998. Therefore, DOE is proposing to amend the test procedure for 
WSHPs so as to incorporate by reference in the proposed new appendix C1 
the test provisions in AHRI 340/360-2022 and ASHRAE 37-2009, along with 
certain additional provisions.
    Throughout the remainder of the discussion in section III of this 
NOPR, DOE presents the details and justifications for the proposed test 
procedure and deviation from the currently referenced industry test 
procedure, ISO 13256-1:1998 (i.e., the industry test standard 
referenced in ASHRAE Standard 90.1). The following paragraphs summarize 
the key areas in which DOE has tentatively concluded, supported by 
clear and convincing evidence, that the proposal would improve the 
representativeness of the test procedure:
    (1) Cooling efficiency metric: As discussed, the cooling metric 
specified in the current DOE test procedure (which references ISO 
13256-1:1998) is EER, which reflects full-load performance only at a 
single operating condition. In contrast, IEER, the metric specified in 
section 6.2 of AHRI 340/360-2022, is a seasonal metric that is a 
weighted average of the full- and part-load performance at different 
outdoor conditions intended to represent average efficiency over a full 
cooling season. For the vast majority of operating hours for WSHPs and 
other commercial air conditioners and heat pumps installed in the 
field, loads are at less than full-load capacity. This is because units 
are sized to be able to provide sufficient air conditioning capacity at 
the hottest time on the hottest day of the year, but the vast majority 
of annual cooling hours are at significantly lower outdoor temperatures 
(and thus lower EWTs), with correspondingly lower cooling loads. This 
is demonstrated in the IEER metric specified in section 6.2.2 of AHRI 
340/360-2022, which specifies a weighting factor for full-load 
conditions of only 2 percent of the hours included in the IEER metric, 
with the remaining 98 percent of hours assigned to lower load levels 
and lower outdoor temperatures. As discussed, from RFI comments and 
DOE's participation in AHRI 600 committee meetings, DOE understands 
that the AHRI 340/360-2022 IEER weighting factors are also included in 
the draft AHRI 600. Therefore, DOE has tentatively concluded that IEER 
would be more representative of an average use cycle than the EER 
metric. This topic is discussed further in section III.E.1 of this 
NOPR.
    (2) Fan power and indoor air external static pressure: As 
discussed, for ducted units, ISO 13256-1:1998 does not produce ratings 
that reflect the fan power needed to overcome ESP. Further, that ISO 
standard does not specify ESP requirements for ducted units and instead 
uses a fan power adjustment, such that ratings reflect only the fan 
power needed to overcome internal static pressure within the unit and 
not the ESP from the ductwork that would be installed in the field. In 
contrast, Table 7 of AHRI 340/360-2022 specifies minimum ESP 
requirements at which performance is measured. Because ducted WSHPs are 
manufactured to be installed in the field with ductwork, DOE has 
tentatively concluded that a WSHP rating that reflects the indoor fan 
power needed to overcome ESP representative of typical installations 
(i.e., the approach taken by AHRI 340/360-2022) would produce test 
results that are more representative of an average use cycle than 
testing in accordance with ISO 13256-1:1998, the standard currently 
incorporated by reference.
    (3) Pump power and liquid external static pressure: ISO 13256-
1:1998 does not produce ratings that reflect the pump power needed to 
overcome liquid ESP. Further, for units with integral pumps, ISO 13256-
1:1998 does not specify ESP requirements and uses a pump power 
adjustment such that ratings reflect only the pump power needed to 
overcome internal static pressure within the unit. For units with 
integral pumps, DOE has tentatively concluded that ratings would be 
more representative if based on testing at a liquid ESP that is 
representative of the ESP from water piping in typical installations. 
For units without integral pumps, DOE has tentatively concluded that 
ratings would be more

[[Page 53312]]

representative if a pump power adder is included in the rating that 
reflects pump power needed to overcome a field-representative liquid 
ESP. More discussion on this topic is provided in section III.F.4 of 
this document.
    DOE is proposing to adopt in its WSHP test procedure the following 
specific sections of AHRI 340/360-2022:

    (1) Section 3: Definitions, excluding sections 3.2, 3.4, 3.5, 
3.7, 3.8, 3.12, 3.14, 3.15, 3.17, 3.23, 3.26, 3.27, 3.29, 3.30, and 
3.36;
    (2) Section 5: Test Requirements;
    (3) Section 6: Rating Requirements, excluding sections 6.1.1.7, 
6.1.2.1, 6.1.3.4.5, 6.1.3.5.4, 6.1.3.5.5, 6.5, 6.6, and 6.7;
    (4) Appendix A. References--Normative;
    (5) Appendix C. Indoor and Outdoor Air Condition Measurement--
Normative;
    (6) Appendix E. Method of Testing Unitary Air Conditioning 
Products--Normative;

    The key substantive changes that would result from DOE's proposal 
to adopt AHRI 340/360-2022 for testing WSHPs include the following:

    (1) A new energy efficiency descriptor, IEER, which incorporates 
part-load cooling performance (see section 6.2 of AHRI 340/360-
2022);
    (2) Minimum ESP requirements, instructions for setting airflow 
and ESP, and tolerances for airflow and ESP (see sections 6.1.3.3, 
6.1.3.4, and Table 6 of AHRI 340/360-2022);
    (3) Fixed inlet and outlet water temperature conditions (see 
Table 5 of AHRI 340/360-2022);
    (4) Operating tolerance for voltage (see Table 10 of AHRI 340/
360-2022);
    (5) Different indoor air conditions used for testing (see Table 
5 of AHRI 340/360-2022);
    (6) Refrigerant charging instructions for cases where they are 
not provided by the manufacturer (see section 5.8 of AHRI 340/360-
2022), and
    (7) Use of the primary capacity measurement (i.e., indoor air 
enthalpy method) as the value for capacity, and different provisions 
for required agreement between primary and secondary capacity 
measurements (see section E6 of Appendix E to AHRI 340/360-2022).

    Appendix E of AHRI 340/360-2022 specifies the method of test, 
including the use of specified provisions of ANSI/ASHRAE 37-2009. 
Consistent with AHRI 340/360-2022, DOE is proposing to incorporate by 
reference ANSI/ASHRAE 37-2009 in its test procedure for WSHPs. 
Specifically, in section 1 of the proposed test procedure for WSHPs in 
the proposed appendix C1, DOE is proposing to adopt all sections except 
sections 1, 2, and 4 of ANSI/ASHRAE 37-2009. The key substantive 
changes that would result from DOE's proposal to adopt ANSI/ASHRAE 37-
2009 for testing WSHPs include the following:

    (1) Provisions for split systems, such as accounting for 
compressor heat and refrigerant line losses (see sections 7.3.3.4, 
7.3.4.4, and 7.6.1.2 of ASHRAE 37-2009);
    (2) Measurement of duct losses for ducted units (see section 
7.3.3.3 of ASHRAE 37-2009);
    (3) Standardized heat capacity of water and brine (see section 
12.2 of ASHRAE 37-2009), and
    (4) A calculation for discharge coefficients (see section 6.3.2 
of ASHRAE 37-2009).

    Throughout the remainder of this NOPR, DOE discusses substantive 
differences between the proposed test procedure (including references 
to AHRI 340/360-2022 and ASHRAE 37-2009) and the current DOE test 
procedure (which incorporates by reference ISO 13256-1:1998). DOE also 
identified and considered provisions in the updated industry test 
procedure ISO 13256-1:2021 that substantively differ from ISO 13256-
1:1998.

E. Efficiency Metrics

1. IEER
a. General Discussion
    As discussed previously, DOE's current test procedure for WSHPs 
measures cooling-mode performance in terms of the EER metric, the 
current regulatory metric. 10 CFR 431.96. EER captures WSHP performance 
at a single, full-load operating point in cooling mode (i.e., a single 
EWT) and does not provide a seasonal or load-weighted measure of energy 
efficiency. A seasonal metric is a weighted average of the performance 
of cooling or heating systems at different outdoor conditions intended 
to represent average efficiency over a full cooling or heating season. 
Several categories of commercial package air-conditioning and heating 
equipment are rated using a seasonal or part-load metric, such as IEER 
for CUACs specified in section 6.2 of AHRI 340/360-2022. IEER is a 
weighted average of efficiency at four load levels representing 100, 
75, 50, and 25 percent of full-load capacity, each measured at a 
specified outdoor condition that is representative of field operation 
at the given load level. In general, the IEER metric provides a more 
representative measure of field performance than EER by weighting the 
full-load and part-load efficiencies by the average amount of time 
equipment spends operating at each load level. Table 1 of ISO 13256-
1:1998, the industry test standard incorporated by reference into DOE's 
current WSHP test procedure, and Table 2 of ISO 13256-1:2021 both 
specify entering water temperature conditions to be used for developing 
part-load ratings of EER for WSHPs with capacity control (tested at 
minimum compressor speed). However, part-load EER ratings are not 
addressed in the current DOE test procedure. Further, each part-load 
rating captures operation only at a single compressor speed and 
entering water temperature, not operation across a range of 
temperatures and compressor speeds. Neither ISO 13256-1:1998 nor ISO 
13256-1:2021 include seasonal metrics.
    In the June 2018 RFI, DOE requested comment on whether a seasonal 
metric that accounts for part-load performance would be appropriate for 
WSHPs, and the Department sought information on the specific details of 
a seasonal metric that would best represent average cooling efficiency 
for WSHPs. 83 FR 29048, 29051 (June 22, 2018).
    NEEA encouraged DOE to consider adopting IEER for WSHPs and to 
improve the metric so as to make it more representative of an average 
use cycle by including changes to more accurately represent fan energy 
use in field applications, accounting for all modes of operation, and 
including ventilating and economizing. (NEEA, No. 11 at p. 2)
    The Joint Advocates recommended that DOE should consider seasonal 
efficiency metrics for WSHPs to better reflect field energy 
consumption, including part-load operation. The Joint Advocates stated 
that it was their understanding that WSHPs operate most of the time at 
part-load, and that, therefore, full-load efficiency ratings do not 
provide sufficient information to consumers. The Joint Advocates also 
stated that the current metrics do not demonstrate the potential 
savings associated with technologies that improve part-load efficiency, 
such as variable-speed compressors. (Joint Advocates, No. 10 at p. 2)
    The CA IOUs stated that while the IEER metric provides a valuable 
measure of annual efficiency, the EER metric is important for achieving 
reductions in peak loads. These commenters remarked that because the 
IEER metric uses a low weighting (i.e., 2 percent) for the full-load 
condition, a standard based only on the IEER metric would incentivize 
manufacturers to optimize equipment at the part-load conditions and 
could potentially result in equipment that is designed with lower full-
load EERs than the current standards for this equipment. To prevent 
poor equipment performance at full-load conditions, the CA IOUs 
supported using the IEER metric that measures part-load efficiencies in 
conjunction with the currently regulated full-load EER metric. (CA 
IOUs, No. 9 at pp. 1-2) The CA IOUs further commented that the 
prevalence of economizers in buildings with WSHPs

[[Page 53313]]

should be investigated and that modifications to the IEER metric should 
be informed by the outcome of such research before the IEER metric is 
implemented as the efficiency metric for WSHPs. (CA IOUs, No. 9 at p. 
1)
    Trane, AHRI, and WaterFurnace commented that industry is currently 
developing an IEER metric for WSHPs (Trane, No. 8 at p. 4; AHRI, No. 12 
at p. 11; WaterFurnace, No. 7 at p. 9). AHRI and WaterFurnace explained 
further that the IEER metric is included in the draft version of AHRI 
500P,\14\ and as drafted, IEER is calculated using performance data 
from ISO 13256-1:1998. AHRI and WaterFurnace commented that the 
provisions used for determining IEER for WSHPs in the draft version of 
AHRI 500P are similar to those included in AHRI 340/360 and AHRI 1230. 
Both AHRI and WaterFurnace commented that they anticipated AHRI 500P to 
be completed in 2019. (AHRI, No. 12 at p. 11; WaterFurnace, No. 7 at p. 
9)
---------------------------------------------------------------------------

    \14\ As discussed, after DOE received comments in response to 
the June 2018 RFI, the draft AHRI Standard 500P was redesignated as 
the draft AHRI Standard 600.
---------------------------------------------------------------------------

    As explained previously, DOE notes that the EER metric in DOE's 
current test procedure for WSHPs measures only full-load performance, 
and the revised industry test procedure ISO 13256-1:2021 does not 
include a seasonal metric. For the vast majority of operating hours of 
WSHPs installed in the field, loads are less than full-load capacity, 
thus causing single-stage WSHPs to cycle and multi-stage WSHPs to 
operate at part-load (i.e., less than designed full capacity). Because 
a seasonal metric reflects operation at a range of conditions 
experienced over the period of a cooling season, DOE has tentatively 
concluded that a cooling metric that accounts for part-load performance 
across a range of temperatures (such as IEER specified in section 6.2 
of AHRI 340/360-2022) would be more representative of an average use 
cycle than the full-load EER metric, which reflects operation at a 
single condition. Further, a seasonal metric that reflects varying load 
levels representative of a full cooling season would better incentivize 
use of modulating components (e.g., multi-stage and variable-speed 
compressors) that can reduce annual energy consumption in field 
installations.
    DOE has been participating in AHRI committee meetings to develop 
AHRI 600 with the goal of specifying an IEER metric for WSHPs. It is 
DOE's understanding that the committee's work is ongoing, and its 
completion date is uncertain. However, based on comments received on 
the June 2018 RFI, manufacturer feedback obtained via DOE's 
participation in AHRI 600 committee meetings, and DOE's own research, 
the Department has tentatively concluded that the EWTs and weighting 
factors specified in Table 9 and equation 3 of AHRI 340/360-2022 for 
water-cooled CUACs would be representative for WSHPs. DOE's 
understanding based on a review of market literature and available 
studies is that in the past, WSHP installations were more typically 
controlled such that water-loop temperatures were maintained at 
temperatures above 60 [deg]F through heat provided by a system boiler. 
From manufacturer feedback provided in AHRI 600 committee meetings, DOE 
understands that in current practice, WSHP installations are typically 
controlled to allow water-loop temperatures to drop to temperatures 
closer to 50 [deg]F. Manufacturers indicated that this change in how 
WSHP system loops are typically controlled in the field is because of 
multiple factors. One factor provided by manufacturers is that because 
commercial buildings with WSHP installations are typically cooling-
dominated (i.e., most WSHPs spend more time in cooling mode than 
heating mode), building engineers have increasingly optimized overall 
WSHP system performance by using the cooling tower to decrease EWTs 
below 60 [deg]F even when some WSHPs in the loop are in heating mode, 
thereby improving efficiency for the WSHPs in cooling mode at the 
expense of reducing efficiency for the fewer WSHPs in heating mode. 
Additionally, manufacturers indicated that the market penetration of 
WSHPs with water-side economizers has significantly increased in recent 
years, largely related to requirements in ASHRAE Standard 90.1 
regarding presence of economizers in HVAC systems. Water-side 
economizers provide compressor-free cooling when supplied with water of 
sufficiently low temperature; therefore, manufacturers have indicated 
that building engineers are increasingly maintaining WSHP loop 
temperatures below 60 [deg]F to take advantage of water-side economizer 
cooling.\15\ Given this feedback provided by manufacturers on the WSHP 
loop water temperatures typically used in the field, DOE has 
tentatively concluded that the IEER EWTs specified in Table 9 of AHRI 
340/360-2022 (i.e., 85 [deg]F, 73.5 [deg]F, 62 [deg]F, and 55 [deg]F) 
are representative of current installations of WSHPs. Section III.E.4 
of this NOPR includes discussion on other operating modes other than 
mechanical cooling and heating, such as ventilation and economizing.
---------------------------------------------------------------------------

    \15\ In WSHPs with water-side economizers, if the EWT is 
sufficiently low in cooling mode, some or all of the entering water 
that would otherwise enter the water-to-refrigerant condenser coil 
instead enters the economizer coil, in which the cool water is used 
to directly cool indoor air, reducing the need for mechanical 
cooling from the compressor.
---------------------------------------------------------------------------

    Based on the discussion in the preceding paragraphs, DOE has 
tentatively determined that use of a seasonal efficiency metric, 
specifically IEER based on AHRI 340/360-2022, would be more 
representative of the average use cycle of a unit as compared to the 
current EER metric. Once again, DOE notes that while it may have been 
expected that AHRI 600 was to publish in 2019, the draft standard has 
not yet been finalized. Accordingly, DOE is moving forward and 
proposing to adopt certain provisions of AHRI 340/360-2022 and use the 
IEER metric specified in section 6.2 of AHRI 340/360-2022 for WSHPs. 
DOE is proposing to specify the relevant test procedure requirements 
for WSHPs for measuring IEER in section 5.1 of proposed appendix C1.
    As discussed, the proposed IEER test procedure for WSHPs would not 
be required until such a time as DOE adopts energy conservation 
standards for WSHPs denominated in terms of IEER, should DOE adopt such 
standards. If DOE were to adopt such standards, such shift to the IEER 
metric for WSHPs would require all WSHPs to be re-rated in terms of the 
IEER metric. Further, beginning 360 days after final rule publication, 
manufacturers would be required to use the proposed test procedure in 
appendix C1 to make optional representations of IEER for WSHPs. The 
cost and impacts to manufacturers of the proposed test procedure are 
discussed further in section III.I of this document. Additionally, 
adopting the IEER metric for WSHPs would increase the number of 
required cooling-mode tests from one to four. However, as discussed, 
DOE understands that AHRI 600 would provide for calculating IEER from 
test results measured at the EWTs specified in Table 1 of ISO 13256-
1:1998. Consistent with this approach and as discussed in the following 
section, DOE is proposing to allow determination of IEER via 
interpolation and extrapolation from testing at the full-load and part-
load EWT conditions specified in Table 1 of ISO 13256-1:1998.

[[Page 53314]]

    In response to the CA IOUs' suggestion, although EPCA limits the 
agency to promulgation of a single performance standard (see 42 U.S.C. 
6311(18)), DOE is proposing to provide for optional representations of 
EER conducted per the proposed test procedure (sections 2 through 4 and 
7 of proposed appendix C1) at the full-load and part-load EWT 
conditions specified in Table 1 of ISO 13256-1:1998 (i.e., full load 
tests at 86 [deg]F, 77 [deg]F, and 59 [deg]F and part-load tests at 86 
[deg]F, 68 [deg]F, and 59 [deg]F).
    Issue 3: DOE requests comment on its proposal to adopt the test 
methods specified in AHRI 340/360-2022 for calculating the IEER of 
WSHPs. DOE also requests comment on its proposal that all EER tests at 
full-load and part-load conditions specified in Table 1 of ISO 13256-
1:1998 (i.e., full-load tests at 86 [deg]F, 77 [deg]F, and 59 [deg]F 
and part-load tests at 86 [deg]F, 68 [deg]F, and 59 [deg]F) are 
optional.
b. Determination of IEER Via Interpolation and Extrapolation
    As discussed, DOE understands that the draft AHRI 600 would provide 
a mechanism for calculating IEER from test results measured at the EWTs 
specified in Table 1 of ISO 13256-1:1998. Specifically, interpolation 
and extrapolation \16\ from ISO 13256-1:1998 test results would be used 
to calculate performance at the EWTs specified in Table 9 of AHRI 340/
360-2022 for WCUACs, allowing calculation of IEER for WSHPs using the 
weighting factors specified in section 6.2.2 of AHRI 340/360-2022. 
Under this approach, AHRI 600 would not include any provisions for 
testing, but rather would provide a method for calculation of IEER 
based on results of testing under ISO 13256-1:1998. DOE recognizes that 
there may be a value for stakeholders in representations of full-load 
and part-load EER ratings at the temperatures specified in Table 1 of 
ISO 13256-1:1998. Specifically, these EWTs represent different 
applications, and manufacturers may prefer to provide representations 
of performance specific to different applications.
---------------------------------------------------------------------------

    \16\ Per the draft AHRI 600 method, performance at IEER EWTs can 
be determined using test results at two different temperature 
conditions (specified in ISO 13256-1:1998). Interpolation is used if 
the IEER EWT is between the two tested EWTs, and extrapolation is 
used if the IEER EWT is outside the range of the two tested results.
---------------------------------------------------------------------------

    The ability to determine EER ratings at the ISO 13256-1:1998 EWTs 
(in accordance with the proposed test procedure, at section 5.2 of the 
proposed appendix C1), and to determine IEER via interpolation and 
extrapolation from testing at the ISO 13256-1:1998 EWTs, rather than 
from additional testing at the IEER EWTs specified in AHRI 340/360-
2022, may reduce overall testing burden for manufacturers. 
Consequently, DOE investigated the AHRI 600 method of calculating IEER.
    To evaluate the draft AHRI 600 method of calculating IEER, DOE 
conducted investigative testing on a sample of WSHPs. DOE presents the 
results of testing 15 WSHPs in the following paragraphs. This testing 
compared the interpolation and extrapolation method of calculating IEER 
at the ISO 13256-1:1998 EWTs to testing at the IEER EWTs specified in 
AHRI 340/360-2022. In summary and for the reasons discussed in the 
following paragraphs, DOE has tentatively determined that an 
interpolation and extrapolation approach, similar to that in draft AHRI 
600 with certain modifications, is appropriately representative to 
calculate IEER.
    To determine if the interpolation and extrapolation method is 
appropriate for WSHPs, DOE evaluated whether the components needed to 
calculate IEER can be linearly interpolated across EWT. Specifically, 
the parameters necessary for the calculation of IEER are EER, capacity, 
total power, and all components of power (i.e., compressor power, fan 
power, condenser section power, controls power). DOE tested 15 units at 
different EWTs to compare physical tested results and interpolated and 
extrapolated values. The method evaluated by DOE determines IEER 
ratings for WSHPs by interpolation and extrapolation from full-load 
tests at liquid inlet temperatures of 86 [deg]F, 77 [deg]F, and 59 
[deg]F and, for two-stage and variable-speed units, part-load tests at 
86 [deg]F, 68 [deg]F, and 59 [deg]F. DOE first evaluated the accuracy 
of interpolating to a different EWT for full-load tests. For each of 
the 15 units tested, DOE conducted full-load tests to measure EER at 86 
[deg]F, 77 [deg]F, and 59 [deg]F. DOE then used the results from the 86 
[deg]F and 59 [deg]F tests to linearly interpolate to performance at 77 
[deg]F, and compared these interpolated results to the results of 
testing at 77 [deg]F. Table 3 presents a summary of the percentage 
differences between the interpolated and measured values. Positive 
values in the average, minimum, and maximum columns of Table 3 indicate 
that the values interpolated to 77 [deg]F from results measured at 86 
[deg]F and 59 [deg]F were higher than the values measured at 77 [deg]F, 
and negative values indicate the opposite.

   Table 3--Percentage Differences of Interpolated Results From Measured Results for Capacity, Power, and EER
----------------------------------------------------------------------------------------------------------------
                                                                                                      Average
                    Parameter                         Average         Minimum         Maximum     absolute value
----------------------------------------------------------------------------------------------------------------
Cooling Capacity................................            -0.2            -1.4             2.2             0.9
Total Power.....................................            -0.4            -2.6             1.5             0.8
Interpolated EER................................             2.3             0.3             4.8             2.3
EER calculated from interpolated capacity and                0.2            -1.7             2.9             1.0
 power..........................................
----------------------------------------------------------------------------------------------------------------
Note: Positive values in the average, minimum, and maximum columns indicate that the values interpolated to 77
  [deg]F from results measured at 86 [deg]F and 59 [deg]F were higher than the values measured at 77 [deg]F.
  Negative values in the average, minimum, and maximum columns indicate that the values interpolated to 77
  [deg]F from results measured at 86 [deg]F and 59 [deg]F were lower than the values measured at 77 [deg]F.

    As shown in Table 3, the interpolated values for cooling capacity 
and total power differed from the corresponding tested values by an 
average of less than 1 percent. Therefore, DOE has determined that 
interpolating capacity and total power results in representative values 
of capacity and total power, respectively. However, the interpolated 
EER value at 77 [deg]F was higher than the tested EER value at 77 
[deg]F for all tested units, with an average difference of 2.3 percent 
(ranging from 0.3 percent to 4.8 percent higher). Because of the 
consistent bias in the results showing interpolated EER higher than 
tested

[[Page 53315]]

EER,\17\ DOE considered an alternate approach of calculating EER based 
on interpolated values of cooling capacity and total power rather than 
interpolating EER directly. The bottom row of Table 3 shows the results 
of calculating EER at 77 [deg]F using the interpolated values of 
cooling capacity and total power. As shown in in the bottom row of 
Table 3, calculating EER at 77 [deg]F using interpolated values of 
cooling capacity and total power resulted in EER values that were on 
average 0.2 percent higher than the tested EER value at 77 [deg]F 
(ranging from 1.7 percent lower to 2.9 percent higher). Because 
determining EER by interpolating cooling capacity and total power 
results in closer agreement to tested values than directly 
interpolating EER (and does not consistently bias results toward higher 
interpolated EER values), DOE used the former approach in the 
calculation of IEER values discussed in the following paragraphs.
---------------------------------------------------------------------------

    \17\ As presented in Table 3, the results from DOE's testing 
show that that linear interpolation across EWT results in close 
agreement for cooling capacity and total power. Because EER = 
Cooling Capacity/Total Power, if linear equations are used to 
represent the relationship between cooling capacity and EWT, as well 
as between total power and EWT, the resulting equation for EER has 
equations linearly dependent on EWT in the numerator and 
denominator. Such an equation simplifies to an inverse function 
(i.e., the variable (EWT) is in the denominator), which is concave 
up (i.e., the slope of the EER vs EWT curve increases with 
increasing EWT), such that between any two points on the curve, the 
curve is always below a line drawn between the two points. 
Therefore, calculating EER by linearly interpolating EER values 
across EWT consistently results in an interpolated EER value that is 
higher than the EER value measured by testing or determined by 
linearly interpolating cooling capacity and total power.
---------------------------------------------------------------------------

    For determining IEER for single-stage units, this interpolation and 
extrapolation approach would be used to determine EER at the EWTs for 
all 4 IEER points, and the EER results for the part-load points (i.e., 
test points designated as B, C, and D in AHRI 340/360-2022) would also 
be adjusted for cyclic degradation (see discussion in section III.F.2.b 
of this document).
    For two-stage and variable-speed WSHPs, DOE evaluated a method that 
tests at the minimum compressor speed at the EWTs specified in Table 1 
of ISO 13256-1:1998 for part-load tests (i.e., at 86 [deg]F, 68 [deg]F, 
and 59 [deg]F). As with the draft AHRI 600 method, the method evaluated 
by DOE then provides for interpolating to the IEER liquid inlet 
temperatures from these part-load tests, and IEER is determined using 
interpolated results for the IEER EWTs for both full-load and part-load 
tests.\18\ To evaluate the accuracy of this methodology for calculating 
IEER for staged WSHPs, DOE conducted additional investigative testing 
on 10 of the 15 tested WSHPs (6 two-stage WSHPs and 4 variable-speed 
WSHPs). Specifically, these 10 units were tested to calculate IEER via 
the interpolation and extrapolation method (by conducting full-load and 
part-load tests at the EWTs specified in Table 1 of ISO 13256-1:1998 
and using interpolation and extrapolation to calculate IEER) and were 
tested to determine IEER per section 6.2 of AHRI 340/360-2022 by 
testing at the IEER EWTs and target load levels specified in Table 9 of 
AHRI 340/360-2022. Consistent with the discussion in the previous 
paragraphs, when interpolating to determine performance at a different 
EWT for a given compressor stage for staged units, DOE calculated the 
EER values by interpolating and extrapolating values of cooling 
capacity and total power, rather than directly interpolating and 
extrapolating values of EER. Table 4 presents a summary of the results. 
Positive values in the average, minimum, and maximum columns of Table 4 
indicate that the IEER values determined via the interpolation and 
extrapolation method were higher than the IEER values determined 
through testing at the EWTs and load levels specified in section 6.2 of 
AHRI 340/360-2022, and negative values indicate the opposite.
---------------------------------------------------------------------------

    \18\ After interpolating the full-load and part-load 
interpolated across EWT, the AHRI 340/360-2022 IEER calculation 
methodology is then used. The interpolated results would either need 
cyclic degradation (see discussion in section III.F.2.b of this 
NOPR) or interpolation across compressor staging to determine the 
specific load EER values to be used in the IEER calculation, unless 
the EWT interpolation yields a calculated percent load that meets 
the 3 percent tolerance for the respective IEER load point.

 Table 4--Percentage Differences of Interpolated IEER From Measured IEER for Two-Stage and Variable-Speed Units
----------------------------------------------------------------------------------------------------------------
                                                                                                      Average
              Capacity control type                   Average         Minimum         Maximum     absolute value
----------------------------------------------------------------------------------------------------------------
Two-Stage.......................................            -0.9            -2.7            -0.0             0.9
Variable-Speed..................................            -6.3           -13.6             0.2             6.4
----------------------------------------------------------------------------------------------------------------
Note: Positive values in the average, minimum, and maximum columns indicate that the IEER values determined via
  the interpolation and extrapolation method were higher than the IEER values determined through testing at the
  EWTs and load levels specified in section 6.2 of AHRI 340/360-2022. Negative values in the average, minimum,
  and maximum columns indicate that the IEER values determined via the interpolation and extrapolation method
  were lower than the IEER values determined through testing at the EWTs and load levels specified in section
  6.2 of AHRI 340/360-2022.

    As shown in Table 4, for the six tested two-stage WSHPs, the IEER 
values calculated using the described interpolation and extrapolation 
method were on average 0.9 percent lower than the IEER value measured 
from testing per AHRI 340/360-2022 (ranging from 0.0 percent to 2.7 
percent lower).
    For the four variable-speed units, the IEER values calculated using 
the described interpolation and extrapolation method were on average 
6.3 percent lower than the IEER value measured from testing per AHRI 
340/360-2022 (ranging from 0.2 percent higher to 13.6 percent lower). 
These results demonstrate a wider discrepancy from AHRI 340/360-2022 
results than for single-stage or two-stage WSHPs. This discrepancy is 
likely because the interpolation and extrapolation method described 
only includes testing at maximum and minimum compressor speed, whereas 
the AHRI 340/360-2022 approach includes testing at compressor speeds to 
operate at each of the part-load test points (i.e., 75 percent, 50 
percent, and 25 percent load). Therefore, for variable-speed WSHPs with 
higher EER at intermediate compressor speeds than at maximum or minimum 
compressor speeds, the interpolation and extrapolation method described 
results in a lower calculated IEER than testing at the IEER conditions 
specified in AHRI 340/360-2022, which was the case for three of the 
four tested units. While for certain tested variable-speed units 
calculating IEER via interpolation and extrapolation resulted in a 
lower IEER value, from participation in AHRI 600 committee

[[Page 53316]]

meetings, DOE understands that many manufacturers would prefer the 
option to use the interpolation and extrapolation method for variable-
speed WSHPs even if it results in lower IEER ratings, because it would 
result in less overall testing burden than testing at each of the AHRI 
340/360-2022 conditions.
    Based on the investigative testing conducted, DOE has tentatively 
concluded that determining IEER via interpolation and extrapolation 
from testing at the ISO 13256-1:1998 EWTs (in accordance with DOE's 
proposed test procedure), similar to the method in the draft AHRI 600, 
provides appropriately representative results that are comparable to 
testing at the EWTs (and for staged units, load levels) specified in 
Table 9 of AHRI 340/360-2022. Therefore, DOE is proposing in section 5 
of the proposed appendix C1 to allow that IEER for WSHPs can be 
calculated from either of two methods: (1) ``option 1''--testing in 
accordance with AHRI 340/360-2022 (at EWTs of 85 [deg]F, 73.5 [deg]F, 
62 [deg]F, and 55 [deg]F); or (2) ``option 2''--interpolation and 
extrapolation of cooling capacity and power values based on testing in 
accordance with the proposed test procedure at EWTs of 86 [deg]F, 77 
[deg]F, and 59 [deg]F for full-load tests and (for staged units) EWTs 
of 86 [deg]F, 68 [deg]F, and 59 [deg]F for part-load tests. For single 
speed units, option 2 would require three full-load tests at entering 
liquid temperatures of 86 [deg]F, 77 [deg]F, and 59 [deg]F. For two-
stage and variable-speed units, three additional tests at the minimum 
compressor speed would be required, at entering liquid temperature of 
86 [deg]F, 68 [deg]F, and 59 [deg]F.
    Specifically for option 2, aside from the EWTs, the tests for 
option 2 would be performed using the same test provisions from AHRI 
340/360-2022, ANSI/ASHRAE 37-2009, and sections 2 through 4 and 7 of 
proposed appendix C1 as the tests for option 1. As discussed, DOE has 
tentatively determined that results from the interpolation and 
extrapolation method have greater agreement with, and, therefore, are 
comparably representative to, the tested results by interpolating 
values of cooling capacity and total power rather than interpolating 
values of EER; therefore, DOE is proposing that the alternative method 
specify interpolation using the cooling capacity and total power. The 
proposed provisions for option 2 in section 5.1.2 of proposed appendix 
C1 are otherwise generally consistent with the draft AHRI 600 method, 
except for the cyclic degradation approach, which is discussed in 
section III.F.2.b of this NOPR.
    DOE notes that representations for WSHPs can be made either based 
on testing (in accordance with 10 CFR 429.43(a)(1)) or AEDMs (in 
accordance with 10 CFR 429.43(a)(2)). If represented values for a basic 
model are determined with an AEDM, the AEDM could use either option 1 
or option 2 for determining IEER per the proposed test procedure in 
appendix C1.
    Issue 4: DOE requests comment on the proposal to allow 
determination of IEER using two different methods: (1) testing in 
accordance with AHRI 340/360-2022; or (2) interpolation and 
extrapolation of cooling capacity and power values based on testing in 
accordance with the proposed test procedure at the EWTs specified in 
Table 1 of ISO 13256-1:1998. Specifically, DOE seeks feedback on the 
proposed method for calculating IEER via interpolation and 
extrapolation, and on whether this approach would serve as a potential 
burden-reducing option as compared to testing at the AHRI 340/360-2022 
conditions.
    Issue 5: DOE requests comment on whether the proposed methodology 
to determine IEER based on interpolation and extrapolation is 
appropriate for variable-speed units. DOE would consider requiring 
variable-speed equipment be tested only according to AHRI 340/360-2022 
and, thus, testing physically at the IEER EWTs, if suggested by 
commenters.
    DOE is aware that ISO 13256-1:2021 includes changes from ISO 13256-
1:1998 with respect to the EWTs specified for cooling tests. 
Specifically, Table 2 of ISO 13256-1:2021 specifies full-load cooling 
temperatures of 86 [deg]F, 68 [deg]F, and 50 [deg]F, and part-load 
cooling temperatures of 77 [deg]F, 59 [deg]F, and 41 [deg]F. Consistent 
with the draft AHRI 600 method, DOE is proposing to use the 
temperatures specified in Table 1 of ISO 13256-1:1998 for option 2 
tests; however, it is expected that the results under the proposed 
interpolation and extrapolation method would provide comparable results 
using the EWTs specified in Table 2 of ISO 13256-1:2021.
    Issue 6: DOE seeks feedback on whether the proposed interpolation 
and extrapolation method should be based on testing at the ISO 13256-
1:2021 EWTs.
2. COP
a. General Discussion
    DOE's current test procedure for WSHPs measures heating-mode 
performance in terms of the COP metric, based on testing with a 68 
[deg]F EWT. 10 CFR 431.96. For the reasons explained in the following 
paragraphs, DOE is proposing in section 6.2 of proposed appendix C1 to 
use an EWT of 55 [deg]F for the COP metric because DOE has tentatively 
concluded that 55 [deg]F is more representative of field operation than 
the current EWT of 68 [deg]F.
    COP is a full-load heating efficiency metric for WSHP water-loop 
applications, meaning that it represents the heating efficiency for a 
WSHP operating at its maximum capacity at an EWT that is typical of 
heating operation in water-loop applications. Because commercial 
buildings served by WSHPs in water-loop applications are typically 
cooling-dominated, DOE understands that the majority of heating hours 
in these applications occur in simultaneous cooling and heating 
operation--in which certain WSHPs (e.g., servicing zones around the 
perimeter of the building) are in heating mode while other WSHPs (e.g., 
servicing interior zones closer to the center of the building) are in 
cooling mode. Because all WSHPs in the system loop are provided water 
with the same EWT, at any given time, WSHPs that are in heating mode 
operate at the same EWT as WSHPs in cooling mode. As discussed in 
section III.E.1.a of this NOPR, from manufacturer feedback provided in 
AHRI 600 committee meetings, DOE understands that while in the past 
water-loop temperatures were maintained at temperatures above 60 [deg]F 
via heat provided by a system boiler, in current practice, WSHP 
installations are typically controlled to allow water-loop temperatures 
to drop to temperatures closer to 50 [deg]F. Correspondingly, DOE is 
proposing part-load IEER EWTs that align with AHRI 340/360-2022 and the 
draft AHRI 600, including 62 [deg]F for the 50-percent load point and 
55 [deg]F for the 25-percent load point.
    Because DOE understands that WSHP water-loop temperatures are 
typically controlled to drop closer to 50 [deg]F (as represented by the 
55 [deg]F EWT for the 25-percent load point), the Department 
understands that most hours of heating mode operation for WSHPs in 
water-loop applications occur with EWTs closer to 50 [deg]F. Therefore, 
while the current 68 [deg]F EWT for the COP metric may have been more 
representative of how WSHP systems were controlled in the past (i.e., 
with a boiler maintaining water-loop temperatures above 60 [deg]F), DOE 
has tentatively determined that the COP EWT should be no higher than 
the lowest EWT used in the IEER metric, which is 55 [deg]F (for the 25-
percent load point), because most heating hours occur when outdoor air 
temperatures are lower and, thus, cooling loads are

[[Page 53317]]

lower. Therefore, DOE has tentatively concluded that the COP metric 
would be more representative of water-loop WSHP applications if based 
on an EWT of 55 [deg]F.
    DOE also considered whether an EWT below 55 [deg]F, specifically 50 
[deg]F, might be more representative for determining COP, depending 
upon typical heating conditions for water-loop WSHPs. However, DOE 
currently lacks data or evidence indicating that 50 [deg]F would be a 
more representative heating EWT than 55 [deg]F for WSHPs. Therefore, in 
the absence of any data suggesting a lower EWT would be more 
representative of heating operation of WSHPs, DOE is proposing an EWT 
of 55 [deg]F, which aligns with the lowest IEER EWT as proposed.
    Issue 7: DOE seeks comment and data on the representativeness of 55 
[deg]F as the EWT condition for determining COP. Specifically, DOE 
requests feedback and data on whether a lower EWT, such as 50 [deg]F, 
would be more representative of heating operation of WSHPs. DOE will 
further consider any alternate EWT suggested by comments in developing 
any final rule.
    Additionally, DOE is proposing provisions in section 6.3 of 
proposed appendix C1 to provide for optional representations of COP 
based on testing conducted per the proposed test procedure (sections 2 
through 4 and 7 of proposed appendix C1) at the full-load and part-load 
EWT conditions specified in Table 2 of ISO 13256-1:1998 (i.e., 68 
[deg]F, 50 [deg]F, 41 [deg]F, and 32 [deg]F).
b. Determination of COP Via Interpolation
    As discussed in section III.E.1.b of this NOPR, DOE is proposing to 
include an alternate method for determining IEER that allows 
manufacturers to perform tests at the EWTs in Table 1 of ISO 13256-
1:1998 and interpolate efficiency metrics to the EWTs specified in 
Table 9 of AHRI 340/360-2022. This method would reduce overall testing 
burden for manufacturers who choose to make optional EER 
representations at the EWTs specified in Table 1 of ISO 13256-1:1998, 
by allowing them to avoid additional testing at the IEER EWTs.
    In order to provide comparable flexibility for measuring COP, DOE 
is proposing a similar alternative test method in section 6.2.2 of 
appendix C1 for determining COP by interpolation from results of 
testing at the EWTs specified in Table 2 of ISO 13256-1:1998. To 
evaluate the interpolation method for COP, DOE conducted investigative 
testing on five WSHPs at the three heating EWTs specified in Table 1 of 
ISO 13256-1:1998: 68 [deg]F, 50 [deg]F and 32 [deg]F. DOE interpolated 
the cooling capacity and total power results from 68 [deg]F and 32 
[deg]F to 50 [deg]F, and then calculated COP at 50 [deg]F using the 
interpolated values of cooling capacity and total power.\19\ Finally, 
DOE compared these interpolated values to the results of testing at 50 
[deg]F. Table 5 presents a summary of the percentage differences 
between the interpolated and measured values. Positive values in the 
average, minimum, and maximum columns of Table 5 indicate that the 
values interpolated to 50 [deg]F from results measured at 68 [deg]F and 
32 [deg]F were higher than the values measured at 50 [deg]F, and 
negative values indicate the opposite.
---------------------------------------------------------------------------

    \19\ As discussed in section III.E.1.b of this NOPR, DOE 
tentatively determined that interpolation of EER directly results in 
a consistent bias, and that more representative results are obtained 
by calculating EER using interpolated values of cooling capacity and 
total power. Similarly, for COP, DOE is proposing that COP can be 
determined using interpolated values of heating capacity and total 
power, rather than interpolating COP values directly.

   Table 5--Percentage Differences of Interpolated Results From Measured Results for Capacity, Power, and COP
----------------------------------------------------------------------------------------------------------------
                                                                                                      Average
                    Parameter                         Average         Minimum         Maximum     absolute value
----------------------------------------------------------------------------------------------------------------
Cooling Capacity................................            -0.4            -1.9             0.6             0.9
Total Power.....................................             0.3            -1.2             2.1             0.9
COP calculated from interpolated capacity and               -0.7            -3.9             0.9             1.1
 power..........................................
----------------------------------------------------------------------------------------------------------------
Note: Positive values in the average, minimum, and maximum columns indicate that the values interpolated to 50
  [deg]F from results measured at 68 [deg]F and 32 [deg]F were higher than the values measured at 50 [deg]F.
  Negative values in the average, minimum, and maximum columns indicate that the values interpolated to 50
  [deg]F from results measured at 68 [deg]F and 32 [deg]F were lower than the values measured at 50 [deg]F.

    As shown in Table 4, the COP calculated from interpolated values of 
cooling capacity and total power differed from measured COP by an 
average of less than 1 percent. Therefore, DOE has tentatively 
concluded that determining COP via interpolation in this temperature 
range from testing at the ISO 13256-1:1998 EWTs (in accordance with 
DOE's proposed test procedure) provides appropriately representative 
results that are comparable to testing at 55 [deg]F. Therefore, DOE is 
proposing in section 6.2 of the proposed appendix C1 to allow that COP 
for WSHPs can be calculated from either of two methods: (1) ``option 
A''--testing at 55 [deg]F; or (2) ``option B''--interpolation of 
heating capacity and power values based on testing in accordance with 
the proposed test procedure at EWTs of 50 [deg]F and 68 [deg]F. Aside 
from the EWTs, the tests for option B would be performed using the same 
test provisions from AHRI 340/360-2022, ANSI/ASHRAE 37-2009, and 
sections 2 through 4 and 7 of proposed appendix C1 as the tests for 
option A.
    Issue 8: DOE requests comment on the proposal to allow 
determination of COP using two different methods: (1) testing at 55 
[deg]F; or (2) interpolation of heating capacity and power values based 
on testing in accordance with the proposed test procedure at EWTs 
specified for heating tests in Table 2 of ISO 13256-1:1998 (i.e., 50 
[deg]F and 68 [deg]F). Specifically, DOE seeks feedback on the proposed 
method for calculating COP via interpolation, and on whether this 
approach would serve as a potential burden-reducing option as compared 
to testing at 55 [deg]F.
3. Entering Air Conditions
    The current DOE test procedure references ISO 13256-1:1998, which 
specifies in Table 1 that EER is measured with entering air at 27 
[deg]C (80.6 [deg]F) dry-bulb temperature and 19 [deg]C (66.2 [deg]F) 
wet-bulb temperature and in Table 2 that COP is measured with entering 
air at 20 [deg]C (68 [deg]F) dry-bulb temperature and 15 [deg]C (59 
[deg]F) wet-bulb temperature. Table 2 and Table 3 of ISO 13256-1:2021 
specify the same entering air conditions as ISO 13256-1:1998. As

[[Page 53318]]

discussed in section III.D.3 of this NOPR, DOE proposes to adopt AHRI 
340/360-2022 as the test procedure for WSHPs. Table 6 of AHRI 340/360-
2022 specifies entering indoor air conditions for standard rating 
cooling tests to be 80 [deg]F dry-bulb temperature and a maximum of 67 
[deg]F wet-bulb temperature and standard rating heating tests to be 70 
[deg]F dry-bulb temperature and a maximum of 60 [deg]F wet-bulb 
temperature.
    The entering air conditions specified in AHRI 340/360-2022 are 
similar to the conditions specified in ISO 13256-1:1998 and ISO 13256-
1:2021, differing for cooling by 0.6 [deg]F for dry-bulb temperature 
and 0.8 [deg]F for wet-bulb temperature and for heating by 2 [deg]F for 
dry-bulb temperature and 1 [deg]F for wet-bulb temperature. DOE 
surmises that these differences are likely due to the conditions in ISO 
13256-1 (1998 and 2021 versions) being specified in terms of degrees 
Celsius, whereas the conditions in AHRI 340/360-2022 are specified in 
degrees Fahrenheit. The entering air conditions specified in AHRI 340/
360-2022 are the same as in previous versions of AHRI 340/360, 
including AHRI 340/360-2007, which is referenced in the current DOE 
test procedure for CUAC/HPs. Further, the most common application for 
WSHPs (and the application DOE understands that the WSHP industry is 
intending to represent via use of the IEER metric in AHRI 600) is 
commercial buildings, similar to CUAC/HPs. Therefore, DOE has 
tentatively determined that the entering air conditions in AHRI 340/
360-2022 are appropriately representative of the average conditions in 
which WSHPs operate in the field. DOE is proposing in sections 5 and 6 
of proposed appendix C1 to use entering air conditions from Table 6 of 
AHRI 340/360-2022 for both cooling (IEER) and heating (COP) tests.
    Issue 9: DOE requests comment on its proposal to specify in 
proposed appendix C1 use of the cooling entering air conditions from 
AHRI 340/360-2022 (i.e., 80 [deg]F dry-bulb temperature and 67 [deg]F 
wet-bulb temperature) and the heating entering air conditions from AHRI 
340/360-2022 (i.e., 70 [deg]F dry-bulb temperature and a maximum of 60 
[deg]F wet-bulb temperature).
4. Operating Modes Other Than Mechanical Cooling and Heating
    On April 1, 2015, DOE published in the Federal Register a 
notification of its intent to establish a working group under the 
Appliance Standards and Rulemaking Federal Advisory Committee 
(``ASRAC'') Commercial and Industrial Fans and Blowers Working Group 
(``ASRAC Working Group'') to discuss and, if possible, reach consensus 
on the scope of the rulemaking, certain key aspects of a proposed test 
procedure, and proposed energy conservation standard for fans and 
blowers. 80 FR 17359. The ASRAC Working Group term sheet for commercial 
and industrial fans and blowers was approved (Docket No. EERE-2013-BT-
STD-0006-0179).\20\ Recommendation #3 of the term sheet addressed 
supply and condenser fans that are embedded in certain covered 
equipment. (Id. at p. 3) The ASRAC Working Group recommended that DOE 
consider revising efficiency metrics that include energy use of supply 
fans in order to include the energy consumption during all relevant 
operating modes (e.g., auxiliary heating mode, ventilation mode, and 
part-load operation) in the next round of test procedure rulemakings. 
(Id. at p. 4) The ASRAC Working Group included WSHPs in its list of 
regulated equipment for which fan energy use should be considered. (Id. 
at p. 16)
---------------------------------------------------------------------------

    \20\ Available at: <a href="http://www.regulations.gov/document/EERE-2013-BT-STD-0006-0179">www.regulations.gov/document/EERE-2013-BT-STD-0006-0179</a>.
---------------------------------------------------------------------------

    As part of the June 2018 RFI, DOE stated that it was investigating 
whether changes to the WSHP test procedure are needed to properly 
characterize a representative average use cycle, including changes to 
more accurately represent fan energy use in field applications. 83 FR 
29048, 29050 (June 22, 2018). DOE requested information as to the 
extent that accounting for the energy use of fans in commercial 
equipment such as WSHPs would be additive of other existing accountings 
of fan energy use. Id.
    In the June 2018 RFI, DOE also sought comment on whether accounting 
for the energy use of fan operation in WSHPs would alter measured 
efficiency, and if so, to what extent. Id. DOE also requested data and 
information regarding what forms of auxiliary heating are installed in 
WSHPs, how frequently they operate, and whether they operate 
independently of the WSHP. Id. Additionally, DOE requested data and 
information on how frequently WSHP supply fans are operated when there 
is no demand for heating or cooling, such as for fresh air ventilation 
or air circulation or filtration. Id.
    The Joint Advocates and NEEA commented that DOE should amend the 
test procedure to account for fan energy use outside of mechanical 
cooling and heating for fans in regulated equipment to more fully 
capture fan energy use. (Joint Advocates, No. 10 at p. 1; NEEA, No. 11 
at p. 1) The Joint Advocates asserted that by failing to capture fan 
operation for economizing, ventilation, and other functions outside of 
cooling mode, the test procedure may be significantly underestimating 
fan energy consumption. (Joint Advocates, No. 10 at p. 1)
    NEEA commented that the commercial prototype building models used 
by Pacific Northwest National Laboratory in the analysis in support of 
ASHRAE Standard 90.1 include information on the operation of fans in 
ventilation mode and economizer mode and could be used to develop 
national average fan operating hours outside of heating and cooling. 
(NEEA, No. 11 at pp. 3) Furthermore, NEEA stated that the vast majority 
of WSHPs are installed in commercial buildings, thereby subjecting them 
to ASHRAE Standard 90.1 code requirements such as the requirement of 
water side economizers in many U.S. climate zones. Id. NEEA added that 
details of requirements for certain control and component features are 
provided in ASHRAE Standard 90.1 and should be an indicator of 
prevalence of these features in WSHPs on the market. Id.
    NEEA further stated that ANSI and the Air Movement Control 
Association (``AMCA'') developed ANSI/AMCA 208-18, ``Calculation of the 
Fan Energy Index,'' which provides a potential way to measure embedded 
fan performance in WSHPs using the fan energy index (``FEI''). 
According to NEEA, DOE could develop a revised IEER-type metric that 
weighs together cooling performance (using the IEER test) and fan 
efficiency (using an FEI-based metric). NEEA argued that accounting for 
the energy use of fan operation in WSHPs does not need to alter 
measured efficiency, and that to reduce burden on manufacturers, DOE 
could combine the FEI and IEER metrics such that manufacturers would 
have multiple viable design option pathways to achieve the minimum IEER 
efficiency standard without improving the embedded fan efficiency above 
the minimum FEI efficiency standard. (NEEA, No. 11 at p. 2)
    Trane commented that there are some applications in which a WSHP 
would be used for ventilation, but that ventilation is not the main 
use, and that using a WSHP for purposes other than heating and cooling 
is rare. Trane stated further that typical practice is for ventilation 
air to be provided by a dedicated outdoor air system (``DOAS'') using a 
separate ductwork system, whereas the WSHP system provides the heating 
and cooling. Finally, Trane commented that for installations in which 
the DOAS and WSHPs supply to common ductwork, WSHP fans would operate 
when

[[Page 53319]]

ventilation is needed, but rarely would this be needed without heating 
or cooling. (Trane, No. 8 at pp. 2, 5)
    AHRI and WaterFurnace both stated that a high percentage of WSHP 
systems offer a continuous fan mode to circulate fresh air but did not 
have data on how often. (AHRI, No. 12 at pp. 4-5; WaterFurnace, No. 7 
at p. 3) However, both estimated that a typical WSHP would operate in 
continuous fan mode (i.e., without cooling or heating) for 
approximately 1,300 hours per year. The commenters estimated total 
cooling and heating mode operation of 3,300 hours per year. (AHRI, No. 
12 at pp. 9; WaterFurnace, No. 7 at p. 9)
    Further, AHRI and WaterFurnace commented that fan power is largely 
dependent on motor type and typically represents 13 to 18 percent of 
total power. (AHRI, No. 12 at pp. 4, 8-9; WaterFurnace, No. 7 at pp. 3, 
8-9) AHRI asserted that EPCA imposes a one-metric-per-product 
limitation and that efforts to capture the energy use of a fan during a 
mode other than cooling (or heating) would result in an impermissible 
design requirement. (AHRI, No. 12 at pp. 5, 10)
    AHRI stated that DOE has the authority to include certain fans and 
blowers, by rule, as ``covered equipment'' if such products meet all 
the requirements of EPCA at 42 U.S.C. 6311(2). AHRI asserted that if 
DOE developed a standard for stand-alone industrial fans, it would not 
be appropriate to apply that standard to fans embedded in regulated 
equipment. Furthermore, AHRI argued that the fact that Congress granted 
a specific provision of authority to DOE for a consumer furnace 
ventilation metric affirms that DOE is without general authority to 
create overlapping ventilation requirements for other regulated 
products. (AHRI, No. 12 at pp. 10-11)
    Trane and WaterFurnace also commented that regulation of WSHP fans 
would produce unnecessary overlapping regulations, and that system-
level efficiency metrics allow for optimization of the entire system. 
(Trane, No. 8 at p. 4; WaterFurnace, No. 7 at p. 8) AHRI and 
WaterFurnace stated that fan energy in cooling and heating are 
accounted for in the current test procedure and that fans are optimized 
for these modes because they account for the majority of operational 
time. (AHRI, No. 12 at p. 8; WaterFurnace, No. 7 at p. 9)
    AHRI and WaterFurnace commented that auxiliary heating is not 
common in WSHPs and estimated that electric heat is included in less 
than one percent of WSHP shipments. AHRI and WaterFurnace further 
commented that the primary mode of operation of most WSHPs is cooling 
and that heating requirements are limited, such that adequate heating 
can be supplied through heat pump operation alone. (AHRI, No. 12 at p. 
4; WaterFurnace, No. 7 at p. 3) Trane stated that for their WSHPs, 
electric heat is provided only when heat pump operation alone cannot 
meet the heating demand. Trane further stated that the compressors are 
locked out while back-up electric heating is used for most WSHPs, with 
the exception of rooftop WSHP equipment, which allows auxiliary 
electric heat to supplement the heating provided by the heat pump. 
(Trane, No. 8 at p. 2)
    In response, DOE emphasizes that its request for information 
regarding fan energy use was in investigation of energy use of WSHPs in 
operational modes other than those currently evaluated by the test 
procedure (i.e., operational modes other than cooling and heating). DOE 
understands that much of the energy use attributable to these other 
modes is likely a product of fan operation. Provisions to measure 
energy use for ancillary functions (e.g., economizing, ventilation, 
filtration, and auxiliary heat) when there is no heating or cooling are 
not included in ISO 13256-1:1998 or AHRI 340/360-2022. As discussed in 
section III.D.3 of this NOPR, DOE is proposing to adopt AHRI 340/360-
2022 for testing WSHPs. Additionally, provisions addressing other 
operational modes have not been included in the updated ISO 13256-
1:2021. In light of the above, at this time, DOE lacks sufficient 
information on the number of units capable of operating in these other 
modes or the frequency of operation of these modes during field 
conditions to determine whether such testing would be appropriate for 
WSHPs and/or to develop a test method capable of accounting for energy 
use of such auxiliary functions of WSHPs. To the extent that data and 
further information are developed regarding operation of WSHPs in modes 
other than mechanical cooling and heating, DOE would consider such 
developments in a future WSHP test procedure rulemaking.
5. Dynamic Load-Based Test Procedure
    In response to the June 2018 RFI, both NEEA and the Joint Advocates 
encouraged DOE to investigate a load-based test method that could allow 
more sophisticated and inclusive efficiency metrics. Both NEEA and 
Joint Advocates commented that the Canadian Standards Association 
(``CSA'') group is developing CSA EXP07 (``Load-based and climate-
specific testing and rating procedures for heat pumps and air 
conditioners''), which is a dynamic, load-based test procedure expected 
to better capture performance in the field, including the capturing of 
cycling losses, benefits of variable-speed operation, and importance of 
control strategies. (NEEA, No. 11 at p. 2; Joint Advocates, No. 10 at 
p. 2)
    DOE is aware of the dynamic, load-based test procedure being 
developed by CSA. However, at this time, DOE understands that CSA EXP07 
has not been validated and finalized. Furthermore, the CSA EXP07 test 
procedure is applicable to CAC/HPs, and that test procedure has not yet 
been evaluated for WSHPs. Further, DOE is not aware of data showing 
that any dynamic, load-based test procedure produces repeatable and 
reproducible test results. Therefore, DOE has tentatively concluded 
that further consideration of CSA EXP07 would be premature at this 
time, and accordingly, the Department is not proposing to adopt any 
dynamic, load-based test procedures in this NOPR.

F. Test Method

1. Airflow and External Static Pressure
a. Fan Power Adjustment and Required Air External Static Pressure
    As discussed in section III.D.1.a of this NOPR, for ducted units, 
sections 4.1.3.1 and 4.1.3.2 of ISO 13256-1:1998 specify a fan power 
adjustment calculation that does not account for fan power used for 
overcoming external resistance. As a result, the calculation of 
efficiency includes only the fan power required to overcome the 
internal resistance of the unit. In addition, ISO 13256-1:1998 does not 
specify ESP requirements for ducted equipment, instead allowing 
manufacturers to specify a rated ESP. While Table 9 of ISO 13256-1:1998 
includes an operating tolerance (i.e., maximum variation of individual 
reading from rating conditions) and a condition tolerance (i.e., 
maximum variation of arithmetical average values from specified test 
conditions) for external resistance to airflow, the test standard does 
not specify to which values of ESP these tolerances are intended to 
apply.
    In the June 2018 RFI, DOE requested comment on whether minimum ESP 
requirements should be included for ducted WSHPs, and if so, what 
values would be appropriate. 83 FR 29048, 29050 (June 22, 2018). DOE 
also requested information on whether field ESP values typically vary 
with capacity, and whether fan power used for overcoming ESP should be 
included in the efficiency calculation for WSHPs

[[Page 53320]]

intended to be used with ducting. Id. DOE asked for comment and data on 
whether the fan/motor efficiency factor used in the calculation of fan 
power for WSHPs is representative of units currently on the market and 
whether the value accurately represents the efficiency of existing fans 
that are not replaced in WSHP installations. Id at 83 FR 29051. 
Additionally, DOE requested comment on whether indoor fans are 
typically replaced when coil-only WSHPs are installed. Id.
    In response to DOE's request for information, the Joint Advocates 
encouraged DOE to establish minimum ESP values for ducted equipment and 
to include the fan power used for overcoming external resistance in 
efficiency calculations for WSHPs. (Joint Advocates, No. 10 at pp. 1-2) 
NEEA commented that representative ESPs for WSHPs are higher than zero 
ESP, and the commenter recommended that DOE should ensure the WSHP ESP 
requirements reflect field installations, stating that otherwise, WSHP 
ratings will neither provide an adequate representation of actual 
efficiency nor provide good information to consumers. (NEEA, No. 11 at 
p. 3) NEEA also reminded that the ASRAC Working Group recommended that 
test procedures for regulated equipment, including WSHPs, be revised to 
better capture fan energy use. NEEA further commented that adding 
minimum ESP values would not increase test burden. Id.
    AHRI, Trane, and WaterFurnace stated that the AHRI WSHP 
certification program does require minimum ESPs that increase with 
rated capacity for ducted units with fans driven by an electronically-
commutated motor (``ECM''), and that these minimum ESPs are being 
considered for inclusion in the revised version of ISO 13256-1. (AHRI, 
No. 12 at pp. 5-6; Trane, No. 8 at p. 3; WaterFurnace, No. 7 at p. 5) 
AHRI and WaterFurnace commented that the field ESP of commercial WSHPs 
is largely tied to the ductwork and a single filter, typically 
resulting in ESPs less than 0.50 inches water column (``in 
H<INF>2</INF>O''), but the commenters noted that some larger systems 
(>60,000 Btu/h) may be installed such that ESP values are as much as 
1.0 in H<INF>2</INF>O. (AHRI, No. 12 at p. 5; WaterFurnace, No. 7 at p. 
4) AHRI also mentioned that commercial WSHPs are not typically 
installed with substantial ancillary filters or other high-static 
accessories found in larger air handlers. (AHRI, No. 12 at p. 5)
    Trane and AHRI commented that fan power for overcoming ESP should 
not be included in the efficiency calculation. (AHRI, No. 12 at p. 6; 
Trane, No. 8 at pp. 2-3) AHRI further commented that the ISO 13256-
1:1998 approach (of including a fan power adjustment down to zero ESP) 
results from the acknowledgment of the variability of ESP in the wide 
variety of WSHP applications that range from cooling towers/boilers to 
dry coolers to geothermal earth loop systems. (AHRI, No. 12 at p. 5) 
Trane and WaterFurnace further commented that excluding the fan power 
for overcoming ESP from the efficiency calculation ensures that units 
with indoor fans that produce higher static pressure are not penalized 
for having a stronger fan motor. (Trane, No. 8 at pp. 2-3; 
WaterFurnace, No. 7 at p. 4) WaterFurnace added that because more 
powerful fans to overcome higher field ESPs results in lower certified 
efficiency, most manufacturers design to the minimum ESP to avoid the 
excess fan power, and that in field applications, this results in low 
airflow and poor performance. WaterFurnace commented that their typical 
WSHP product is tested at higher ESP (greater than 0.4 in 
H<INF>2</INF>O) but then corrected to zero ESP. (WaterFurnace, No. 7 at 
pp. 1, 4) AHRI stated that fewer than 10 percent of all installed WSHPs 
have a cooling capacity greater than 5 tons, and the organization 
further noted that the table of ESP requirements in AHRI WSHP/
Geothermal Operations Manual specifies an ESP of 0.20 in H<INF>2</INF>O 
for 5-ton models, suggesting that 90 percent of WSHPs would have an ESP 
less than 0.2 in H<INF>2</INF>O. (AHRI, No. 12 at p. 8)
    AHRI and WaterFurnace commented that the AHRI WSHP/Geothermal 
Operations Manual limits the fan power correction to three percent on 
the cooling capacity to prevent any application of the correction as a 
way to inflate efficiencies. (AHRI, No. 12 at p. 8; WaterFurnace, No. 7 
at p. 8) AHRI and WaterFurnace further commented that aligning ESP 
requirements for different equipment categories (with different 
conditions and applications) is futile and that there will always be 
differences in HVAC test standards. (AHRI, No. 12 at p. 8; 
WaterFurnace, No. 7 at p. 7) AHRI, Trane, and WaterFurnace stated that 
the fan power adjustment factor in ISO 13256-1:1998 is representative 
for WSHPs. (AHRI, No. 12 at p. 8; Trane, No. 8 at p. 4; WaterFurnace, 
No. 7 at p. 8) AHRI, Trane, and WaterFurnace also stated that the fan 
power adjustment factor provides the ability to predict performance at 
any ESP level. (AHRI, No. 12 at p. 3; Trane, No. 8 at p. 3; 
WaterFurnace, No. 7 at p. 5)
    AHRI and WaterFurnace also stated that the fan efficiency factor 
noted in the RFI is the same for all current fan motor designs, both 
permanent magnet variable speed and induction technologies, and they 
have found them to be reasonable. (AHRI, No. 12 at p. 8; WaterFurnace, 
No. 7 at p. 7) WaterFurnace further stated that the fan and pump 
correction factors were developed in 1998 after high-efficiency 
permanent split capacitor (``PSC'') and ECM fan motor technology were 
both deployed into the market and that the factor is intended to cover 
a number of technologies. (WaterFurnace, No. 7 at p. 7)
    Regarding whether indoor fans are typically replaced when coil-only 
WSHPs are installed, AHRI and WaterFurnace commented that they are not 
aware of any coil-only WSHPs, and, therefore, that test procedure 
revisions to address such units are unnecessary. (AHRI, No. 12 at p. 8; 
WaterFurnace, No. 7 at p. 8) AHRI and WaterFurnace also stated that all 
commercial WSHPs are packaged units and that split systems are not 
commercially used. Id.
    In response to those comments on the June 2018 RFI, DOE would 
clarify that ducted WSHPs installed in the field must overcome ESP from 
ductwork. As noted, the method used in ISO 13256-1:1998 and ISO 13256-
1:2021 excludes the power to overcome ESP via the fan power adjustment, 
which adjusts the fan power down to reflect zero ESP. In contrast, 
testing per AHRI 340/360-2022 requires testing at a minimum ESP 
requirement (specified in Table 7 of AHRI 340/360-2022) and does not 
include any adjustments to the fan power. In other words, ratings in 
accordance with AHRI 340/360-2022 reflect performance at the applicable 
minimum ESP requirement. DOE has tentatively concluded that testing 
ducted WSHPs in accordance with AHRI 340/360-2022 (i.e., testing at 
minimum ESP requirements with no fan power adjustment) would be more 
representative of field installations than the method used in ISO 
13256-1:1998, for the following three reasons:
    (1) Use of the fan power adjustment in ISO 13256-1:1998 results in 
ratings that do not reflect the fan power needed to overcome ESP;
    (2) The fan power adjustment in ISO 13256-1:1998 assumes a fan 
efficiency of 0.3, which underestimates the efficiency of fans in 
WSHPs, and, thus, underestimates the fan power that would be needed for 
the fan to operate at zero ESP; and
    (3) Rated ESP values that manufacturers use when testing to ISO 
13256-1:1998 are typically significantly higher than ESPs 
representative of water-loop WSHP installations. Because, as stated, 
the fan power

[[Page 53321]]

adjustment subtracts fan power to reflect performance at zero ESP, 
assuming a low fan efficiency, testing at ESPs higher than 
representative values subtracts more fan power than would typically be 
needed to overcome that high tested ESP, and, thus, it further results 
in efficiency ratings that underestimate fan power needed to operate at 
zero ESP.
    DOE conducted investigative testing on five WSHPs to determine the 
extent to which ISO 13256-1:1998 accounts for fan energy use compared 
to testing at representative ESP requirements per AHRI 340/360-2022. 
DOE also determined the fan efficiency of these five units. Of the five 
tested units, three had constant airflow ECM motors and two had 
constant torque ECM motors.

   Table 6--Investigative Testing Results Regarding Fan Power and Fan
                               Efficiency
------------------------------------------------------------------------
 
------------------------------------------------------------------------
Fan Power at AHRI 340/360 ESP Requirement (W)...........          262.04
Fan Power Determined According to ISO 13256-1:1998 (W)..          139.57
Average Measured Fan Efficiency.........................            0.46
Measured Fan Efficiency Range...........................       0.34-0.71
------------------------------------------------------------------------

    DOE determined the relationship between ESP and fan power for the 
five WSHPs by conducting several tests with varying ESP at the rated 
airflow. As shown in Table 5, DOE determined the fan power for each of 
the five units at the applicable ESP requirement in AHRI 340/360-2022. 
These data show that the method in ISO 13256-1:1998 accounts for an 
average of only 53 percent of the fan power required to overcome the 
ESP specified in AHRI 340/360-2022.
    DOE also calculated the fan efficiency for each unit based on tests 
conducted with varying ESP at the rated airflow. As shown in Table 5, 
DOE found that the measured fan efficiency for all five units is higher 
than the fan efficiency value assumed in ISO 13256-1:1998 (30 percent). 
Specifically, the average measured efficiency (46 percent) is over 50 
percent higher than the ISO 13256-1:1998 value, and the highest 
measured efficiency is more than double the ISO 13256-1:1998 value. The 
consistent underestimation of fan efficiency by the ISO 13256-1:1998 
fan power adjustment equation for the five tested units results in a 
larger amount of fan power being subtracted from the measured value 
when adjusting down to zero ESP than would be representative of the 
actual fan's operation. In other words, when adjusting the measured fan 
power down to zero ESP, the fan power adjustment's assumption of a fan 
efficiency that is lower than is typical in WSHPs results in more power 
being subtracted than the fan would actually have needed to overcome 
that level of ESP (because lower-efficiency fans consume more power to 
provide the same level of output). Therefore, for these five units the 
resulting rating determined per ISO 13256-1:1998 underestimates the fan 
power needed to operate at zero ESP because too much fan power is 
subtracted using the fan power adjustment.
    The low fan efficiency value in the ISO 13256-1:1998 fan power 
adjustment equation results in an incentive for manufacturers to test 
at a higher ESP than would be representative for WSHPs, to take more 
advantage of the fan power adjustment by subtracting a larger 
calculated adjustment from the measured fan power (when adjusting fan 
power down to reflect performance at zero ESP). DOE's examination of 
rated ESP values in supplemental test instructions (``STI'') indicates 
that WSHPs are being rated based on testing with ESPs higher than would 
be representative. Specifically, DOE examined the STI for 15 WSHPs and 
found that the average rated ESP was 0.51 in H<INF>2</INF>O. In 
contrast, the rated ESPs in the STI exceeded the AHRI 340/360-2022 ESP 
requirements (which, as discussed, align with the ESP levels included 
in the AHRI WSHP/Geothermal Operations Manual and are very similar to 
the ESP levels in included in ISO 13256:1-2021) by more than the +0.05 
in H<INF>2</INF>O tolerance for 13 of the 15 units. Given the low fan 
efficiency assumed in the ISO 13256-1:1998 fan power adjustment, 
testing at ESPs higher than representative for WSHPs results in 
efficiency ratings that underestimate fan power needed to operate at 
zero ESP.
    Regarding comments received about ESP requirements in the revised 
version of ISO 13256-1, DOE acknowledges that Table 1 of ISO 13256-
1:2021 does include minimum ESPs for all fan motor types, and that 
those minimum ESPs are generally consistent with the values in Table 7 
of AHRI 340/360-2022, albeit with slight differences due to rounding. 
However, ISO 13256-1:2021 does not include an upper tolerance on ESP 
(i.e., tests can still be conducted at any ESP above the minimum) and 
maintains the fan power correction to adjust down to zero ESP. Again, 
DOE tentatively finds that its proposed approach based on AHRI 340/360-
2022 would produce results more representative of an average WSHP use 
cycle, so the Department is not proposing to use ISO 13256-1:2021 in 
this context.
    Because the fan power adjustment method used in ISO 13256-1:1998 
and ISO 13256-1:2021 does not capture the fan power to overcome ESP, 
and underestimates the fan power needed to operate at zero ESP for many 
units (as determined from DOE's testing and examination of rated ESPs 
from STI), DOE has tentatively concluded that ratings based on 
performance at a representative ESP requirement (as is the case in AHRI 
340/360-2022) are more representative of the total fan power that would 
be consumed in field installations.
    The minimum ESP requirements specified in Table 7 of AHRI 340/360-
2022 align with the minimum ESP requirements specified in Table B2 of 
the AHRI WSHP/Geothermal Operations Manual and are generally consistent 
with the minimum ESPs specified in Table 1 of ISO 13256-1:2021, with 
slight differences due to rounding. Based on the inclusion of similar 
minimum ESP requirements in the AHRI WSHP/Geothermal Operations Manual 
and ISO 13256-1:2021, DOE has tentatively concluded that the minimum 
ESP requirements specified in AHRI 340/360-2022 are representative of 
water-loop WSHP field installations.
    To account for the impacts of ESP typically encountered in the 
field, DOE is proposing provisions to reflect fan power to overcome a 
representative ESP when calculating efficiency. As per the discussion 
in this section and in section III.D.2 of this NOPR, DOE has 
tentatively determined that to best reflect field operation, WSHPs 
should be tested with minimum ESPs; the power for overcoming ESP should 
be included in efficiency calculations; and all equipment should be 
tested with an ESP upper tolerance. Therefore, DOE has tentatively 
determined that for WSHPs the method in AHRI 340/360-2022 is more 
representative of field energy use than the methods used in ISO 13256-
1:1998 or ISO 13256-1:2021. As such, DOE is proposing to adopt AHRI 
340/360-2022 for WSHPs, including section 6.1.3.3 and Table 7 of AHRI 
340/360-2022, which specify minimum ESPs for ducted units, a tolerance 
on ESP of -0.00/+0.05 in H<INF>2</INF>O, and no fan power adjustment. 
In the following sections (sections III.F.1.b and III.F.1.b.i of this 
document), DOE provides further detail on proposed provisions for 
setting airflow and ESP for units intended to be installed both with 
and without ducts.
    Regarding comments received about WSHPs with higher-static fan 
motors, DOE is proposing an approach for

[[Page 53322]]

representations and enforcement of units with non-standard indoor fan 
motors (i.e., more powerful fan motors intended for operation with ESPs 
higher than the ESP requirements in the test procedure). This approach 
would allow for an individual model with a non-standard indoor fan 
motor to be included in the same basic model as an individual model 
with a standard indoor fan motor, with the rating based on performance 
with the standard indoor fan motor, as long as the non-standard indoor 
fan motor has the same or better relative efficiency performance as 
compared to the standard motor. DOE has tentatively concluded that this 
proposed approach addresses the concerns raised by commenters that ESP 
requirements would penalize units with higher-static indoor fan motors. 
Section III.G.3 of this NOPR includes additional discussion on DOE's 
proposed approach for non-standard indoor fan motors.
    Regarding comments received about the AHRI WSHP/Geothermal 
Operations Manual, DOE notes that the Operations Manual is not 
incorporated by reference in the DOE test procedure and is not 
referenced in ASHRAE Standard 90.1. Therefore, the provisions included 
in the AHRI WSHP/Geothermal Operations Manual are not reflected in the 
current DOE test procedure. However, DOE has nonetheless reviewed the 
AHRI WSHP/Geothermal Operations Manual as part of its consideration of 
potential amended test procedure provisions in this NOPR. DOE notes 
that Table B2 of the AHRI WSHP/Geothermal Operations Manual does 
specify ESP requirements that align with the ESP requirements specified 
in Table 7 of AHRI 340/360-2022; however, the ESP requirements in the 
AHRI WSHP/Geothermal Operations Manual only apply to ducted units with 
ECM fan motors. DOE has tentatively concluded that specification of ESP 
requirements would provide for more representative ratings for all 
ducted WSHPs, not just units with ECM fan motors. Additionally, DOE 
notes that section A5 of the AHRI WSHP/Geothermal Operations Manual 
limits the fan power correction to no more than 3 percent of the 
measured cooling capacity. However, because the fan power correction is 
applied to both the capacity and total power when calculating EER or 
COP, the effect of a fan power correction of 3 percent on the 
calculated efficiency would be significantly more than 3 percent. 
Further, as discussed, DOE has tentatively concluded that ratings based 
on minimum ESP requirements would be more representative than ratings 
based on zero ESP (developed using the fan power correction). For these 
reasons, DOE is not proposing to incorporate by reference or otherwise 
adopt the AHRI WSHP/Geothermal Operations Manual as part of the DOE 
WSHP test procedure.
    Regarding comments received about coil-only units, DOE has 
identified at least one coil-only unit that would meet the definition 
of a WSHP. In accordance with DOE's proposal to adopt AHRI 340/360-
2022, coil-only WSHPs would be subject to the test provisions for 
setting airflow for coil-only units specified in sections 6.1.3.3 and 
6.1.3.4 of AHRI 340/360-2022.
    Issue 10: DOE requests comment on the proposal to adopt provisions 
from AHRI 340/360-2022 such that testing would be conducted within 
tolerance of the AHRI 340/360-2022 minimum ESP requirements, and 
efficiency ratings would include the fan power measured to overcome the 
tested ESP.
b. Setting Airflow and ESP
    ISO 13256-1:1998 specifies airflow rates in section 4.1.5 of that 
document, including that: (a) non-ducted heat pumps shall be tested at 
airflow rates obtained at zero ESP; (b) ducted heat pumps with internal 
fans or with designated air movers shall be tested at the airflow rates 
obtained at zero ESP or the manufacturer-specified airflow rate, 
whichever is lower, and (c) ducted heat pumps without internal fans 
shall be tested at the manufacturer-specified airflow rate subject to a 
maximum internal pressure drop. Additionally, paragraph (e)(2) of 10 
CFR 431.96 requires that the airflow rate used for testing must be 
specified by the manufacturer in the installation and operation manuals 
being shipped to the commercial customer, and that if a rated air flow 
value for testing is not clearly identified, a value of 400 standard 
cubic feet per minute per ton shall be used.
    ISO 13256-1:1998 does not indicate which speed setting should be 
used to achieve specified airflow for a fan with more than one speed 
setting. Also, in some cases, the airflow rate and pressure conditions 
specified for a given ducted heat pump without an internal fan may not 
be achievable simultaneously. ISO 13256-1:1998 does not provide an 
approach for simultaneously achieving the specified airflow rate and 
pressure conditions in cases where the airflow may not be achievable 
below the maximum internal pressure drop. In the June 2018 RFI, DOE 
requested comment on whether indoor fans typically have multiple speed 
settings for WSHPs, and if so, how manufacturers choose the speed to 
use during testing. DOE also requested comment on how specified airflow 
is achieved if none of the speed settings produce that airflow at the 
specified internal or external static pressure. 83 FR 29048, 29051 
(June 22, 2018).
    AHRI and WaterFurnace commented that most WSHP fans have at least 
three speeds. (AHRI, No. 12 at p. 7; WaterFurnace, No. 7 at p. 7) Trane 
commented that their company offers single-speed and multi-speed units. 
(Trane, No. 8 at p. 4) AHRI, Trane, and WaterFurnace stated that as 
part of AHRI's certification program, the test facility utilizes the 
blower speed specified by the manufacturer in literature and submission 
data. (AHRI, No. 12 at p. 7; Trane, No. 8 at p. 4; WaterFurnace, No. 7 
at p. 7) AHRI and WaterFurnace further stated that manufacturers select 
an airflow that is advantageous for the specifications they are trying 
to achieve; for example, low airflows are beneficial for humidity 
removal. Id. The commenters also indicated that the AHRI WSHP/
Geothermal Operations Manual specifies steps to be taken if the 
manufacturer's specified airflow is not met with the initial fan 
settings, which include reducing ESP to a minimum value set forth in 
the AHRI WSHP/Geothermal Operations Manual. Id.
    AHRI acknowledged that in some cases, the airflow rate and pressure 
conditions specified by ISO 13256-1:1998 for a given ducted heat pump 
without an internal fan may not be achievable simultaneously. As an 
example, AHRI described a scenario in which the manufacturer-specified 
airflow may not be achievable below the maximum internal pressure drop 
specified in section 4.1.5.3 of ISO 13256-1:1998. AHRI stated that ISO 
13256-1:1998 does not provide an approach for simultaneously achieving 
the specified airflow rate and pressure conditions in such a case. 
(AHRI, No. 12 at p. 7) In such cases, AHRI and WaterFurnace stated that 
provisions in Appendix B of the AHRI WSHP/Geothermal Operations Manual 
are used that permit a tolerance for achieving the specified airflow 
within 10 percent of the manufacturers specified flow rate. (AHRI, No. 
12 at p. 7; WaterFurnace, No. 7 at p. 6)
    On this topic, DOE notes that the provisions of ISO 13256-1:2021 
are equivalent to those in ISO 13256-1:1998 for setting airflow of non-
ducted units and ducted units without internal fans. For ducted units 
with internal fans, ISO 13256-1:2021 provides additional specifications 
beyond those in ISO 13256-1:1998. Table 1 of ISO 13256-1:2021 provides 
minimum ESP values and explains that airflow should be set

[[Page 53323]]

as specified by the manufacturer with an ESP greater than or equal to 
the minimum ESP value set forth in ISO 13256-1:2021. For units with 
non-constant airflow fans and adjustable speed, ISO 13256-1:2021 states 
that the speed may be adjusted as needed to the lowest speed that 
provides at least the minimum ESP at the specified airflow rate. In 
cases where the airflow rate cannot be maintained within tolerance with 
an ESP greater than or equal to the minimum ESP, the test must be run 
at the airflow achieved with an ESP equal to the minimum ESP.
    As noted in section III.F.1.a of this document, DOE is proposing to 
adopt the minimum ESP requirements in Table 7 of AHRI 340/360-2022 and 
condition tolerances in Table 6 of AHRI 340/360-2022. For the reasons 
that follow, DOE has tentatively concluded that AHRI 340/360-2022 is 
superior to available alternatives in terms of these objectives. To 
start, DOE has tentatively determined that more specification than 
provided in ISO 13256-1:1998 is needed to ensure consistent and 
repeatable setting of airflow and ESP for testing, thereby ensuring the 
representativeness of the results. For example, ISO 13256-1:1998 does 
not specify what to do in certain circumstances when instructions 
provided are unclear or conflict (e.g., if no fan control setting is 
certified and multiple combinations of ESP and fan speed can provide 
the manufacturer-specified airflow). Although ISO 13256-1:2021 provides 
more specification than ISO 13256-1:1998 for setting airflow in ducted 
units with an internal fan, it still does not address situations in 
which instructions are missing, are unclear, or conflict. In addition, 
neither version of the ISO test procedure specifies an upper tolerance 
on ESP for ducted units. As such, further detail than what is provided 
in ISO 13256-1:1998 and ISO 13256-1:2021 is warranted. Furthermore, the 
AHRI WSHP/Geothermal Operations Manual includes some provisions on fan 
settings, but these provisions are likewise insufficient for setting 
airflow and ESP with minimum ESPs and condition tolerances, as that 
manual relies on communication and agreement between the manufacturer 
and AHRI in situations in which both ESP and airflow tolerances cannot 
be met. Such approach is inappropriate in a regulatory context.
    Therefore, as stated previously in this NOPR, DOE is proposing to 
incorporate by reference AHRI 340/360-2022, including adoption of 
sections 6.1.3.3 through 6.1.3.5, which specify a 3 percent condition 
tolerance for airflow rate, a -0.00/+0.05 in H<INF>2</INF>O condition 
tolerance for ESP, and instructions on setting airflow and ESP during 
testing. These sections additionally provide guidance on what to do 
during testing if one or both of the conditions cannot be met. DOE 
preliminarily finds that these provisions would improve test 
repeatability, provide test conditions that are more representative of 
field operation, and appropriately address the issue where none of the 
speed settings produce the specified airflow at the specified internal 
or external static pressure.
    DOE notes, however, that the relevant provisions in AHRI 340/360-
2022 were generally developed for ducted units with continuously 
variable-speed fans. Accordingly, additional provisions specific to 
testing ducted units with discrete-step fans and non-ducted units are 
necessary. The following sub-sections discuss the proposed additional 
provisions for such WSHPs.
    Issue 11: DOE requests comment on the proposed adoption of 
provisions from AHRI 340/360-2022 for setting airflow and ESP for WSHP 
testing.
(i) Ducted Units With Discrete-Step Fans
    Many ducted WSHPs have fans with discrete steps in speed. In 
situations where both airflow and ESP tolerances cannot be met, the 
instructions in section 6.1.3.5 of AHRI 340/360-2022 can result in 
ducted units with discrete-step fans operating with ESPs that are 
higher than the tolerance on the ESP requirements due to the difference 
in fan speed between each step.
    Section 6.1.3.5 of AHRI 340/360-2022 specifies that the measured 
airflow during test must be within 3 percent of the rated airflow and 
that the ESP during test must be within -0.00/+0.05 in H<INF>2</INF>O 
of the minimum ESP specified in Table 6. Section 6.1.3.5.2.4 specifies 
that for two adjacent fan control settings, if the lower setting is too 
low (such that ESP or airflow are lower than the tolerance range) and 
the higher setting is too high (such that ESP or airflow are higher 
than the tolerance range), then the higher fan control setting should 
be used. At this higher fan control setting, section 6.1.3.5.2.4 
specifies to maintain airflow within tolerance, which would result in 
an ESP higher than the +0.05 in H<INF>2</INF>O tolerance. However, 
WSHPs with discrete-step fans may have a limited number of fan control 
settings, such that testing at the higher fan speed in this case may 
result in testing with an ESP that significantly exceeds the minimum 
ESP requirement. For such units, in a case in which operating at the 
lower fan control setting with the ESP in tolerance results in an 
airflow slightly lower than 97 percent of the rated airflow, it would 
be more representative to test at the lower fan control setting with 
the airflow slightly below the 97 percent tolerance, rather than test 
at the higher fan control setting with an ESP potentially significantly 
exceeding the minimum ESP requirement. In such a case, the industry 
test procedures for SPVUs (AHRI 390-2021; section 5.7.3.4.1.4) and CAC/
HPs (AHRI 210/240-2023; section 6.1.5.1.6) allow airflow to drop to 90 
percent of the rated airflow while maintaining ESP within tolerance. 
DOE has tentatively concluded that adopting this approach for WSHPs 
would result in testing at conditions more representative of field 
applications.
    Therefore, for ducted units with discrete-step fans, DOE is 
proposing in section 3.2 of proposed appendix C1 instructions for 
setting the fan speed in the scenario in which: (1) tolerances for 
airflow and ESP cannot be met simultaneously, and (2) adjacent fan 
control settings result in airflow or ESP too low at the lower fan 
control setting and too high at the higher fan control setting. These 
proposed instructions specify to exclude sections 6.1.3.5.2.4 and 
6.1.3.5.3.2.3 of AHRI 340/360-2022, and to allow airflow to drop to 90 
percent of the specified airflow rate while maintaining ESP within 
tolerance. If ESP cannot be maintained within tolerance at 90 percent 
of the specified airflow rate, the proposed instructions specify to use 
the next highest fan speed and allow ESP to exceed the tolerance while 
maintaining airflow within tolerance.
    Issue 12: DOE requests comment on its proposed instructions for 
setting airflow and ESP for ducted WSHP units with discrete-step fans.
(ii) Non-Ducted Units
    DOE is aware that some WSHPs may be installed without indoor air 
distribution ducts in the field. Depending on the type of installation, 
the test method specified in ISO 13256-1:1998 differs; section 4.1.2 of 
ISO 13256-1:1998 specifies provisions for WSHPs installed without 
ducts, and section 4.1.3 of the standard specifies provisions for WSHPs 
installed with ducts. ISO 13256-1:1998 does not specify how to 
distinguish whether a unit is ducted or non-ducted. The provisions of 
ISO 13256-1:2021 are the same as those of ISO 13256-1:1998 in this 
regard.
    In the June 2018 RFI, DOE requested comment on the physical 
characteristics that distinguish ducted and non-ducted WSHPs. DOE also 
requested comment

[[Page 53324]]

on whether any WSHP models can be installed either with or without 
indoor distribution ducts, and if such models exist, DOE requested 
comment on whether manufacturers test these models to the non-ducted 
provisions in section 4.1.2 of ISO 13256-1:1998 or the ducted 
provisions in section 4.1.3 of ISO 13256-1:1998, or whether these 
models are tested using both provisions of section 4.1.2 and 4.1.3. 83 
FR 29048, 29050-29051 (June 22, 2018).
    In response to DOE's request for information, AHRI and WaterFurnace 
commented that WSHPs may be designed for use either with or without 
indoor air distribution ducts, and that while the specified test set-
ups are different, the non-ducted test simulates the conditions of the 
ducted test using a hood with zero static to accumulate the supply air 
for volumetric and enthalpy measurements. (AHRI, No. 12 at pp. 6-7; 
WaterFurnace, No. 7 at pp. 5-6)
    AHRI and WaterFurnace also commented that the majority of WSHPs are 
designed for use with ductwork but that there are some console units 
designed to ``free blow'' into the space with no ductwork at zero ESP. 
(AHRI, No. 12 at pp. 6-7; WaterFurnace, No. 7 at pp. 5-6) AHRI added 
that such non-ducted WSHPs typically include a tangential blower 
(similar to packaged terminal air conditioners) meant for low-static 
operation and free discharge into the conditioned space. (AHRI, No. 12 
at pp. 6-7) Trane commented that motor horsepower and fan size are 
designed to deliver zero ESP for non-ducted units and that units that 
are required to be ducted will require a different motor horsepower and 
fan size. (Trane, No. 8 at p. 4)
    Additionally, AHRI and Trane pointed out that WSHPs are certified 
to AHRI as either ``ducted'' or ``non-ducted'' and that the equipment 
is tested to the appropriate section of ISO 13256-1:1998. AHRI and 
WaterFurnace commented that there are no known WSHP models designed for 
both ducted and non-ducted application. (AHRI, No. 12 at pp. 6-7; 
WaterFurnace, No. 7 at pp. 5-6) In contrast, Trane stated that although 
it does not offer any equipment that can be installed as either ducted 
or non-ducted, there is a selection of WSHP equipment that is designed 
for both ducted and non-ducted applications. (Trane, No. 8 at pp. 3-4)
    Consistent with AHRI's, WaterFurnace's, and Trane's comments, DOE 
has identified some WSHPs, marketed as ``console units,'' which would 
operate without a duct. As noted previously, AHRI 340/360-2022 does not 
have any instructions for setting up airflow and ESP for non-ducted 
units. (AHRI 340/360-2022 is the industry test procedure for testing 
CUACs and there are no non-ducted CUACs.) Section 4.1.5 of ISO 13256-
1:1998 and section 5.1.5 of ISO 13256-1:2021 include provisions for 
setting airflow for non-ducted units at zero ESP, but the provisions in 
ISO 13256-1:1998 and ISO 13256-1:2021 do not specify the settings to 
use or how to address situations in which test procedure instructions 
are missing or conflict (also see discussion in section III.F.1.b of 
this NOPR). Therefore, DOE has tentatively concluded that specific 
provisions for non-ducted WSHPs are warranted.
    To address testing of non-ducted WSHPs, DOE proposes separate 
provisions for setting airflow and ESP for non-ducted units in section 
3.1 of proposed appendix C1. Consistent with ISO 13256-1:1998 and ISO 
13256-1:2021, DOE proposes that non-ducted units be tested at zero ESP, 
because non-ducted units would not be installed with ductwork in the 
field. DOE proposes that these provisions would apply to all units that 
are not configured exclusively for delivery of conditioned air to the 
indoor space without a duct(s). Units that are configured for delivery 
of conditioned air to the indoor space without a duct(s) would be 
required to use the provisions for setting airflow and ESP in section 
6.1.3 of AHRI 340/360-2022 and section 3.2 of proposed appendix C1, as 
applicable.
    DOE is proposing in section 3.1 of proposed appendix C1 that WSHP 
units that are not configured exclusively for delivery of conditioned 
air to the indoor space without a duct(s) would be tested with a target 
ESP of 0.00 in H<INF>2</INF>O (consistent with ISO 13256-1:1998 and ISO 
13256-1:2021) within a tolerance of -0.00/+0.05 in H<INF>2</INF>O in 
place of the ESP specified in Table 7 of AHRI 340/360-2022 (because the 
ESP requirements in AHRI 340/360-2022 are intended to reflect the 
pressure drop in ductwork for ducted units). The proposed ESP tolerance 
for non-ducted units aligns with the tolerance for ducted units in AHRI 
340/360-2022. Instead of the instructions for setting airflow and ESP 
in section 6.1.3.5 of AHRI 340/360-2022, DOE proposes that if both the 
ESP and airflow cannot be simultaneously maintained within tolerance 
for any test, to maintain the ESP within the required tolerance and use 
an airflow as close to the target value as possible (i.e., prioritize 
maintaining ESP in tolerance over maintaining airflow in tolerance). 
This is because testing an ESP of more than 0.05 in H<INF>2</INF>O 
would not be representative for a non-ducted unit which would not be 
installed with ductwork in the field. Finally, DOE proposes that if an 
airflow out of tolerance is used for the full-load cooling test, then 
the measured full-load cooling airflow is to be used as the target 
airflow for all subsequent tests that call for the full-load cooling 
airflow within a tolerance of +/-3 percent. These provisions are 
similar to those included for testing non-ducted units in other 
industry test standards for comparable categories of commercial air 
conditioners and heat pumps, such as AHRI 390-2021 for testing SPVUs.
    DOE has tentatively determined that these provisions would provide 
a representative and repeatable test procedure for non-ducted WSHPs, 
and that they would be appropriate for testing WSHPs because they are 
the generally accepted industry method used for testing similar 
equipment such as SPVUs. This proposed approach remedies some of the 
shortcomings identified with the current WSHP test procedure which 
incorporates by reference ISO 13256-1:1998.
    Issue 13: DOE requests comment on its proposal for setting airflow 
and ESP for non-ducted WSHP units.
2. Capacity Measurement
a. Primary and Secondary Methods
    The current DOE test procedure, through adoption of section 6.1 of 
ISO 13256-1:1998, specifies that total cooling and heating capacities 
are to be determined by averaging the results obtained using two test 
methods: the liquid enthalpy test method for the liquid side tests and 
the indoor air enthalpy test method for the air side tests. For non-
ducted equipment, section 6.1 of ISO 13256-1:1998 includes an option 
for conducting the air-side tests using the calorimeter room test 
method instead of the air enthalpy test method. Section 6.1 of ISO 
13256-1:1998 also specifies that, for a test to be valid, the results 
obtained by the two methods used must agree within 5 percent.
    In the June 2018 RFI, DOE discussed how ANSI/ASHRAE 37-2009 is 
similar to the test method in ISO 13256-1:1998, and that DOE was 
considering whether testing to ANSI/ASHRAE 37-2009 would be appropriate 
for WSHPs. DOE further discussed how ANSI/ASHRAE 37-2009 requires two 
capacity measurements for units with cooling capacity less than 135,000 
Btu/h; the first method of measurement (i.e., the primary method) is 
used as the determination of the unit's capacity, while the second 
measurement (i.e., the secondary method) is used to confirm

[[Page 53325]]

rather than to be averaged with the primary measurement (see section 
10.1 and Table 1 of ANSI/ASHRAE 37-2009). 83 FR 29048, 29052 (June 22, 
2018).
    In the June 2018 RFI, DOE requested information on whether one of 
the two capacity measurements prescribed in ISO 13256-1:1998 gives a 
consistently higher or lower result than the other, or whether one of 
the methods can be considered more accurate for a range of different 
WSHP configurations and models. Id. Additionally, DOE requested comment 
on whether the ANSI/ASHRAE 37-2009 approach for determination of rated 
capacity (i.e., using the primary method's measurement as the rated 
capacity rather than averaging the two capacity measurements) would 
result in more representative ratings than the ISO 13256-1:1998 
approach. Id.
    Trane commented that the capacity value measured by the liquid 
enthalpy method is generally higher than the value measured by the 
indoor air enthalpy method, stating that air-side measurements have 
more opportunity for losses than water-side measurements. (Trane, No. 8 
at p. 5) AHRI and WaterFurnace commented that the water side test is 
generally simpler to conduct and also more accurate than the air 
enthalpy method, because the uncertainties of measurement are much 
lower in the water-side calculations. (AHRI, No. 12 at p. 13; 
WaterFurnace, No. 7 at p. 11)
    AHRI, Trane, and WaterFurnace recommended continuing to use the 
average of the air-side and water-side measurements as the basis for 
capacity ratings. (AHRI, No. 12 at p. 13; Trane, No. 8 at p. 5; 
WaterFurnace, No. 7 at p. 11) AHRI and WaterFurnace stated that the 
current approach in ISO 13256-1:1998 represents a compromise that helps 
ensure best testing procedures. (AHRI, No. 12 at p. 13; WaterFurnace, 
No. 7 at p. 11) AHRI argued that the ANSI/ASHRAE 37-2009 approach does 
not yield more representative ratings compared to the ISO 13256-1:1998 
method. (AHRI, No. 12 at p. 13) Trane further asserted that the average 
of the methods is more accurate than the measurement from either single 
method alone. (Trane, No. 8 at p. 5) AHRI and WaterFurnace also stated 
that ANSI/ASHRAE 37-2009 does not include the liquid enthalpy method of 
test required on the source side for all WSHPs. (AHRI, No. 12 at p. 13; 
WaterFurnace, No. 7 at p. 10)
    In response, DOE notes first that the capacity measurement 
provisions in section 7.1 of ISO 13256-1:2021 differ from those in 
section 6.1 of ISO 13256-1:1998 in several ways. Instead of averaging 
the two capacity measurements, section 7.1 of ISO 13256-1:2021 
specifies that the capacity rating is equal to the value determined 
from the air side (referred to as the load side in ISO 13256-1:2021), 
consistent with the approach used in section 10.1.2 of ANSI/ASHRAE 37-
2009. ISO 13256-1:2021 also does not allow use of the calorimeter 
method in place of the indoor air enthalpy method for measuring 
capacity on the load side, but section 7.1 of ISO 13256-1:2021 allows 
use of the refrigerant enthalpy method for configurations that cannot 
use the indoor air enthalpy method. Section 7.1 of ISO 13256-1:2021 
continues to require the liquid enthalpy method for measuring capacity 
on the liquid side (referred to as the source side in ISO 13256-
1:2021). Section 7.1 of ISO 13256-1:2021 also continues to require the 
two capacity measurements to agree within 5 percent for the test to be 
valid.
    As discussed in section III.D.2 of this NOPR, DOE proposes to adopt 
specific sections of AHRI 340/360-2022 for use in the WSHP test 
procedure, including section E6, which specifies test methods for 
capacity measurement. Section E6.1 of AHRI 340/360-2022 requires use of 
the indoor air enthalpy method specified in section 7.3 of ANSI/ASHRAE 
37-2009 as the primary method for capacity measurement. This is the 
measurement used to determine capacity, as required in section 10.1.2 
of ANSI/ASHRAE 37-2009. Section E6.2.2 of AHRI 340/360-2022 requires 
use of one of the applicable ``Group B'' methods specified in Table 1 
of ANSI/ASHRAE 37-2009 as a secondary method for capacity measurement. 
The group B methods that are applicable to WSHPs are the outdoor liquid 
coil method (similar to the liquid enthalpy method included in the 1998 
and 2021 versions of ISO 13256-1), the refrigerant enthalpy method, and 
the compressor calibration method. Section E6.4.2 of AHRI 340/360-2022 
requires that the primary and secondary measurements match for full-
load cooling and heating tests, within 6 percent of the primary 
measurement. No match is required between primary and secondary 
measurements for part-load cooling tests.
    Regarding commenters' claims that ANSI/ASHRAE 37-2009 does not 
include the liquid enthalpy method of test required on the source side 
for all WSHPs, as discussed, ANSI/ASHRAE 37-2009 does include a liquid 
enthalpy method of test. The liquid enthalpy method is referred to as 
the outdoor liquid coil method in section 7 of ANSI/ASHRAE 37-2009, and 
it provides a measurement of liquid enthalpy that is similar to the 
measurement provided by the liquid enthalpy method in normative 
appendix C of ISO 13256-1:1998. As discussed, Table 1 of ANSI/ASHRAE 
37-2009 specifies three secondary capacity measurement methods (i.e., 
outdoor liquid coil, refrigerant enthalpy, and compressor calibration 
methods) that may be used to conduct the secondary measurements that 
are required for testing WSHPs with cooling capacity less than 135,000 
Btu/h, rather than requiring the outdoor liquid coil for all water-
source units (as is the case in section 6.1 of ISO 13256-1:1998). Table 
1 of ANSI/ASHRAE 37-2009 also specifies the applicability of each 
secondary capacity method based on the configuration of the unit being 
tested. This specification of applicable secondary capacity measurement 
methods in ANSI/ASHRAE 37-2009 ensures that the chosen secondary 
capacity measurement is accurate because the outdoor liquid coil method 
in ANSI/ASHRAE 37-2009 is not applicable for certain unit 
configurations in which the compressor heat would not be sufficiently 
accounted for. Specifically, section 7.6.1.2 and note g to Table 1 of 
ANSI/ASHRAE 37-2009 specify that the outdoor liquid coil method may not 
be used if the system has a compressor that is ventilated by outdoor 
air or a remote outdoor compressor that is not insulated per section 
7.6.1.2 of ANSI/ASHRAE 37-2009. Section III.F.2.b of this NOPR includes 
further discussion on this topic.
    As part of DOE's proposal generally to adopt the test provisions in 
section E6 of AHRI 340/360-2022, DOE is proposing to adopt the 
provisions for measuring capacity in AHRI 340/360-2022 instead of those 
in section 6.1 of ISO 13256-1:1998. Using the indoor air enthalpy 
measurement as the measurement of capacity ensures that actual output 
of the WSHP--the cooling or heating of air--is used as the measure of 
capacity. The approach used in section 6.1 of ISO 13256-1:1998, in 
which the indoor air enthalpy measurement is averaged with the liquid 
enthalpy measurement, has the potential to result in capacity values 
that are higher than the actual delivered capacity because of heat 
transfer to/from the ambient air (either through heat transfer through 
the WSHP cabinet walls or air leakage). This potential is consistent 
with Trane's comment that the capacity value measured by the liquid 
enthalpy method is generally higher than the value measured by the 
indoor air enthalpy method. In addition,

[[Page 53326]]

the approach used in section E6 of AHRI 340/360-2022 is consistent with 
the approach in section 7.1 of ISO 13256-1:2021, in that the indoor air 
enthalpy measurement is used as the capacity measurement in ISO 13256-
1:2021. It is also consistent with the industry test procedures for 
other categories of air conditioning and heating equipment (e.g., AHRI 
Standard 1230, AHRI Standard 390, and AHRI Standard 210/240). 
Therefore, DOE has tentatively concluded that it is more representative 
for the capacity rating of WSHPs to be determined with the indoor air 
enthalpy method, and for the secondary measurement to serve only as a 
verification of the indoor enthalpy measurement, rather than being 
averaged with the indoor air enthalpy method result to determine the 
capacity rating.
    The proposed provisions do not permit use of the calorimeter method 
or refrigerant enthalpy method in place of the indoor enthalpy method, 
which is allowed in section 6.1 of ISO 13256-1:1998 and section 7.1 of 
ISO 13256-1:2021. However, DOE has tentatively concluded that 
alternatives to the indoor air enthalpy method are not necessary 
because DOE is not aware of any WSHPs that are unable to use the indoor 
enthalpy method as specified in ANSI/ASHRAE 37-2009 (with additional 
provisions in AHRI 340/360-2022).
    The proposed provisions also allow a difference in capacity 
measurements of up to 6 percent in section E6.4.2 of AHRI 340/360-2022 
instead of the 5 percent allowed in section 6.1 of ISO 13256-1:1998. 
DOE has tentatively concluded that this reduces burden while still 
ensuring accurate measurements of indoor air enthalpy. Once again, this 
proposal is consistent with the industry test procedures for other 
categories of air conditioning and heating equipment (e.g., AHRI 
Standard 1230, AHRI Standard 390, and AHRI Standard 210/240).
    Issue 14: DOE requests comment on its proposed approach to adopt 
the provisions in AHRI 340/360-2022 and ANSI/ASHRAE 37-2009 regarding 
primary and secondary capacity measurements.
b. Compressor Heat
    DOE has identified split-system WSHPs available on the market. For 
at least one of these split systems WSHPs, the unit containing the 
compressor is intended for either indoor or outdoor installation. The 
installed location of the compressor, in relation to the conditioned 
space and other system components, impacts the capacity of a WSHP 
system and the provisions necessary for accurately measuring system 
capacity due to the generation of heat during compressor operation.
    As discussed in section III.F.2.a of this NOPR, the current DOE 
test procedure, through adoption of ISO 13256-1:1998, requires use of 
two methods to measure space-conditioning capacity provided by a WSHP. 
One of these methods, the indoor air enthalpy method (see normative 
annex B of ISO 13256-1:1998), measures capacity directly by measuring 
mass flow and enthalpy change of the indoor air.\21\ The second method, 
the liquid enthalpy test method (see normative annex C of ISO 13256-
1:1998), measures heat transferred at the liquid coil. The liquid 
enthalpy measurement is adjusted by adding or subtracting the total 
unit input power (including the compressor input power) from the 
measured liquid side capacity in the heating or cooling mode tests, 
respectively, using the equations in sections C3.1 and C3.2 of ISO 
13256-1:1998.
---------------------------------------------------------------------------

    \21\ The alternative calorimeter room test method (see normative 
annex E of ISO 13256-1:1998), allowed to be used instead of the 
indoor air enthalpy method for non-ducted WSHPs, also measures 
indoor space-conditioning capacity directly.
---------------------------------------------------------------------------

    The liquid enthalpy adjustment in sections C3.1 and C3.2 of ISO 
13256-1:1998 assumes that all compressor heat is absorbed and 
ultimately transferred to the conditioned space, thereby increasing 
heating capacity or decreasing cooling capacity. However, this fails to 
account for any heat transferred from the compressor or other 
components to their surroundings that does not contribute to space 
conditioning. For example, in the case of a split-system WSHP with an 
uninsulated compressor/liquid coil section installed outdoors, the air 
that absorbs compressor heat would not directly affect the conditioned 
space. In this case, adding or subtracting the entire compressor input 
power to or from the capacity calculated based on liquid temperature 
change likely overestimates the impact of compressor power input on the 
indoor-side capacity that is calculated using the liquid enthalpy-based 
method.
    In the June 2018 RFI, DOE requested comment on whether there are 
split-system WSHP models on the market for which the unit containing 
the compressor is intended only for outdoor installation or only for 
indoor installation. DOE further requested comment on manufacturers' 
practices for testing split-system WSHPs for which the compressor is 
not housed in the section containing the indoor refrigerant-to-air 
coil, including which test rooms are used for the compressor section, 
and whether any adjustments are made to properly account for the 
compressor heat. 83 FR 29048, 29053 (June 22, 2018).
    In response to DOE's requests for comment, AHRI, Trane, and 
WaterFurnace commented that accounting for compressor heat would not be 
a relevant issue because there are very few, if any, split-system WSHPs 
in the commercial market. (AHRI, No. 12 at p. 13; Trane, No. 8 at p. 5; 
WaterFurnace, No. 7 at pp. 11-12) The CA IOUs commented that, based on 
the AHRI directory, 90 percent of WSHPs are single-package units. (CA 
IOUs, No. 9 at p. 2)
    As stated previously, DOE has identified a number of split-system 
WSHPs, several of which are certified in the DOE Compliance 
Certification Database, and the Federal test procedure \22\ applies to 
any WSHP that meets DOE's definition of a WSHP. Further, because split-
system WSHPs are available on the market, test procedure provisions are 
needed for testing them, regardless of their share of the WSHP market.
---------------------------------------------------------------------------

    \22\ Currently, the DOE test procedure applies to all WSHPs with 
a capacity less than 135,000 Btu/h. However, DOE is proposing in 
section III.A of this NOPR to increase the scope of the Federal test 
procedure to include all WSHPs with a capacity less than 760,000 
Btu/h.
---------------------------------------------------------------------------

    Sections D.4 and D.5 of ISO 13256-1:2021 use the same adjustment of 
the liquid enthalpy method as sections C3.1 and C3.2 of ISO 13256-
1:1998. Thus, ISO 13256-1:2021 provides no additional methods to 
address compressor heat for split systems with the compressor in the 
liquid coil section.
    As discussed in section III.D.2 of this NOPR, DOE proposes to adopt 
specific sections of AHRI 340/360-2022 in its test procedure for WSHPs. 
AHRI 340/360-2022 in turn references the test method in ANSI/ASHRAE 37-
2009. Sections 6.1.3 and 6.1.5 of ANSI/ASHRAE 37-2009 contain 
provisions for addressing compressor heat in the indoor air enthalpy 
method that are similar to the provisions in sections F7.3 and F7.5 of 
ISO 13256-1:1998. For secondary capacity measurements, however, ANSI/
ASHRAE 37-2009 has provisions that go beyond the provisions in ISO 
13256-1:1998 to ensure that capacity is measured more accurately than 
it is by ISO 13256-1:1998, as discussed in the following paragraphs.
    Section 7.6 of ANSI/ASHRAE 37-2009 includes a liquid enthalpy 
measurement method (referred to as the

[[Page 53327]]

``outdoor liquid coil method'' and applicable to both single-package 
units and split systems) that is similar to the method in normative 
annex C of ISO 13256-1:1998 in that it adjusts the liquid enthalpy 
measurement by the total input power of the WSHP. For split-system 
WSHPs, ANSI/ASHRAE 37-2009 includes the outdoor liquid coil method, the 
refrigerant enthalpy method, and the compressor calibration method as 
options for conducting the secondary measurements that are required for 
testing WSHPs with cooling capacity less than 135,000 Btu/h. However, 
ANSI/ASHRAE 37-2009 limits use of the outdoor liquid coil method so 
that it does not apply for certain unit configurations in which the 
compressor heat would not be sufficiently accounted for. Specifically, 
Section 7.6.1.2 and note g to Table 1 of ANSI/ASHRAE 37-2009 specify 
that the outdoor liquid coil method may not be used if the system has a 
compressor that is ventilated by outdoor air or a remote outdoor 
compressor that is not insulated per section 7.6.1.2 of ANSI/ASHRAE 37-
2009. These limits on the applicability of the outdoor liquid coil 
method in ANSI/ASHRAE 37-2009 minimize discrepancy between measurements 
from the indoor air enthalpy method and liquid coil method by ensuring 
that either: (1) compressor heat is captured in indoor air enthalpy 
measurements, or (2) compressor heat loss to outdoor air is minimal 
because the compressor is sufficiently insulated.
    For split-system WSHPs for which the outdoor liquid coil method in 
ANSI/ASHRAE 37-2009 cannot be used (i.e., the system has a compressor 
that is ventilated by outdoor air or a remote outdoor compressor that 
is not insulated per section 7.6.1.2 of ANSI/ASHRAE 37-2009), ANSI/
ASHRAE 37-2009 requires the use of either the refrigerant enthalpy 
method specified in section 7.5 of ANSI/ASHRAE 37-2009 or the 
compressor calibration method specified in section 7.4 of ANSI/ASHRAE 
37-2009. For both of these methods, measured capacity is adjusted by 
only the input power of the indoor section of the WSHP, and not the 
total input power. Therefore, for both methods, the compressor heat 
lost to outdoor air from a remote outdoor compressor or compressor 
ventilated by outdoor air would appropriately be excluded from capacity 
measurements, similar to the indoor air enthalpy method. Therefore, for 
WSHPs with those configurations, the refrigerant enthalpy method and 
compressor calibration method specified in sections 7.5 and 7.4 
(respectively) of ANSI/ASHRAE 37-2009 would provide a more 
representative result as compared to the approach used in normative 
annex C of ISO 13256-1:1998 (i.e., liquid enthalpy method).
    Based on the discussion in the prior paragraphs, DOE tentatively 
concludes that the proposed test procedure would provide an accurate 
secondary measure of capacity for all equipment configurations and 
would provide a more representative secondary measure of capacity than 
ISO 13256-1:1998 or ISO 13256-1:2021 for split systems with the 
compressor mounted in the outdoor section.
3. Cyclic Degradation
    As discussed in section III.D.2 of this NOPR, DOE proposes to adopt 
specific sections of AHRI 340/360-2022 in its test procedure for WSHPs, 
including section 6.2.3.2 of that industry standard. Equation 4 in 
section 6.2.3.2 of AHRI 340/360-2022 is used to calculate part-load EER 
for a unit that needs to cycle in order to meet the 75-percent, 50-
percent, and/or 25-percent load conditions required for the IEER 
metric. Cycling is the term used to describe the process in which a 
unit's compressor is repeatedly turned off and on in order to meet a 
load that is lower than the unit's capacity at its lowest compressor 
stage.
    Equation 4 of AHRI 340/360-2022 multiplies only the compressor 
power and condenser section power by the load factor and the 
coefficient of degradation, while the indoor fan power and controls 
power are not multiplied by these variables. This means that equation 4 
of AHRI 340/360-2022 assumes that the indoor fan continues to operate 
when the compressor cycles off. DOE understands that the draft of AHRI 
600 has an equation similar to equation 4 of AHRI 340/360-2022, but the 
equation in draft of AHRI 600 assumes that the indoor fan stops 
operating whenever the compressor cycles off.
    As discussed previously in section III.E.4 of this NOPR, 
stakeholders provided comment regarding the operation of a WSHP, 
including operation of the fan, in modes other than mechanical heating 
and cooling. (AHRI, No. 12 at pp. 4-5, 9; WaterFurnace, No. 7 at pp. 3, 
9; Trane, No. 8 at pp. 2, 5) These comments on fan operation 
specifically referred to operation when there is no heating or cooling, 
but they might also be applicable to the issue of fan operation during 
compressor cycling under part-load conditions. Certain comments 
indicated that it is common for WSHP fans to operate continuously to 
provide air circulation or ventilation air. (AHRI, No. 12 at pp. 4-5; 
WaterFurnace, No. 7 at p. 3) Continuous operation of WSHP fans 
indicates that the fan would continue to run when the compressor cycles 
off.
    In addition, the cyclic degradation approach used in equation 4 of 
AHRI 340/360-2022 is used in the IEER metric for multiple other 
categories of commercial HVAC equipment, indicating that it is common 
for the indoor fan to continue operating while the compressor cycles 
off. AHRI 340/360-2022 is used for testing CUAC/HPs, and equation 4 of 
AHRI 340/360-2022 is equivalent to equation 10 of AHRI 1230-2021 (which 
is used for testing VRF multi-split systems) and equation 3 of AHRI 
390-2021 (which is used for testing SPVUs). These other equipment 
categories typically operate in similar environments to WSHPs (i.e., 
commercial buildings with ventilation air requirements). Similar to 
these other equipment categories, DOE acknowledges that not all WSHPs 
are installed in the same manner, and the Department understands that 
fans operate continuously for many, but not all, installed WSHPs. 
However, comments received suggest that continuous operation of fans is 
representative of operation of many WSHPs, and adopting a cyclic 
degradation approach that assumes continuous fan operation is 
consistent with the IEER approach used for other equipment categories 
that use the IEER metric.
    For the foregoing reasons, DOE has tentatively concluded that the 
cyclic degradation approach in equation 4 of AHRI 340/360-2022 is 
representative of WSHP operation. Therefore, DOE is proposing to adopt 
the approach in AHRI 340/360-2022 in proposed appendix C1. DOE is also 
proposing in section 5.1.2.5.4 of proposed appendix C1 that the same 
approach for cyclic degradation be used when determining IEER through 
interpo

[…truncated; see source link]
Indexed from Federal Register on August 30, 2022.

This is legal information, not legal advice. Laws vary by jurisdiction and change frequently. Always verify current law with official sources and consult a licensed attorney in your jurisdiction for advice on your specific situation.